Deer Run-LR000229CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12 28.27 square inches
CYLINDER
NUMBER
AGE
(days)
DATE
TESTED
TOTAL
LOAD
(pounds)
COMPRESSIVE
STRENGTH
(psi)
SPECIFIED COMPRESSIVE
STRENGTH
(psi)
DRC 33
7
02/28/00
80000
2830
4000/28 days
DRC 34
28
03/20/00
DRC 35
28
03/20/00
DRC 36
Hold
Specifications:
Making ASTM C -31
Curing:
Testing ASTM C -143,
Methods: ASTM C -39
Fracture mode
Types of
Fracture: A
is (A) unless otherwise noted
gli
rA B L C D
FUGRO SOUTH, INC.
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Ryland Homes
PROJECT: Deer Run, Coppell, Texas
SAMPLE DATE: February 21, 2000
CONTRACTOR:
TICKET NO.:
AMBIENT TEMP. °F):
CONCRETE TEMP. °F) (ASTM C 1064):
TIME BATCHED:
TIME SAMPLED:
WEATHER CONDITION:
LOCATION OF PLACEMENT:
REMARKS:
Technician: Dumitru Balas
S M H /rm
Distribution:
Ryland Homes Philip Flink
City of Coppell Garth Campbell
Gilco Mark Leonard
Gilco Contracting
473925
60
60
9:36 am
10:10 am
Cloudy
CONCRETE SUPPLIER: Pioneer Concrete
PLANT/TRUCK: 27/807
MIX ID NUMBER: 7724
AIR (ASTM C 231) 6
WATER ADDED (gal): 10
SLUMP (in.) (ASTM C 143) 7
Paving, on intersection west Hawkins Drive with south Hawkins Drive
FUGRO SOUTH INC.
Reviewed By:
GIRO
LTLIP
im
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484 -8301; Fax (972) 620 -7328
REPORT DATE: February 29, 2000
PROJECT NO: 0791 -2308