Loading...
BEI Properties-LR060206Concrete Compression Test Report ~~~ ENGINEERING, INC. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Cooper General Contractors Project: Bfoom Retail Center Report Distribution. (1) Cooper General Contractors (1) Ray Mansoory (1) Ciry of Coppell CMJ Report No. 502-5167-016 Report Date. 02/06/2006 Specifications Test Data Strength 3500 psi @ 28 Days Placement Date 01/25/2006 Slump 3 in min 5 in max Sampled By Daniel Bohon Air Content 3 % min 6 % max Weather Clear/Light Wind Concrete Temperature 55° F min 90° F max Supplier/Mix Beall/102 Ambient Temperature Na Air Content Method ASTM C231 Fie#d Qata et#01. Ticket Number 13657163 Time Batched: 11 17 Time Sampled 11:50 Slump• 6 in* Air Content: 3 4 % Unit Weight: N/A Concrete Temperature: 71 ° F Ambient Temperature 62° F Yardage (c.y ): 20 of 90 Placement Location: Paving, Entire Parking Lot & Fire Lane, Including Entry Sample Location. 24' W & 20' N of Sta 0+64 11 An asterisk (*) appears next to field data which does NOT meet specifications. Concrete Compression Test Results Cylinder Age Max Load Area i Stren th si Set # # Test Date n.) (days) (Ibs. force) (sq. (p 01 BRC01250601 02/01/2006 7 142380 28.27 5040 01 BRC01250602 02/22/2006 28 01 BRC01250603 02/22/2006 28 01 BRC01250604 Hold Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231 " Non-Compliant: Contractor Notified 5 Gallons of Water Added On-Site, approved by' Gus w/Cooper Construction CMJ Engineering, Inc Fracture Type E-columnar LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The .test results do not pertain to any other samples, items or areas regardless of similarity Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. °~ Page 1 of 1 Concrete Compression Test Report ~~ ENGINEERING, INC 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Cooper General Contractors Project: Bloom Retail Center CMJ Report No.. 502-5167-017 Report Date: 02!06/2006 Report Distribution. (1) Cooper General Contractors (1) Ray Mansoory (1) City of Coppell Strength Slump Air Content Concrete Temperature Ambient Temperature 3000 psi @ 28 Days 3 in min 5 in max 3%min6%max 55° F min 90° F max n/a Placement Date Sampled By Weather Supplier/Mix Air Content Method Test Data 01 /25/2006 Daniel Bohon Clear/Light Wind Beal Il102 ASTM C231 -~ ~ Fielt}Data~Sef#02 Ticket Number Slump Concrete Temperature Placement Location. 13657192 4 in 72° F Paving, City Approach Time Batched: 02:00 Air Content: 3.9 Ambient Temperature: 75° F Time Sampled: 02:20 Unit Weight: N/A Yardage (c.y ): 110 of 110 Sample Location: Concrete Compression Test Results Cylinder Age Max Load Area i Ib f Stren th i Set # # Test Date orce) (sq. n.) s. (days) ( (ps 02 BRC01250601 02/01/2006 7 160360 28.27 5670 02 BRC01250602 02/22/2006 28 02 BRC01250603 02/22/2006 28 02 BRC01250604 Hold Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231 0 Gallons of Water Added On-Site Drive Approach CMJ Engineering, Inc Fracture Type E-columnar LIMITATIONS' The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. ui Page 1 of 1