Loading...
SS9901-LR060126A T Construction Materials Testing and Environmental Consulting Texas CMT Inc., 10044 Monroe Drive Dallas, Texas 75229 (214) 352 -6957 Fax (214) 352.6972 0 www.texascmt.com GENERAL REPORT Report Hate January 26, 2006 c liem City of Coppell pr'llecr DeForest Lift Station Identification Coating Observations Test Date January 17 K 18, 2006 General Report No 2 Project No 20-5 0126 high voltage holiday detector observation and an adhesion test observation were performed on the �,\ -et well coating today with results as follows A I hgh voltage holiday detector observation 1 A Sterns Holiday Detector set at 9,000 volts was used for this observation Repair areas from the previous observation and areas coated after scaffold removal were observed today Holidays found were marked with black Marks -A -Lot. Most holidays are pinhole type and are found below the low level alarm height. 13 Adhesion Test 1 Additional dollies were glued in place on ;the north and east walls on 1/17/06 using Loctite glue 2 1/18/06 -Dollies were scribed around down to the concrete prior to pulling them with an Elcometer 0 -1,000 psi adhesion tester Results are as follows a East wall - 300 psi - 60% Coating cohesion /40% Concrete b North wall - 275 psi - 98% Concrete / 2% Coating Cohesion r CC Mr Risk (_ Dill - City otCoppcll tilr Todd(_ I lull- Canlcr Cunstnictuai Lo. ti15. Lrika k.luopir- "turner (_ollie& 13raden �fi- Iire.n.d I t. �' cud lil.,,,l1h, d ,.cd ,I.I — C Ml: k" n..... i �,� ��� u, rl .,...I I I. i "u ... mld �..i .ill i.. �. Iii Jl' I.,..da"'l - 1--i d I I�...u. u� II d ..',"t Ih, q — I.."1'11 uiil�.i. ulLir