ST9902-LR060912
Concrr~ Compression Test Report
eM J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-122
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
08/17/2006
Zach Hartgraves
Clear/Calm
Tiseo/2465H
ASTM C231
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Cylinder Age Max Load Area
Set# # Test Date (days) (Ibs. force) (sq.in.)
01 SlR08170601 08/24/2006 7 28.18
01 SlR08170602 09/14/2006 28
01 SlR08170603 09/14/2006 28
01 SlR08170604 Hold
Ticket Number:
Slump:
Concrete Temperature:
Placement location:
Sample Location:
N/A
3in
830 F
Time Batched: 08:12 Time Sampled: 08:45
Air Content: 4.0 % Unit Weight: N/A
Ambient Temperature: 850 F Yardage (c.y.): 40/250
Sandy lake Road, eastbound side right turn lane onto Oak Bend Drive at Station 48+50 to Station
Paving:
46+00
3 feet north of south curb, 5 feet north of Station 48+00
Concrete Compression Test Results
Strength
(pSI)
Fracture
Type
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
* NO TEST DATA AVAILABLE; CYLINDERS REMOVED FROM CAST lOCATION BY PERSONS UNKNOWN.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of2
Concrn Compression Test Report
C M J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-122
Report Date: 09/12/2006
Specifications
Test Data
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
08/17/2006
Zach Hartgraves
Clear/Calm
Tiseo/2465H
ASTM C231
Ticket Number: N/A Time Batched: 10:47 Time Sampled: 11 :30
Slump: 3 in Air Content: 5.0% Unit Weight: N/A
Concrete Temperature: 940 F Ambient Temperature: 90" F Yardage (c.y.): 160/250
Placement location: Paving: In front of empty building just before north point at Station 29+30
Sample location:
2 feet south and 4 feet west of northeast corner of paving
Concrete Compression Test Results
Cylinder Age Max Load Area
Set# # Test Date (days) (Ibs. force) (sq.in.)
02 SlR08170605 08/24/2006 7 28.18
02 SlR08170606 09/14/2006 28
02 SlR08170607 09/14/2006 28
02 SlR08170608 Hold
Strength
(psi)
Fracture
Type
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
* NO TEST DATA AVAILABLE; CYLINDERS REMOVED FROM CAST LOCATION BY PERSONS UNKNOWN.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
OJ Page 2 of2
Concr( -~ Compression Test Report
eM J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-086
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Concrete Temperature
Ambient Temperature
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
07/26/2006
Travis Powell
Cloudy/Breezy
Tiseo/2465
ASTM C231
Strength
Slump
Air Content
Specifications
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
Ticket Number:
Slump:
Concrete Temperature:
Placement location:
n/a Time Batched: 07:45
2 in Air Content: 4.5 %
920 F Ambient Temperature: 930 F
Paving: N. Coppell Road
Time Sampled: 08:20
Unit Weight: n/a
Yardage (c.y.): 40 of 160
Sample location:
Sta.53+50
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SlR07260601 07/29/2006 3 85400 28.18 3030 C-cone/shear
01 SlR07260602 08/02/2006 7 100760 27.99 3600 E-columnar
01 SLR07260603 08/23/2006 28 129360 28.18 4590 E-columnar
01 SlR07260604 08/23/2006 28 130890 28.18 4640 E-columnar
28 day average 4620
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
CMJ Engineering, 'nc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
O! Page 1 of2
Concn-' Compression Test Report
eM J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-086
Report Date: 09/12/2006
Concrete Temperature
Ambient Temperature
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
07/26/2006
Travis Powell
Partly Cloudy/Light Wind
Tiseo/2465
ASTM C231
Strength
Slump
Air Content
Specifications
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
Ticket Number:
Slump:
Concrete Temperature:
Placement location:
n/a
4.75 in*
900 F
Paving -
Time Batched: 10:40
Air Content: 5.8 %
Ambient Temperature: 820 F
N. Coppell Road: Southbound lane from Sta. 1+14 to Sta. 3+85
Time Sampled: 11 :20
Unit Weight: n/a
Yardage (c.y.): 160 of 160
Sample Location:
Centerline of Southbound lane at Sta. 3+36
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
02 SlR07260605 07/29/2006 3 74680 28.18 2650 C-cone/shear
02 SlR07260606 08/02/2006 7 90800 27.99 3240 C-cone/shear
02 SlR07260607 08/23/2006 28 116760 28.18 4140 E-columnar
02 SlR07260608 08/23/2006 28 111620 28.18 3960 C-cone/shear
28 day average 4050
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1 064, and C617 or C1231.
