Deer Run-LR000419CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12 28.27 square inches CYLINDER NUMBER AGE (days) DATE TESTED TOTAL LOAD (pounds) COMPRESSIVE STRENGTH (psi) SPECIFIED COMPRESSIVE STRENGTH (psi) DRC 33 7 02/28/00 80000 2830 4000/28 days DRC 34 28 03/20/00 95000 3360* DRC 35 28 03/20/00 96000 3400* DRC 36 56 04/18/00 115000 4070 Specifications: Making ASTM C -31 Curing: Testing ASTM C -143, Methods: ASTM C -39 Fracture mode Types of Fracture: ArA is (A) unless otherwise noted 1 B7 D FUGRO SOUTH, INC. COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Ryland Homes PROJECT: Deer Run, Coppell, Texas SAMPLE DATE: February 21, 2000 CONTRACTOR: TICKET NO.: AMBIENT TEMP. °F): CONCRETE TEMP. °F) (ASTM C- 1064): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: REMARKS: Does not meet required compressive strength at 28 days. Technician: Dumitru Balas SMH /rm Distribution: Ryland Homes Philip Flink City of Coppell Garth Campbell Gilco Mark Leonard CONCRETE SUPPLIER: PLANT/TRUCK: MIX ID NUMBER: AIR (ASTM C -231) WATER ADDED (gal): SLUMP (in.) (ASTM C -143) FUGRO SOUTH INC. Reviewed By: 2880 Virgo Lane: Dallas, Texas 75229 Ph (972) 484 -8301; Fax (972) 620 -7328 REPORT DATE: April 19, 2000 PROJECT NO: 0791 -2308 Gilco Contracting 473925 60 60 9:36 am 10:10 am Cloudy Paving, on intersection west Hawkins Drive with south Hawkins Drive Pioneer Concrete 27/807 7724 6 10 7