Park West CC(02-2)-CS060412
Apr 12 06 04:08p
c; yt-1;&/4.-(,jd y
c" :J1t;~
THE CITY OF
corrELL
~~-*~~~
;r~~
.\: <\ S I l>
MEMORANDUM
TO
Larry Davis, Englneenng
FROM:
Danny Hightower, Public Works
DATE:
Apnl 12, 2006
REF:
Parkwest Commerce Center, Lot 2R-3, Blk 2 (MaJestic)
,.,
Need b10ckmg in vaults under valves
Vault lIds need lock latch on top
Pamt vault hds blue
Need fire hydrant makers m street; blue to mark fire hydrant
Pamt all fire hydrant valve stack lids red
Chams on all fire hydrant caps
Sewer manholes (3) need chImney seals and ram pans
Mark FHV on curb m red at all fire hydrant valves
:Yfark ML V on curb m blue at all main Ime valves
Two mam lme valves need 6 feet extensIOn on Alrlme
Vault on AirlIne needs dramage around vault
Two domestic and one Imgahon - mark on curb in blue and pamt lids blue
Fire hydrant valve south ofbuildmg at dock dnve - valve not workmg
Pamt building fire line valves stack lids red
Water mam hne valve north of building at truck dock not workmg
Sewer manholes - check grout around pIpe at bottom of all manholes
Turn fire hydrant north ofbUlldmg at truck dock, not to prmts
Mark MH on curb m red at three manholes and pamt lids red
Paperwork on all DC's 2 domestic and lITIgation, 2 vaults, test DC
3
4
5
6
7
8
9
10
II
12
[3
14
15
16
17
18
19
~~9;2-~5~5~~~t"r,toche~k~unCh~ ~ J-JJ
Z I' f/S"i3u;/~/~
1I.Jl.~
p. 1