o Gallons of Water Added On-Site
* Non-Compliant: Contractor Notified
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
R. Carl Lee, S.E.T.
Vice PresidentlCMT Manager
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 2 of2
Concrf - Compression Test Report
eM J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-080
Report Date: 09/12/2006
~* REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
'Sampled By
Weather
Supplier/Mix
Air Content Method
07/21/2006
Joshua Davis
Sunny/Calm
Southern Star/9618-B
ASTM C231
Ticket Number: 1178312
Slump: 3 in
Concrete Temperature: 1100 F
Placement location: Inlet top, C1-3
Time Batched: 13:44
Air Content: 3.3 %
Ambient Temperature: 1000 F
Time Sampled: 14:15
Unit Weight: N/A
Yardage (c.y.): 4.5/4.5
Sample location:
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SlR0721 0601 07/28/2006 7 133400 28.27 4720 E-columnar
01 SlR0721 0602 08/18/2006 28 158580 28.09 5650 C-cone/shear
01 SlR0721 0603 08/18/2006 28 161400 28.09 5750 E-columnar
01 SlR0721 0604 Hold
28 day average 5700
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
5 Gallons of water added on site, approved by Better Inlets
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice PresidentlCMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
a I Page 1 of 1
Concrr-' Compression Test Report
eM J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-078
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Test Data
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
07/20/2006
Jory Goldring
Clear/Calm
Southern Star/Class C
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement location:
1260414 Time Batched: 13:19
3.75 in Air Content: 3.2 %
1020 F Ambient Temperature: 1050 F
Manhole at Branchwood and Sandy lake
Time Sampled: 14:10
Unit Weight: n/a
Yardage (c.y.): 4.5 of 4.5
Sample location:
Same
Concrete Compression Test Results
Cylinder Age Max Load Area Strenrrh Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SlR07200601 07/27/2006 7 105560 28.18 3750 E-columnar
01 SlR07200602 08/17/2006 28 138460 28.18 4910 E-columnar
01 SlR07200603 08/17/2006 28 139660 28.18 4960 E-columnar
01 SlR07200604 Hold
28 day average 4940
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
5 Gallons of Water Added On-Site, Approved by: Contractor
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the speCific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concrr -, Compression Test Report
C M J ENGINEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-074
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
40. F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
07/19/2006
David McNeil
Clear
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement location:
Sample Location:
1178278
3.25 in
900 F
Inlet
Time Batched: 13:38
Air Content: 4.0 %
Ambient Temperature: 980 F
Time Sampled: 14:15
Unit Weight: N/A
Yardage (c.y.): 7.5 of 7.5
Area located at Intersection of East Sandy lake Road and Branchwood Trail, South of East Sandy lake Road
and East of Branchwood Trail
Concrete Compression Test Results
Cylinder Age Max Load Area Stren8th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SlR07190601 07/26/2006 7 106040 27.81 3810 E-columnar
01 SlR07190602 08/16/2006 28 140720 27.99 5030 E-columnar
01 SlR07190603 08/16/2006 28 136120 27.99 4860 C-cone/shear
01 SlR07190604 Hold
28 day average 4950
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
o I Page 1 of 1
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Concrr-"--'\ Compression Test Report
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-073
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
Strength
Slump
Air Content
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
07/18/2006
Richard Jones
Partly Cloudy/Light Wind
Southern Star/9618-B
ASTM C231
Concrete Temperature n/a
Ambient Temperature 400 F min
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1260332 Time Batched: 13:30
4 in Air Content: 3.3 %
1010 F Ambient Temperature: 1030 F
Inlet: Eastside of Branchwood at Sandy Lake, Sta. 0+15.43
Time Sampled: 14:15
Unit Weight: N/A
Yardage (c.y.): 4 of 4
Sample Location:
Inlet: Eastside of Branchwood at Sandy Lake, Sta. 0+15.43
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SLR07180601 07/25/2006 7 118740 28.18 4210 E-columnar
01 SLR07180602 08/15/2006 28 151060 28.18 5360 C-cone/shear
01 SLR07180603 08/15/2006 28 155980 28.18 5530 E-columnar
01 SLR07180604 Hold
28 day average 5450
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
5 Gallons of Water Added On-Site, approved by: Clemendez
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
'\
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
o I Page 1 of 1
Concr'.......~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-072
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
-~
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
07/17/2006
Jory Goldring
Clear/No Wind
Southern Star/9618-B
ASTM C231
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
11798210
3.25 in
9rF
Inlet Walls and Bottom
13:40
4.2%
1010 F
Time Sampled: 14:10
Unit Weight: N/A
Yardage (c.y.): 4 of 4
Time Batched:
Air Content:
Ambient Temperature:
West side, Branchwood Dr, Sta. 0+19, Lat C1 - 2A
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR07170601 07/24/2006 7 125760 28.18 4460 E-columnar
01 SLR07170602 08/14/2006 28 150480 28.18 5340 E-columnar
01 SLR07170603 08/14/2006 28 148700 28.18 5280 C-cone/shear
