ST9902-LR060918 (2) Con cretA Compression Test Report eM J ENGINEERING, INC. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Project: City of Coppell West Sandy Lake Road Reconstruction Report Distribution: (1) City of Coppell (1) City of Coppell (1) Tiseo Paving Company (1) Teague Nail & Perkins CMJ Report No.: 687-5192-120 Report Date: 09/18/2006 3 % min 6 % max Placement Date Sampled By Weather Supplier/Mix Air Content Method Test Data 08/15/2006 Zach Hartgraves Clear/Windy Southern Star/9618-B ASTM C231 Strength Slump Air Content Concrete Temperature Ambient Temperature Specifications 3600 psi @ 28 Days 4 in max n/a 400 F min iJ " A" ;,-. 1--- ~~ --!<:~~"""rn'" T ">'"Th~"""~f-7"''''WTh~~~~~"!/'f";t~'I'''ry"~'''~- - r-'-'-~"""- -:1' ,.- ~,.,r. -,.......,"'''f<'"'' "'"r~--;rr:!F'"~ '"'-"I"""""~"~~~'" ,.",..,..",-- ,.,.,.,..-..,...... .. ~,,,.-" ~~ - : ,', ';': .;,' , ,;;, ; V,;:: ,,'." .'.' ~ :', :,' ~, " C:f~:t2tutS.;:jSO:f}l, '" .'k:;"" ,,", '~.,,' '. " ,-"__~~~~~__~~~~~ ~~~-....._~~~~...............~~~..1 _.~ -~ "-_.... Ticket Number: Slump: Concrete Temperature: Placement Location: 1257986 Time Batched: 13:35 Time Sampled: 15:00 4 in Air Content: 5.0 % Unit Weight: N/A 880 F Ambient Temperature: 970 F Yardage (c.y.): 6/6 Storm Drain Inlet - Royal Lane, southbound, right lane, on west curb, Station 3+84.72 Sample Location: 2 feet north of southern front of inlet, Station 3+84.72 Concrete Compression Test Results Cylinder Age Max Load Area Stren&th Fracture Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type 01 S LR0815060 1 08/22/2006 7 101760 27.81 3660 E-columnar 01 SLR08150602 09/12/2006 28 137820 28.18 4890 E-columnar 01 SLR08150603 09/12/2006 28 139560 28.18 4950 E-columnar 01 SLR08150604 Hold 28 day average 4920 Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231. o gallons of water added on site, approved by John Gay **REVISED REPORT 9/12/2006** Strength specification changed from 3000 to 3600 Concrete temperature specification removed Ambient temperature specification revised to remove maximum temperature. CMJ Engineerin , I c R. Carl Lee, S.E.T. Vice President/CMT Manager LIMITATIONS: The test results presented in this report apply only to the specific samples, I ms, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. 01 Page 1 of 1