Loading...
Gateway BP(1.6)-LR061030;CONCRETE COMPRESSIVE STRENGTH TEST • 94061163 0128 l~~rracon Report Number. Service Date: October 21, 2006 6901 Carpenter Fnnry, ste #too Dallas, Texas 75247 (214) 630-1010 Client: Report Date:October 30, 2006 ProLogis Project: Freeport Corporate Ctr. Bldg. 6 Attn: Keith Porter Freeport Pkwy & Gateway 2310 LBJ Freeway Ste 200 Coppell, TX Dallas TX 75234 Project No.: 94061163 Material Information Specified Strength: 3500 psi cLD 28 Days Batch Time: 3:02am Plant: 27 Supplier: Southern Star Truck No: 5019 Ticket No: 1448986 Mix I.D. No.: 9339 Water Added Onsite Before Test: SGallons Field Tesf Data Test Res u It Slump, inches: 6.00 Air Content, %: 3.7 Concrete Temperature, ~F: 74 Ambient Temperature,~F: 54 Plastic Unit Weight, pcf: 144.9 Sample Information Date Cast: October 21, 2006 Time: 3:34am Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 40 Placement Method: Pump Sample Locations: See attached sketch for Location #1 Placement Location: Pavement, E of Building Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 " =Field Test Results do not meet project specifications. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 1 1 6.00 28.27 10/28/200fi 7 81,890 2,900 2 6.00 28.27 10/28/2006 7 82,830 2,930 Average (7 Days) 2,920 3 11 /18/2006 28 4 11 /18/2006 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 °'."`~°,_FN°'° "eY CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061163.0128 l~~rracon Service Date: October 21, 2006 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214} 630-t 010 Client: Report Date: October 30, 2006 ProLogis Project: Freeport Corporate Ctr. Bldg. 6 Attn: Keith Porter Freeport Pkwy & Gateway 2310 LBJ Freeway Ste 200 Coppell, TX Dallas TX 75234 Project No.: 94061163 Material Information Specified Strength: 3500 psi ~ 28 Days Batch Time: 4:10am Plant: 27 Supplier: Southern Star Truck No: 1827 Ticket No: 1448993 Mix I.D. No.: 9339 Field Test Data Test Result Slump, inches: 6.00 Air Content, %: 3.8 Concrete Temperature, °F: 74 Ambient Temperature,~F: 53 Plastic Unit Weight, pcf: 144.8 Sample Information Date Cast: October 21, 2006 Time: 5:OOam Sampled by: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 110 Placement Method: Pump Sample Locations: See attached sketch for Location #2 Placement Location: Pavement, E of Building Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 * =Field Test Results do not meet project specifications. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 2 1 6.00 28.27 10/28/2006 7 81,520 2,880 2 2 6.00 28.27 10/28/2006 7 84,350 2,980 Average (7 Days) 2,930 2 3 11/18/2006 28 2 4 11 /18/2006 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep: Jose A. Martinez Report Distribution: (1) ProLogis (1) Meinhardt & Assoc Architects PLLC (1) City of Coppell TX (1) Jordan Construction Services Reviewed by: (1) City of Coppell TX (1) Meinhardt & Assoc Architects PLLC Robert D. Ray, .T. (1) Haynes Whaley Assoc Inc Senior Project Hager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page Z of 2 °~-~s~°,-FU°~a".Y m . ~~ '-61~-_ ~ _---_ / -_~ TERRACON REPORT N0. ~~abl! ~3 . ~r2 ~ -ozs_ - ---- -_~ '~~ s~ ~ ~~ ~~ ~ ~~ ~. ' `wi F....{ f~ °~`~- G^~` -~z5- ~~- ~,-- ~ ~- ~ ~~ i ~,,~ ~ ,~ ~ ,~ ~~~~~-~