01 SLR07170604 Hold
28 day average 5310
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
Ot Page 1 of 1
Concrr Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-070
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
1 .5 in max
Test Data
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
07/14/2006
Robert Dunnam
Clear/Light Wind
Tiseo/2446M
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1 Time Batched: 07:18
2.5 in* Air Content: 5.9 %
880 F Ambient Temperature: 830 F
Paving: West Sandy Lake Rd, East bound, Sta. 52+50 to Sta. 53+90
Time Sampled: 07:45
Unit Weight: N/A
Yardage (c.y.): 10 of 175
Sample Location:
Sta. 53+90
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR07140601 07/17/2006 3 75960 28.09 2700 B-cone/split
01 SLR07140602 07/21/2006 7 91180 28.09 3250 C-cone/shear
01 SLR07140603 08/11/2006 28 111400 28.27 3940 E-columnar
01 SLR07140604 08/11/2006 28 115340 28.27 4080 C-cone/shear
01 SLR07140605 Hold
28 day average 4010
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
* Non-Compliant: Contractor Notified
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised to
remove maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of2
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Concr'-' Compression Test Report
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-070
Report Date: 09/12/2006
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
1.5inmax
3 % min 6 % max
Test Data
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
07/14/2006
Robert Dunnam
Clear/Light Wind
Tiseo/2446M
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
18 Time Batched: 09:12
3 in. Air Content: 7.4 %*
900 F Ambient Temperature: 850 F
Paving: West Sandy Lake Rd, East bound, Sta. 52+50 to Sta. 53+90
Time Sampled: 09:30
Unit Weight: N/A
Yardage (c.y.): 180 of 180
Sample Location:
Sta. 52+75
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area strenWh Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
02 SLR07140606 07/17/2006 3 76520 28.09 2720 B-cone/split
02 SLR07140607 07/21/2006 7 106260 28.09 3780 E-columnar
02 SLR07140608 08/11/2006 28 119120 28.27 4210 C-cone/shear
02 SLR07140609 08/11/2006 28 122410 28.27 4330 E-columnar
02 SLR07140610 Hold
28 day average 4270
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
* Non-Compliant: Contractor Notified
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised to
remove maximum temperature.
CMJ Engineering, Inc
'\
I
I
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 2 of2
Concrr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-064
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
06/27/2006
Contractor Made
n/a
Contractor Made/
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
n/a
n/a
n/a
Inlet
Time Batched:
Air Content:
Ambient Temperature:
n/a
. n/a
n/a
Time Sampled: n/a
Unit Weight: n/a
Yardage (c.y.): n/a
Sample Location:
Inlet: West Sandy Lake, North Coppell
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06270601 07/05/2006 8 111840 28.27 3960 E-columnar
01 SLR06270602 07/25/2006 28 129360 28.18 4590 E-columnar
01 SLR06270603 07/25/2006 28 131740 28.18 4670 C-cone/shear
01 SLR06270604 Hold
28 day average 4630
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
^^^ ALL INFORMATION PROVIDED BY CONTRACTOR ^^^
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-063
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
Strength 3600 psi @ 28 Days
Slump 4 in max
Air Content 3 % min 6 % max
Concrete Temperature n/a
Ambient Temperature 400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
06/29/2006
Brent Talcott
Sunny/Light Breeze
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1180556 Time Batched: 13:38
2.5 in Air Content: 3.5 %
900 F Ambient Temperature: 920 F
Inlet: Line C2-4, Sta. 0+07.37
Time Sampled: 14:15
Unit Weight: N/A
Yardage (c.y.): 4.5 of 4.5
Sample Location:
Inlet: Line C2-4, Sta. 0+07.37
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SLR06290601 07/06/2006 7 147560 28.27 5220 E-columnar
01 SLR06290602 07/27/2006 28 178440 28.18 6330 E-columnar
01 SLR06290603 07/27/2006 28 176690 28.18 6270 E'-columnar
01 SLR06290604 Hold
28 day average 6300
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples. items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
C M J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-062
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
Strength
Slump
Air Content
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
06/26/2006
Robert Dunnam
Partly Cloudy/Light Wind
Southern Star/9618-B
ASTM C231
Concrete Temperature n/a
Ambient Temperature 400 F min
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1180377 Time Batched: 13:10
2.5 in Air Content: 2.2 %*
900 F Ambient Temperature: 87" F
Inlet: C1-5 Oakbend and West Sandy Lake Road
Time Sampled: 14:00
Unit Weight: n/a
Yardage (c.y.): 4 of 4
Sample Location:
Next to above
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06260601 07/03/2006 7 129320 28.27 4570 C-cone/shear
01 SLR06260602 07/24/2006 28 160700 28.18 5700 E-columnar
01 SLR06260603 07/24/2006 28 159700 28.18 5670 E-columnar
01 SLR06260604 Hold
28 day average 5690
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
* Non-Compliant: Contractor Notified
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, 'nc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concrr Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-116
