Gateway BP(1.6)-LR061024CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061163.0118 Service Date: September 25, 2006 l~~rracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: ProLogis Attn: Keith Porter 2310 LBJ Freeway Ste 200 Dallas TX 75234 Report Date: October 24, 2006 Project: Freeport Corporate Ctr. Bldg. 6 Freeport Pkwy & Gateway Coppell, TX Project No.: 94061163 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 2:50am Plant: 27 Supplier: Southern Star Truck No: 31 Ticket No: 1435490 Mix I.D. No.: 9339 Water Added Onsite Before Test: SGallons Sample Information Date Cast: September 25, 2006 Time: 3:51am Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 50 Placement Method: Pump Sample Locations: See attached sketch for Location #1 Placement Location: Pavement, E of Building Field Test Data Test Result Specification Test Method Slump, inches: 5.50 3-5 ASTM C143 Air Content, %: 3.4 3-6 ASTM C231 Concrete Temperature, °F: 80 ASTM C1064 Ambient Temperature,~F: 54 ASTM C1064 Plastic Unit Weight, pcf: 145.6 ASTM C138 * =Field Test Results do not meet project specifications. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 1 1 6.00 28.27 10/02/2006 7 86,410 3,060 1 2 6.00 28.27 10/02/2006 7 90,780 3,210 Average (7 Days) 3,140 1 3 6.00 28.27 10/23/2006 28 124,990 4,420 1 4 6.00 28.27 10/23/2006 28 124,930 4,420 Average (28 Days) 4,420 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 5 ~~-^~~~~-F~a KaY CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061163.0118 11~rr~con Service Date: September 25, 2006 8901 Carpenter Fnvy, ste#1oo Dallas, Texas 75247 (214) 630-1010 Client: Report Date: October 24, 2006 ProLogis Project: Freeport Corporate Ctr. Bldg. 6 Attn: Keith Porter Freeport Pkwy & Gateway 2310 LBJ Freeway Ste 200 Coppell, TX Dallas TX 75234 Project No.: 94061163 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 4:02am Plant: 27 Supplier: Southern Star Truck No: 120 Ticket No: Mix I.D. No.: 9339 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, of Ambient Temperature,~F: Plastic Unit Weight, pcf: Samale Information Date Cast: September 25, 2006 Time: 4:50am Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 120 Placement Method: Pump Sample Locations: See attached sketch for Location #2 Placement Location: Pavement, E of Building Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Result 5.75 3.0 79 52 147.4 " =Field Test Results do not meet project specifications. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches} Tested (days) (Ibs) (psi) 2 1 6.00 28.27 10/02/2006 7 78,830 2,790 2 2 6.00 28.27 10/02/2006 7 79,060 2,800 Average (7 Days) 2,800 2 3 6.00 28.27 10/23/2006 28 112,290 3,970 2 4 6.00 28.27 10/23/2006 28 108,930 3,850 Average (28 Days) 3,910 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were pertormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consenk of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 Of 5 oi-ACSam7-FNUre Key CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061163.0118 l~~rracon Service Date: September 25, 2006 8901 Carpenter Fnny, Ste#too Dallas, Texas 75247 (214)630-1010 Client: Report Date: October 24, 2006 ProLogis Project: Freeport Corporate Ctr. Bldg. 6 Attn: Keith Porter Freeport Pkwy & Gateway 2310 LBJ Freeway Ste 200 Coppell, TX Dallas TX 75234 Project No.: 94061163 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 5:35am Plant: 27 Supplier: Southern Star Truck No: 31 Ticket No: 1435507 Mix I.D. No.: 9339 Water Added Onsite Before Test: 10Gallons Field Test Data Test Result Slump, inches: 5.50 Air Content, %: 3.4 Concrete Temperature, °F: 80 Ambient Temperature,oF: 53 Plastic Unit Weight, pcf: 147.0 Samale Information Date Cast: September 25, 2006 Time: 6:13am Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 220 Placement Method: Pump Sample Locations: See attached sketch for Location #3 Placement Location: Pavement, E of Building Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 * =Field Test Results do not meet project specifications. