SS9901-CS050302Turner Collie 0Braden Inc. TRANSMITTAL
To: See Distribution of-,
From: Erika K. Cooper, P.E. — TCB
Date: March 2, 2005
Job No.: 052 131124.0001 04000.Al23 (2.1)
Subject: Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
DeForest & Sandy Lake Wastewater Lift Stations
Shop Drawing Review Comments
Submittal No. 04- 44 -047A (Generator Connection Panel Assembly)
Submittal No. 04- 44 -048A (Pipe & Misc)
TCB has the following comments on these submittals:
Description
Status
Comment
Generator Connection
No Exception Taken
Panel Assembly
Pipe & Misc
Make Corrections Noted
• Use ductile iron thickness Class 50 for
16 -inch, 20 -inch, and 30 -inch yard
piping
• Maximum joint deflection of full length
pipe must not exceed 80% of
manufacturer's recommended maximum
deflection
• Use ductile iron thickness Class 53
(minimum) for all above grade piping in
lift stations and valve vaults
• Provide Megalug for PVC pipe on
bypass lines at Deforest and Sandy Lake
• 3/4 -inch or 1 -inch post hydrant not
needed
• On 2 -inch post hydrant, provide national
straight thread hose connection, 1/8-
inch (minimum) drain hole, and
aluminum casing guard
• Provide 4 -inch PVC hub on floor drain
• Size Link -Seal per manufacturer's
recommendation for opening and pipe
sizes
When you re- submit the shop drawings, please address all comments and submit eight (8) copies to
this office.
Distribution: [X] 2 copies of submittal to the City
[X] 4 copies of submittal to Can -Fer Construction Company, Inc.
[X] 2 copies of submittal to TCB file