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
3500 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
08/10/2006
Brent Talcott
Clear/Light Breeze
LMC/1551
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
7196056
3in
9rF
Time Batched: 11 :00 Time Sampled: 12:00
Air Content: 5.5 % Unit Weight: N/A
Ambient Temperature: 920 F Yardage (c.y.): 10/20
N Coppell Road, northbound side, 500 feet north of Sandy Lake Road, 2 feet east of north Coppell
Sidewalk:
Road
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
02 SLR08100605 08/17/2006 7 89960 28.18 3190 E-columnar
02 SLR08100606 09/07/2006 28 125960 28.09 4480 E-columnar
02 SLR081 00607 09/07/2006 28 121980 28.09 4340 E-columnar
02 SLR08100608 Hold
28 day average 4410
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3500
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 ofl
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-061
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
-~
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
06/23/2006
Josh Bridges
Cloudy/Light Wind
Southern Star/9618-B
ASTM C231
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
1177945 Time Batched: 13:35
4 in Air Content: 3.2 %
880 F Ambient Temperature: 890 F
Inlet - Station 8+99.27 and Station 0+15.99
Time Sampled: 14:10
Unit Weight: N/A_
Yardage (c.y.): 9/9
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06230601 06/30/2006 7 112960 28.27 3990 E-columnar
01 SLR06230602 07/21/2006 28 144180 28.09 5130 C-cone/shear
01 SLR06230603 07/21/2006 28 143980 28.09 5130 E-columnar
01 SLR06230604 Hold
28 day average 5130
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-050
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
Strength
Slump
Air Content
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
06/06/2006
Phil Sommerville
Clear/Breezy
Southern Star/9618-B
ASTM C231
Concrete Temperature n/a
Ambient Temperature 400 F min
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1181656 Time Batched: 13:13
4 in Air Content: 4.4 %
910 F Ambient Temperature: 950 F
Inlet, south side Sandy Lake Road, C1-11
Time Sampled: 14:10
Unit Weight: N/A
Yardage (c.y.): 4.5/4.5
Sample Location:
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06060601 06/13/2006 7 120820 27.99 4320 E-columnar
01 SLR06060602 07/05/2006 29 156700 28.27 5540 E-columnar
01 SLR06060603 07/05/2006 29 151160 28.27 5350 E-columnar
01 SLR06060604 Hold
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, 'nc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr'-'~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-049
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
06/05/2006
Phil Sommerville
Partly CloudylWindy
Southern Star/9618-B
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
1179482 Time Batched: 13:34 Time Sampled: 14:25
3.5 in Air Content: 4.1 % Unit Weight: N/A
890 F AmbientTemperature: 860 F Yardage (c.y.): 5/5
Inlet bottom south side of Sandy Lake Road, west side of entrance to the church (751 Sandy Lake Road), Inlet
#C-9
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06050601 06/12/2006 7 144900 28.27 5120 C-cone/shear
01 SLR06050602 07/03/2006 28 170080 28.27 6010 E-columnar
01 SLR06050603 07/03/2006 28 166230 28.27 5880 E-columnar
01 SLR06050604 Hold
28 day average 5950
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, In
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page] of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth. Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-048
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications
Test Data
Strength
Slump
Air Content
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
06/02/2006
Jonathan Hubbard
Partly Cloudy
Southern Star/9618-B
ASTM C231
Concrete Temperature n/a
Ambient Temperature 400 F min
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1179466
Time Batched:
13:40
3.2%
860 F
Time Sampled: 14:20
Unit Weight: N/A
Yardage (c.y.): 4.5 of 4.5
3 in Air Content:
830 F Ambient Temperature:
Inlet: South side of Sandy Lake at Sta. 0+7.37
Sample Location:
Inlet: South side of Sandy Lake at Sta. 0+7.37
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06020601 06/09/2006 7 131740 28.27 4660 E-columnar
01 SLR06020602 06/30/2006 28 152980 28.27 5410 E-columnar
01 SLR06020603 06/30/2006 28 160160 28.27 5660 E-columnar
01 SLR06020604 Hold
28 day average 5540
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-047
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
06/01/2006
Oscar Flores
Cloudy
Southern Star/9618-B
ASTM C231
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
1176977 Time Satched: 13:15 Time Sampled: 14:18
4 in Air Content: 3.2 % Unit Weight: N/A
860 F Ambient Temperature: 820 F Yardage (c.y.): 6.5 of 6.5
Inlets, Walls and Bottom: Westbound, Sta. 18+59 and Eastbound, Sta. 40+15
Westbound, Sta. 18+59
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06010601 06/08/2006 7 126920 28.27 4490 E-columnar
01 SLR06010602 06/29/2006 28 146800 28.27 5190 C-cone/shear
01 SLR06010603 06/29/2006 28 150940 28.27 5340 E-columnar
01 SLR06010604 Hold
28 day average 5270
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
o I Page 1 of 1
Concr ....~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-046
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Sp~cifications
3600 psi @ 28 Days
4 in max
Test Data
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
