Loading...
SS9901-LR060619rim AT iexas CMT Inc. Construction Materials Testing and Environmental Consulting 10044 Monroe Drive Dallas, Texas 75229 (214) 352 -6957 Fax (214) 352 -6972 www.texascmt.com GENERAL REPORT Report Date June 19, 2006 Client City of Coppell Project DeForest Lift Station Identification Adhesion Test Test Date: June 6, 2006 General Report No 4 Project No 205 -0126 An adhesion test was performed on the walls coated with the Raven 405 material. Dollies were glued in place on 6 -5 -06 using Loctite glue. Dollies were scribed around down to concrete today prior to performing adhesion test. An Elcometer 0 -1,000 psi gage was used to pull dollies Results Location 1 ) East Wall (Existing Concrete) 2 ) South Wall (Existing Concrete) 3 ) East Wall of Trough (New Concrete) 4.) Bottom Wall of Trough (New Concrete) PSI Failure Mode 300 98% Concrete /2 % Coating Cohesion 175 100% Concrete 200 100% Concrete 350 100% Concrete According to ASTM standard 3 pulls make an accurate test. 3 dollies pulled to concrete Coating adhesion is acceptable. CC. Mr Rick O'Dell - City of Coppell Mr Todd C Hoff - Canfer Construction Co. Ms. Erika K. Cooper - Turner, Collie & Braden Our I.M. sad reports are for the escl.&v use of the cbM m whom they area Wm—d sod null M d reproduced widrout the fWl approval of Tens CMT la. The me of our name must receive our prior wriw o approval. Our letters and repays apply only w We sample coned ad/or inspected sod arc not oecewrhy indicative of the quantities of apparently ideatical or similar produce. k T\ Construction Materials Testing and Environmental Consulting �°exas CMT Inc. 10044 Monroe Drive n Dallas, Texas 75229 (214) 352 -6957 Fax (214) 352 -6972 1 www texascmt.com GENERAL REPORT Report Date June 19, 2006 Test Date: June 5, 2006 Client City of Coppell General Report No 3 Project DeForest Lift Station Project No 205 -0126 Identification Coating Observations A high voltage holiday detector observation was performed on the walls, ceiling and trough areas coated with the Raven 405 material today. Detector was set at 9,000 volts. Numerous pinhole holidays were found and marked. 4 block outs at bottom of trough and one area around pipe in ceiling are not yet coated. 4 dollies for adhesion test were glued in place and will be pulled tomorrow. Holiday detector used was DE Sterns Co Model 14/20 regulated voltage pulse type holiday detector cc: Mr Rick O'Dell - City of Coppell Mr Todd C. Hoff - Canfer Construction Co. Ms. Erika K. Cooper - Turner, Collie & Braden Our leers and mpom are for the eulusive use of the chew W whom dwy arc addressed sod shall =be mpomir-d widmut the full approval ofYem CMT. Ice. The uw of our mme mun mews our prior wrim n appr w sl. Our kden and reports apply only m the sample tetrad and/or ingwwd and arc or, oettsurily indiudw of the gmwities of apparently Wand W or similar products.