Concrete Compression Test Report
eM J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-137
Report Date: 09/29/2006
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
08/30/2006
Robert Dunnam
Clear/Light Wind
LMC/1551
ASTM C231
Concrete Temperature
Ambient Temperature
Specifications
3500 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
Strength
Slump
Air Content
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
7169957 Time Batched: 14:02 Time Sampled: 14:46
4 in Air Content: 5.5 % Unit Weight: N/A
900 F Ambient Temperature: 880 F Yardage (c.y.): 10/40
Sidewalk and bike path - from Coppell Bible Fellowship Drive entrance westward 320 feet
Sample Location:
1 st 70 feet
Concrete Compression Test Results
Cylinder Age Max Load Area Strenijth Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
03 SLR08300611 09/06/2006 7 82960 27.99 2960 E-columnar
03 SLR08300612 09/27/2006 28 103260 28.18 3660 C-cone/shear
03 SLR08300613 09/27/2006 28 108700 28.18 3860 E-columnar
03 SLR08300614 Hold
28 day average 3760
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3500
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, SET.
Vice PresidenUCMT Manager