WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Commercial
Project: Coppell Trade Center Bu>Idmg D
Coppell, Texas
Injection Contractor: Mcfadden & Miller
Date of Service: 10/12/06
Project No: M06-1165
Location: Butldmg pad, east 1/2
Area injected previously: Approximately 44,380 square feet of 1St pass and 4,000 square feet of 2nd pass
Area injected (on this day): Approximately 10,000 square feet of 1St and 5,500 square feet of 2nd pass
Area injected (to date): Approximately 54,380 square feet of 1St pass and 9,500 square feet of 2nd pass
Gallons of Water used: 54,200
Surfactant Used: lgallon / 3,500 gallons of water
Injection Pressure (psi): 100
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12-18
Total Depth of Injection (feet): 12
Remarks:
Time
Start 700 a.m.
End 2 54 p.m.
Technician. Joshua Solon
Distribution. Holt Lansford Commercial -Ken Newman
Mcfadden & Miller -Jon Jacobson
City of Coppell -Lee Stone
Saecified Reauirements
as per manufacturer
50 psi-100psi
5 feet (max.)
12 inches
12 feet
Water Meter Reading
7,603,200
7,657,400
Checked by
LIMITATIONS. This report presents test results (a[ particular locations noted) based on data obtained from specific samples selected for testing. Fargo Consultants, fnc. assumes no
responsibility for variation in quality, performance, feature or conditions beyond its control. This report is for the exclusive use of the person(s) to whom it is addressed
and may not be reproduced except iu full without the written approval of Fargo Consultants, Inc.