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 3 1 6.00 28.27 10/02/2006 7 81,070 2,870 3 2 6.00 28.27 10/02/2006 7 86,040 3,040 Average (7 Days) 2,960 3 3 6.00 28.27 10/23/2006 28 115,490 4,080 3 4 6.00 28.27 10/23/2006 28 118,950 4,210 Average (28 Days) 4,150 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 5 Ot-ACSR201-F~re Key CONCRETE COIVIPRESSIVE STRENGTH TEST Report Number: 94061163.0118 Service Date: September 25, 2006 Client: ProLogis Attn: Keith Porter 2310 LBJ Freeway Ste 200 Dallas TX 75234 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 7:07am Plant: 27 Supplier: Southern Star Truck No: 5019 Ticket No: 1435518 Mix I.D. No.: 9339 Water Added Onsite After Test: 5 Gallons Field Test Data lI~rracon 8901 Carpenter Fnnry, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: October 24, 2006 Project: Freeport Corporate Ctr. Bldg. 6 Freeport Pkwy & Gateway Coppell, TX Project No.: 94061163 Sample Information Date Cast: September 25, 2006 Time: 7:33am Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 320 Placement Method: Pump Sample Locations: See attached sketch for Location #4 Placement Location: Pavement, E of Building Test Result Specification Test Method Slump, inches: 5.00 3-5 ASTM C143 Air Content, %: 3.4 3-6 ASTM C231 Concrete Temperature, °F: 79 ASTM C1064 Ambient Temperature,oF: 56 ASTM C1064 Plastic Unit Weight, pcf: 145.5 ASTM C138 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 4 1 6.00 28.27 10/02/2006 7 84,150 2,980 4 2 6.00 28.27 10/02/2006 7 83,260 2,940 Average (7 Days) 2,960 4 3 6.00 28.27 10/23/2006 28 118,460 4,190 4 4 6.00 28.27 10/23/2006 28 115,670 4,090 Average (28 Days) 4,140 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressi~re strength samples. The tests were pertormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 5 0,-~~~,-F~,a Hay CONCRETE COMPRESSIVE STRENGTH TEST lf~rr~con Report Number: 94061163.0118 Service Date: September 25, 2006 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Report Date: October 24, 2006 ProLogis Project: Freeport Corporate Ctr. Bldg. 6 Attn: Keith Porter Freeport Pkwy & Gateway 2310 LBJ Freeway Ste 200 Coppell, TX Dallas TX 75234 Project No.: 94061163 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 8:OOam Plant: 27 Supplier: Southern Star Truck No: 5019 Ticket No: 1435525 Mix I.D. No.: 9339 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, ~F Ambient Temperature,~F: Plastic Unit Weight, pct: Result 6.00 3.5 81 70 146.7 Samp/e Information Date Cast: September 25, 2006 Time: 9:02am Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 410 Placement Method: Pump Sample Locations: See attached sketch for Location #5 Placement Location: Pavement, E of Building Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 * =Field Test Results do not meet project specifications. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 5 1 6.00 28.27 10/02/2006 7 89,860 3,180 5 2 6.00 28.27 10/02/2006 7 91,930 3,250 Average (7 Days) 3,220 5 3 6.00 28.27 10/23/2006 28 116,030 4,100 5 4 6.00 28.27 10/23/2006 28 122,160 4,320 Average (28 Days) 4,210 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep: Jose A. Martinez Report Distribution: (1) ProLogis (1) Meinhardt & Assoc Architects PLLC (1) City of Coppell TX (1) Jordan Construction Services Reviewed by: (1) City of Coppell TX (1) Meinhardt & Assoc Architects PLLC Robert D. Ray, S.E. . (1) Haynes Whaley Assoc Inc Senior Project M ager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 5 o,-~S~RO+-F~~,BKeY ~ } ~ ~,, ~\ ~ - -OZS- - =~.- -: r_-r :, ~ ~ '~~.}~ ~ I °8 3 :~ ~ ~' n t S I ~ ;a ,. ~~ ~. . ~I 1 / ~ e ~ _ n:, ~~ . ~ / i_6 ~ ~ t f ~\ \ ~ I fiy ` ;: \ ~, .~~, 5 -615-~. - /~ r -~ ~ ~ +:~ ,,,, ..5' ~ ,~. ~'ERRAC~N REPORT N0. ~ ~ ~~~ ~~; I 0 ` I Ik i ~ -. P I I .r ~yF 1- ;x~. _ 1 ~~r~ ! y~~' `~t ;'~ rf .,,~ ~ ff ,~~I i" ~ ? ~ ~: ~ (:-. ~~a V ~ i i I ~, G. ~ ~ ~' r~ II ~ ,L~ I << I I ' ~'~~ -~~ ~i I 1 I ', I ~ ; ;. ~ '~I! ~~~ I ~I ~. I I I '~ I '' I 1 (~ II I _~._-_---- h i ~- fl ~I ~.r, ~ ' I ~ - ,1 C a ~ ,y} I ~ ~ ~1 M ' I yS J ---- _ :~ .~~ ~ I ~ - `~' I f ~ a s ~~~~ I F ~ ~~ ~ ~ ~ C~ I I ~\ ,~~ ~~ x3" I ~~ I I I _J I II ~~ ~~ _I~ ~ "I i ~~ /~ / ~'~--~~22 ~/ ~ .~. _{ I ;. i } .~, ~.. .. -/-- -- I I ~- - -•-/ i~ / I I I -'' r ~-- - ,~ _ _ -~ :~ - - __.- :. _., . // ., 1 a ~ J?t ;~ - ~~~ ~ /-~~ }" i ~ I i - ~'-- - I j .` 'ICJ }'~ '~] !! I f ~. t ~ _ i` _ ~~ ~ I ~. 1~~ ~ '>~, l~ { / / ' ~~ 1 °i ~ II ,1:~ _ ~. I~~. I ~ I r'~~ i~ ~ ~,~ . ,. .J~ ~~, ~ I ~ ~ I ,~ ,~ ~ I VIII ... ' ;_1 ~~ III ~' «i ,.III ~- ~' ~~ ~ ! e '~y' (~ , ~ .; I , _. I~ _..___ ._._-- - ~ r--,~~_,-- ~ _ .- ,. __ . _ _ J iI i it ~,_ ~ li li I~ j: I,• 1. I; i; I ~I. ,. L ; Q