05/31/2006
Robert McElvany
Cloudy/Breeze
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
177416 Time Batched: 13:40
3.5 in Air Content: 2.5 %*
820 F Ambient Temperature: 840 F
Inlet Manhole: Sta. 2+10.17, SD-C2
Time Sampled: 14:50
Unit Weight: N/A
Yardage (c.y.): 6.5 of 6.5
Sample Location:
Inlet Manhole: Sta. 2+10.17, SD-C2
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR0531 0601 06/07/2006 7 126980 27.99 4540 E-columnar
01 SLR0531 0602 06/28/2006 28 150740 28.27 5330 E-columnar
01 SLR0531 0603 06/28/2006 28 156540 27.34 5730 E-columnar
01 SLR0531 0604 Hold
28 day average 5530
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
* Non-Compliant: Contractor Notified
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, In
LIMITATIONS: The test results presented in this report apply only to the speCific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr---~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-052
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
06/07/2006
Robert McElvany
Clear/Breezy
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
1181696 Time Batched: 14:00
3.5 in Air Content: 4.0 %
87" F Ambient Temperature: 920 F
Manhole at Station 11 +68.30
Time Sampled: 14:45
Unit Weight: N/A
Yardage (c.y.): 4.5/4.5
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR06070601 06/14/2006 7 143820 28.27 5090 C-cone/shear
01 SLR06070602 07/05/2006 28 182940 28.27 6470 E-columnar
01 SLR06070603 07/05/2006 28 184260 28.27 6520 E-columnar
01 SLR06070604 Hold
28 day average 6500
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-045
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
05/30/2006
Jonathan Hubbard
Partly Cloudy
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
1177376 Time Batched: 13:40
3.5 in Air Content: 3.2 %
820 F Ambient Temperature: 850 F
Inlets: South side of Sandy Lake Rd at Sta. 28+63.66
Time Sampled: 14:15
Unit Weight: N/A
Yardage (c.y.): 2.5 of 2.5
Inlets: South side of Sandy Lake Rd at Sta. 28+63.66
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR05300601 06/06/2006 7 134860 28.27 4770 E-columnar
01 SLR05300602 06/27/2006 28 159720 28.27 5650 C-cone/shear
01 SLR05300603 06/27/2006 28 160500 28.27 5680 E-columnar
01 SLR05300604 Hold
28 day average 5670
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
C M J ENG1NEERrNG, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Concr~e Compression Test Report
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-038
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Test Data
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
05/18/2006
Larry Smallwood
Clear/Calm
Southern Star/9318B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1177103 Time Batched: 14:17
3.75 in Air Content: 3.4 %
880 F Ambient Temperature: 910 F
Inlet Bottom: A2-6 (Sta. #0+09.91) and A2-4 (Sta. #0+16.74)
Time Sampled: 15:20
Unit Weight: n/a
Yardage (c.y.): 8 of 8
Sample Location:
Same as Above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR05180601 OS/25/2006 7 99400 28.27 3520 E-columnar
01 SLR05180602 06/15/2006 28 116060 27.99 4150 C-cone/shear
01 SLR05180603 06/15/2006 28 120430 27.99 4300 E-columnar
01 SLR05180604 Hold
28 day average 4230
Nonmal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Pagelofl
Concr-c.~ Compression Test Report
eM J ENGfNEERING, INC
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-037
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
S pacifications
Test Data
05/17/2006
Robert McElvany
Clear/Breezy
Southern Star/9618-B
ASTM C231
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
1179139 Time Batched: 13:46 Time Sampled: 14:15
3 in Air Content: 3.3 % Unit Weight: N/A
800 F Ambient Temperature: 800 F Yardage (c.y.): 4/4
Manhole top Station 13+44 storm drain Line A2, manhole base and walls Station 17+82, storm drain line A2,
just west of Royal Lane
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in. ) (psi Type
01 SLR05170601 OS/24/2006 7 128120 27.53 4650 E-columnar
01 SLR05170602 06/14/2006 28 150400 28.27 5320 E-columnar
01 SLR05170603 06/14/2006 28 154600 28.27 5470 C-cone/shear
01 SLR05170604 Hold
28 day average 5400
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1 064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
/'
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concret4...Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-115
Report Date: 09/12/2006
3 % min 6 % max
550 F min 900 F max
400 F min 1000 F max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
08/1 0/2006
Brent Talcott
Clear/Light Breeze
Tiseo/2465M
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
ii~ ~- ~::;~_~ _':==-~::::T~ ~-" ;,'; M .- .~;':~!?~::. ,. '[f{~i, ~ S1:~~~Z ~.,~ :~ __~:~.:~:,-~'~"~._~-.~ _~ ~. -~:~ ~ - ~-~]
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
N/A Time Batched: 10:57 Time Sampled: 10:20
4 in Air Content: 6.5 %* Unit Weight: N/A
960 F* Ambient Temperature: 880 F Yardage (c.y.): 38/100
Paving: Median/turning lane of Royal lane, running from Station 10+50 to Station 9+00
Sample Location:
Station 10+70
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren8th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SLR081 00601 08/17/2006 7 104560 28.18 3710 E-columnar
01 SLR081 00602 09/07/2006 28 124780 28.09 ef E-columnar
01 SLR081 00603 09/07/2006 28 122720 28.09 E-columnar
01 SLR081 00604 Hold
28 day average 4410
Normal cylinder size: 6" x 12'
