SS9901-CS050201TurnerCollieOBraden Inc
TRANSMITTAL
To: See Distribution 0-
From: Erika K. Cooper, P.E. — TCB
Date: February 1, 2005
Job No.: 052 131124.0001 04000.Al23 (2.1)
Subject: Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
DeForest & Sandy Lake Wastewater Lift Stations
Shop Drawing Review Comments
Submittal No. 04 -44 -031 A (Backflow Preventor)
Submittal No. 04- 44 -034A (Automatic Transfer Switches)
Submittal No. 04- 44 -035A (Electrical Items Square D)
TCB has the following comments on these submittals:
Description
Status
Comment
Backflow Preventor
Make Corrections Noted
• City Standard Detail requires 210 °F
max temp range
Automatic Transfer
Make Corrections Noted
• Verify foot print with other electrical
Switches
equipment provided
0 No exception with enclosure
Electrical Items
Make Corrections Noted
. Provide RUN command designator in
motor starter control diagram. Run
command appears to be in HOA switch
position "O"
• No exception with panel boards
• No exception with TVSS unit verify
service voltage application with utility
service supply. Limit conductor length
to perform with manufacturer's
submitted charts
• No exception with transformer and
safety switches
• Verify motor hp for manual starters with
actual equipment provided.
When you re- submit the shop drawings, please address all comments and submit eight (8) copies to
this office.