GENERAL REP
Report gate January 1 2, 2006 Test Date December 22, 2005
C Dent Cit" of Coppell General Report No 1
Project DeForest Lift Station Project No 205 - 0126
Identification Coating Observations
A coating observation was performed today at the above noted project with results as follows
A High voltage holiday test (Section 09902, Para 3 05 A 2)
1 The high voltage holiday detector observation was performed with a Spy Model 925,
Serial # 1024 gage Voltage was set at 9 500 volts Pinhole holidays found were marked
, ,N ith black Marks -A -Lot. More holdays were found near the floor elevation and up
about 4' then anywhere else All holidays found were marked.
B Bond Strength (Section 09902, para 3 05 A 3)
1 Adhesion test dollies were glued in place on 12 -22 -05 using Loctite glue
2 Dollies were scribed around to substrate and then pulled with an Elcometer 0 -1000 PSI
gage Results as follows
Location Dolly # PSI Failure Mode
Material Applied
a Ceilmg
1 425
80% Coating Cohesion/
12/16/2005
20 Concrete Cohesion
b North Wall
2 325
100% Coating Cohesion
12/16/2005
c South Wall
3 400
50% Coating Cohesion/
12/17/2005
50% Concrete Cohesion
d East Wall
5 325
70% Coating Cohesion/
12/17/2005
30% Glue Failure
d West Wall 4 600 80% Coating Cohesion/ 12/17/2005
20% Glue Failure
cc Mr RickODcll - City ofCoppell
Mr 'Dodd C ii0n'- Canfcr Construction Co.
MS Erika K. Cooper- Turner Collie & Braden