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1
CMJ Engineering, In
R. Carl Lee, S.E.T.
Vice President/CMT Manager
o gallons of water added on site
* Non-Compliant: Contractor Notified (Angelo, w/ Tiseo)
CfI/~(ly
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of CoppeU
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-034
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Test Data
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
05/03/2006
n/a
Contractor Made/
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
n/a
n/a
n/a
Headwall on A 1, A2, A3
Time Batched:
Air Content:
Ambient Temperature:
n/a
n/a
n/a
Time Sampled: n/a
Unit Weight: n/a
Yardage (c.y.): n/a
Sample Location:
Same
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SLR05030601 05/12/2006 9 122160 27.99 4360 E-columnar
01 SLR05030602 05/31/2006 28 130900 27.99 4680 E-columnar
01 SLR05030603 05/31/2006 28 129160 27.99 4610 E-columnar
01 SLR05030604 05/31/2006 28 126560 27.99 4520 E-columnar
28 day average 4600
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
*ALL INFORMATION PROVIDED BY THE CONTRACTOR*
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
C M J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-033
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Test Data
Specifications
Strength
Slump
Air Content
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
04/27/2006
Josh Bridges
Sunny/Light Wind
Southern Star/9618B
ASTM C231
Concrete Temperature n/a
Ambient Temperature 400 F min
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1025193 Time Batched: 13:17
5.5 in* Air Content: 4.7 %
820 F Ambient Temperature: 800 F
Storm Drain: Sta. 0+98.85, Line A-1
Time Sampled: 14:05
Unit Weight: N/A
Yardage (c.y.): 9 of 9
Sample Location:
15' East from Sta. 0+98.85, Line A-1
An asterisk (*) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR04270601 05/04/2006 7 108580 28.18 3850 C-cone/shear
01 SLR04270602 OS/25/2006 28 129120 28.27 4570 E-columnar
01 SLR04270603 OS/25/2006 28 128580 28.27 4550 E-columnar
01 SLR04270604 Hold
28 day average 4560
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172. C1064, and C617 or C1231.
* Non-Compliant: Contractor Notified
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and ar as described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-032
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Test Data
---
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
04/25/2006
Robert McElvany
Clear/Breezy
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
957192 Time Batched: 13:37
3 in Air Content: 4.0 %
760 F Ambient Temperature: 690 F
Manhole Station 0+25.83, Line C-1, second lift
Time Sampled: 14:20
Unit Weight: N/A
Yardage (c.y.): 4/4
Sample Location:
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Strenth Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR04250601 05/02/2006 7 126780 27.81 4560 C-cone/shear
01 SLR04250602 OS/23/2006 28 148420 27.99 5300 E-columnar
01 SLR04250603 OS/23/2006 28 146980 27.99 5250 E-columnar
01 SLR04250604 Hold
28 day average 5280
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1 064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr'--~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-031
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
1-----..
