Coppell Trade 2-LR061014F~ _ U.
FARGO CONSULTANTS, INC
11440 Reeder Rd. Dallas, 'T'exas 75229
Tel. 214-352-4100 Fax. 214-352-4811
Page 1 of 1
WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Cornmerc>al
Project: Coppell Trade Center Building D
Coppell, Texas
Injection Contractor: Mcfadden & Miller
Date of Service: 10/14/06
Project No: M06-1165
Location: Bulldmg pad, eastern '/2 - 2° pass
Area injected previously: Approximately 14,200 square feet of 2nd pass
Area injected (on this day): Approximately 9,200 square feet of 2nd pass
Area injected (to date): Approximately 23,400 square feet of 2nd pass
Gallons of Water used: 50,400
Surfactant Used: lgallon / 3,500 gallons of water
Injection Pressure (psi): 100
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12-18
Total Depth of Injection (feet): 12
Remarks:
Time
Start 7 00 a.m.
End 2 45 p.m.
Technician. Joshua Solon
Distribution. Holt Lansford Commercial -Ken Newman
Mcfadden & Miller- Jon Jacobson
City ofCoppell -Lee Stone
Specified Requirements
as per manufacturer
50 psi-100pst
5 feet (max.)
12 inches
12 feet
Water Meter Reading
7703900
7753300
Checked by
LIMITATIONS. This report presents test results (at particular locations noted) based ou data obtained from specific samples selected for testing. Fargo Consultants, Inc. assumes no
responsibility for variation in quality performance, feature or conditions beyond its control. 'This report is for the exclusive use of the person(s) to whom it is addressed
and may not be reproduced except in full without the written approval of Fargo Consultants, Inc.
Ceotechnical Engineering Construction Materials Testing Environmental Services