Deer Run-LR000321CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12 28.27 square inches CYLINDER NUMBER AGE (days) DATE TESTED TOTAL LOAD (pounds) COMPRESSIVE STRENGTH (psi) SPECIFIED COMPRESSIVE STRENGTH (psi) DRC 33 7 02/28/00 80000 2830 4000/28 days DRC 34 28 03/20 /00 95000 3360* DRC 35 28 03/20/00 96000 3400* DRC 36 56 04/18/00 Specifications: Making ASTM C -31 Curing: Testing ASTM C -143, Methods: ASTM C -39 Fracture mode Types of Fracture: A is (A) unless otherwise noted T C Z D B T FUGRO SOUTH, INC. COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Ryland Homes PROJECT: Deer Run, Coppell, Texas SAMPLE DATE: February 21, 2000 CONTRACTOR: TICKET NO.: AMBIENT TEMP. °F): CONCRETE TEMP. °F) (ASTM C 1064): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: REMARKS: Does not meet required compressive strength at 28 days. Technician: Dumitru Balas SMH/rm Distribution: Ryland Homes Philip Flink City of Coppell Garth Campbell Gilco Mark Leonard FUGRO SOUTH INC. Reviewed By: GEM El 2880 Virgo Lane; Dallas, Texas 75229 Ph (972) 484 -8301; Fax (972) 620 -7328 REPORT DATE: March 21, 2000 PROJECT NO: 0791 -2308 Gilco Contracting 473925 CONCRETE SUPPLIER: Pioneer Concrete 60 PLANT/TRUCK: 27/807 60 MIX ID NUMBER: 7724 9:36 am AIR (ASTM C 231) 6 10:10 am WATER ADDED (gal): 10 Cloudy SLUMP (in.) (ASTM C -143) 7 Paving, on intersection west Hawkins Drive with south Hawkins Drive