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
04/24/2006
Robert McElvany
Clear/Breezy
Southern Star/9618B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
957172 Time Batched: 13:57
3 in Air Content: 4.0 %
820 F Ambient Temperature: 800 F
Manhole Station 1+25.83 at Line C-1
Time Sampled: 14:30
Unit Weight: N/A
Yardage (c.y.): 5/5.5
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area StrenJth Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR04240601 05/01/2006 7 121160 27.99 4330 C-cone/shear
01 SLR04240602 OS/22/2006 28 166360 27.99 5940 E-columnar
01 SLR04240603 OS/22/2006 28 163120 27.99 5830 E-columnar
01 SLR04240604 Hold
28 day average 5890
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
Page 1 of 1
Concr~ Compression Test Report
C M J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-029
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Specifications
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
04/19/2006
Joshua Davis
Mostly Sunny/Light Wind
Southern Star/9618-B
ASTM C231
Concrete Temperature n/a
Ambient Temperature 400 F min
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
957138
2.75 in
800 F
Inlet Top:
Time Batched: 1427
Air Content: 3.7 %
Ambient Temperature: 790 F
Line "C-1", Sta. 17+29.79, Line "A-2", Sta. 17+28.95
Time Sampled: 1445
Unit Weight: N/A
Yardage (c.y.): 5.5 of 5.5
Sample Location:
Inlet Top: Line "C-1", Sta. 17+29.79, Line "A-2", Sta. 17+28.95
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR0419060 1 04/26/2006 7 112920 27.90 4050 C-cone/shear
01 SLR04190602 05/17/2006 28 148520 28.09 5290 E-columnar
01 SLR04190603 05/17/2006 28 146720 28.09 5220 E-columnar
01 SLR04190604 Hold
28 day average 5260
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
Page 1 of 1
Concrr-, Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-028
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Test Data
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
04/18/2006
Richard Jones
Clear/Calm
Southern Star/9618-B
ASTM C231
Cylinder Age Max Load
Set# # Test Date (days) (Ibs. force)
01 SLR0418060 1 04/25/2006 7 119940
01 SLR04180602 05/16/2006 28 154320
01 SLR04180603 05/16/2006 28 152090
01 SLR04180604 Hold
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
957095 Time Batched: 0145
3.5 in Air Content: 3.0 %
900 F Ambient Temperature: 980 F
Inlet Walls, Southbound Side of Royal Lane at Corner of Sandy Lake Road
Time Sampled: 0230
Unit Weight: n/a
Yardage (c.y.): 4 of 4
Same
Concrete Compression Test Results
fi!f!~
,/
./ Strength
(psi)
4270
5490
5410
Fracture
Type
C-cone/shear
E-columnar
C-cone/shear
. .------..
-" .
Area
(sq.in.) /
28~
28.09
28.09
28 day average 5450
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31. C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum tem rature. J
ev\lle. 1Jf{f
q-1L1' ~
CMJ Engineering, Inc
L- .
~~ 1iO (1 7
c;lfef/ "
~'<'.
J
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
Page 1 of 1
Concrete Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-114
Report Date: 09/12/2006
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Test Data
Strength
Slump
Air Content
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
08/09/2006
Brent Talcott
Clear/Light Breeze
Southern Star/9618-B
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1257754 Time Batched: 13:28
4 in Air Content: 5.2 %
990 F Ambient Temperature: 980 F
Inlet: Southbound side of Royal Road, Station 11 +00
Time Sampled: 14:05
Unit Weight: N/A
Yardage (c.y.): 5/5
Sample Location:
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area StrenJth Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
08 SLR08090631 08/16/2006 7 95420 27.99 3410 C-cone/shear
08 SLR08090632 09/06/2006 28 119460 27.99 4270 C-cone/shear
08 SLR08090633 09/06/2006 28 121080 27.99 4320 E-columnar
08 SLR08090634 Hold
28 day average 4300
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, ,an areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are prodU d solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 ofl
Concrete Compression Test Report
eM J ENGINEERING, TNC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-113
Report Date: 09/12/2006
Concrete Temperature
Ambient Temperature
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
08/09/2006
Brent Talcott
Clear/Light Breeze
LMC/1551
ASTM C231
Strength
Slump
Air Content
Specifications
3500 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
7168981 Time Batched: 12:43
4 in Air Content: 5.5 %
980 F Ambient Temperature: 980 F
Sidewalk, equal with Station 53+00, 75 feet north of Sandy Lake Road
Time Sampled: 13:45
Unit Weight: N/A
Yardage (c.y.): 20/30
Sample Location:
Same as above
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
07 SLR08090627 08/16/2006 7 78440 27.99 2800 B-cone/split
07 SLR08090628 09/06/2006 28 110740 27.99 3960 E-columnar
07 SLR08090629 09/06/2006 28 106580 27.99 3810 E-columnar
07 SLR08090630 Hold
28 day average 3890
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o gallons of water added on site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3500
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
i
CMJ Engineering, In!
