Coppell Trade 2-LR061011~ _ a
FARGO CON3ULTAN'TS, INC
WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Commercial
Project: Coppell Trade Center Building D
Coppell, Texas
Injection Contractor: Mcfadden & Miller
11440 Reeder Rd. Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
Pagelofl
Date of Service: 10/11/06
Project No: M06-1165
Location: Building pad, east half - 2° pass
Area injected previously: Approximately 39,580 square feet of 1St pass and 0 square feet of 2°d pass
Area injected (on this day): Approximately 4,800 square feet of lst pass and 4,000 square feet of 2na pass
Area injected (to date): Approximately 44,380 square feet of lst pass and 4,000 square feet of 2°d pass
Gallons of Water used: 55,3000
Surfactant Used: /gallon / 3,500 gallons of water
Injection Pressure (psi): 100
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12-18
Total Depth of Injection (feet): 12
Remarks:
Time
Start 7 10 a.m.
End 3 10 p.m.
Technician. Joshua Solon
Destruction. Holt Lansford Commercial -Ken Newman
Mcfadden & Miller -Jon Jacobson
City of Coppell -Lee Stone
Specified Reauirements
as per manufacturer
50 psi-100ps1
5 feet (max )
12 inches
12 feet
Water Meter Reading
7,547,900
7,603,200
Checked by:
LIMITATIONS This report presents test results (at particular locations noted) based on data obtained from specific samples selected for testing. Fargo Consultants, Inc. assumes no
responsibility for variation in quality, performance, feature or conditions beyond its control. This report is for the exclusive use of the person(s) to whom it is addressed
and may not be reproduced except in full without the written approval of Fargo Consultants, Inc.
Geotechnical Engineeritag Const~zcction Materials Testing Environmental Services
www. dallasfargo. coin