GENERAL REPORT
Report Date June 9, 2006 Test Date- June 1, 2006
Client City of Coppell General Report No. 4
Project DeForest Lift Station Project No. 205 - 0126
Identification Coating Observation Page 1 of 1
ENVIRONMENTAL CONDITIONS COATING MATERIAL
Date:
06/01/2006
Material Used:
Raven 405
Time:
1.00 pm
Batch No.
Wet film thickness readings - first coat
Dry Bulb:
85
Part A
522602
Wet Bulb:
75
Part B
516601
Humidity
63%
Part C
N/A
Dew Point:
71
Thinner
N/A
Surface Temp:
84 -86
Color
White
VA eather
Partly cloudy, calm winds
Application method:
Plural Component Spray
DRY FILM THICKNESS
Area
Number of Readings
Low
High
Mean
Comments
Wet film thickness readings - first coat
20
65
100
80
Wet film thickness readings - second coat
25
60
80
70
DFT Gage Used. Wet Film Gage
Additional Information:
The concrete walls, ceiling and trough inside the lift station are being coated with the Raven 405 material today Surfaces were water
blast cleaned yesterday and allowed to dry overnight. The trough walls and floor were prime coated prior to the Raven 405 material
application. There are several block outs that will be coated at a later date. These are the 4 openings in trough floor and area around
pipe penetration. Remaining areas had the 405 material applied in two coats. The first coat was sprayed on and then troweled into
fi l l bug holes and uneven areas. Material was allowed to setup. Any pinhole areas were closed up. The second coat was then sprayed
over this. Wet film thickness readings were taken during application and met specified thickness requirement of 125 mils.
cc Mi Rick O'Dell -City of Coppell
Mr Todd C Hoff - Canfer Construction Co. R y�
Ms. Erika K. Cooper - Turner, Collie & Braden 1\ \\
Texas CMT, Inc. Reviewed
All letters and reports are for the exclusive use of the client to whom they are addressed and shall not he reproduced without the full approval of Texas CMT, Inc. he use of our tame must receive our prior written approval. Our letters and
reports apply only to the sarrple tested and/or observed and are not necessarily indicative of the quantities of apparently identical or similar products.