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concr~ Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-103
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
f-------~-~-
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Sp~cifications
Test Data
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
08/03/2006
Travis Powell
Clear/Light Breeze
N/ AlN/ A
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
N/A Time Batched: N/A
4 in Air Content: 4.5 %
900 F Ambient Temperature: 990 F
Intersectioins on North Coppell Road
Time Sampled: 12:00
Unit Weight: N/A
Yardage (c.y.): 20/20
Sample Location:
Station 2+55 North Coppell Road on both sides of the road and at Station 3+60 on North Coppell Road
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR08030601 08/07/2006 4 98200 28.09 3500 C-cone/shear
01 SLR08030602 08/10/2006 7 105540 28.27 3730 E-columnar
01 SLR08030603 08/31/2006 28 127380 28.09 4530 C-cone/shear
01 SLR08030604 08/31/2006 28 129760 28.09 4620 E-columnar
01 SLR08030605 Hold
28 day average 4580
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of water added on site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
CMJ Engineering, 'nc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
o I Page 1 of 1
Concrr::"", Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-101
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
08/01/2006
Travis Powell
Clear/Calm
Southern Star/9618-B
ASTM C231
Strength
Slump
Air Content
Ticket Number: 1268129
Slump: 3 in
Concrete Temperature: 920 F
Placement Location: Inlet Top and Throat
Time Batched: 13:31
Air Content: 3.2 %
Ambient Temperature: 980 F
Time Sampled: 14:30
Unit Weight: N/A
Yardage (c.y.): 8 of 8
Sample Location:
Inlet: Sta. 0+15 on Coppell Rd.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR08010601 08/08/2006 7 128800 28.18 4570 E-columnar
01 SLR08010602 08/29/2006 28 149600 28.18 5310 E-columnar .
01 SLR08010603 08/29/2006 28 149480 28.18 5300 E-columnar
01 SLR08010604 Hold
28 day average 5310
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Strength specification changed from 3000 to 3600
Concrete temperature specification removed
Ambient temperature specification revised to remove
maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concrr- Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-091
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
Specifications Test Data -----
Strength 3600 psi @ 28 Days Placement Date 07/28/2006
Slump 4 in max Sampled By Travis Powell
Air Content 3 % min 6 % max Weather Mostly Cloudy/Breezy
Concrete Temperature n/a Supplier/Mix Tiseo/2465H
Ambient Temperature 400 F min Air Content Method ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
N/A
3.25 in
900 F
Curb and Gutter:
Time Batched:
Air Content:
Ambient Temperature:
Coppell Road
13:44
5.2%
940 F
Time Sampled: 14:15
Unit Weight: N/A
Yardage (c.y.): 10 of 10
Sample Location:
Coppell Road, Sta. 3+00
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR07280601 07/31/2006 3 94500 28.27 3340 C-cone/shear
01 SLR07280602 08/04/2006 7 113040 28.09 4020 E-columnar
01 SLR07280603 08/25/2006 28 141480 27.99 5050 C-cone/shear
01 SLR07280604 08/25/2006 28 144420 27.99 5160 E-columnar
01 SLR07280605 Hold
28 day average 5110
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of 1
Concrr -, Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-089
Report Date: 09/12/2006
** REVISED REPORT **
(SEE COMMENTS BELOW)
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
07/27/2006
Robert Dunnam
Clear/Light Wind
Tiseo/2465H
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
3 % min 6 % max
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Batch 163 Time Batched: 07:26
4 in Air Content: 5.8 %
860 F Ambient Temperature: 790 F
Paving: Westboundllntersection, Sta. 53+00 to Sta. 53+75
Time Sampled: 07:45
Unit Weight: n/a
Yardage (c.y.): 10 of 250
Sample Location: Same
Concrete Compression Test Results
Cylinder Age Max Load Area Stren}th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (psi Type
01 SLR07270601 08/03/2006 7 97320 28.18 3450 C-cone/shear
01 SLR07270602 08/24/2006 28 122220 28.18 4340 E-columnar
01 SLR07270603 08/24/2006 28 123660 28.18 4390 E-columnar
01 SLR07270604 Hold
28 day average 4370
Normal cylinder size: 6" x 12"
.
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39. C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
CMJ Engineering, Inc
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 1 of2
Concrr- Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-089
Report Date: 09/12/2006
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Test Data
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
07/27/2006
Robert Dunnam
Clear/Light Wind
Tiseo/2465H
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Batch 163 Time Batched: 10:08
5 in* Air Content: 5.7 %
930 F Ambient Temperature: 880 F
Paving: Northbound Coppell Rd., North Sta. 1+14.1 to Sta. 3+84
Time Sampled: 10:58
Unit Weight: n/a
Yardage (c.y.): 160 fo 250
Sample Location:
Sta. 2+30.08
An asterisk (0) appears next to field data which does NOT meet specifications.
Concrete Compression Test Results
Cylinder Age Max Load Area Stren~th Fracture
Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
02 SLR07270605 08/03/2006 7 103240 28.18 3660 C-cone/shear
02 SLR07270606 08/24/2006 28 125400 28.18 4450 E-columnar
02 SLR07270607 08/24/2006 28 123960 28.18 4400 E-columnar
02 SLR07270608 Hold
28 day average 4430
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
* Non-Compliant: Contractor Notified
**REVISED REPORT 9/12/2006**
Concrete temperature specification removed.
Ambient temperature specification revised
to remove maximum temperature.
R. Carl Lee, S.E.T.
Vice President/CMT Manager
CMJ Engineering, Inc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page 2 of 2