Concrete Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-184
Report Date: 01/05/2007
Strength
Slump
Air Content
Specifications
3600 psi @ 28 Days
5 in max
3 % min 6 % max
n/a
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Concrete Temperature
Ambient Temperature
400 F min
Test Data
11/07/2006
Zach Hartgraves
Clear/Sunny
On Site/
ASTM C231
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
N/A
4.5 in
780 F
Paving:
Time Batched: 09:35
Air Content: 4.0 %
Ambient Temperature: 67" F
Median at Intersection of Sandy Lake Rd and North ,
Sample Location:
2' South of North Curb at Sta. 27+00
Concrete Compression Test R
Time Sampled: 10:00
Unit Weight: N/A
Yardage (c.y.): 30 of 120
st half of Median
Fracture
Type
C-cone/shear
B-cone/split
C-cone/shear
C-cone/shear
B-cone/split
Cylinder Age Max Load
Set # # Test Date (days) (Ibs. force)
02 SLR11070605 11/10/2006 3 61280
02 SLR 11070606* 11/14/2006 7 71220
02 SLR 11070607 12/05/2006 28 87440
02 SLR11070608 12/05/2006 28 89330
02 SLR 11070609* 01/02/2007 56 89810
Area
(sq,in,)
27.90
28,09
28.18
28.18
27.99
28 day average
Normal cylinder size: 6" x 12" 0
The average 28 day compressive strength test results do not meet specifications, It' 1\
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 O~3VO \
o Gallons of Water Added On-Site ~\ \)
* 7-DAY TEST RESULT INDICATES A MARGINAL 28-DAY COMPRESSIVE STRENGTH
* 28-DAY TEST RESULTS NON-COMPLIANT; CONTRACTOR NOTIFIED VIA FAX ON 12/0 2006.
"HOLD" CYLINDER TO BE TESTED AT 56 DAYS,
*56 Day Non Compliant Contractor Notified
CMJ Engineering, 'nc
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report, The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc,
o I Page I of I
Concrete Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-183
Report Date: 12/08/2006
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
11/07/2006
Zach Hartgraves
Foggy
Southern Star/1618-B
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1449353 Time Batched: 07:36
4 in Air Content: 5.0 %
740 F Ambient Temperature: 550 F
Inlet Top: Sta. 1+00.07, Storm Drain Lateral A5-2
Time Sampled: 08:10
Unit Weight: N/A
Yardage (c.y.): 7 of 7
Sample Location:
Inlet Top: Sta. 1 +00.07, Storm Drain Lateral A5-2
Concrete Compression Test Results
Cylinder Age Max Load Area stren~th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
01 SLR11070601 11/14/2006 7 134340 28.09 4780 C-cone/shear
01 SLR11070602 12/05/2006 28 164530 28.18 5840 E-columnar
01 SLR11070603 12/05/2006 28 162550 28.18 5770 E-columnar
01 SLR11070604 Hold
28 day average 5810
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
filt
f'I'
R. Carl Lee, S.E.T.
Vice PresidentlCMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific sample, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page I of I
Concrete Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppel!
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-184
Report Date: 12/08/2006
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
11/07/2006
Zach Hartgraves
Clear/Sunny
On Site/
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
5 in max
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
N/A
4.5 in
780 F
Paving:
Time Batched: 09:35 Time Sampled: 10:00
Air Content: 4.0 % Unit Weight: N/A
Ambient Temperature: 67" F Yardage (c.y.): 30 of 120
Median at Intersection of Sandy Lake Rd and North Point, West half of Median
Sample Location:
2' South of North Curb at Sta. 27+00
Concrete Compression Test Results
Cylinder Age Max Load Area Stren8th Fracture
Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type
02 SLR11070605 11/10/2006 3 61280 27.90 2200 C-cone/shear
02 SLR11070606* 11/14/2006 7 71220 28.09 2540 B-cone/split
02 SLR 11070607 12/05/2006 28 87440 28.18 3100 C-cone/shear
02 SLR11070608 12/05/2006 28 89330 28.18 3170 C-cone/shear
02 SLR11070609 01/02/2007 56
28 day average 3140
Normal cylinder size: 6" x 12"
The average 28 day compressive strength test results do not meet specifications.
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
* 7-DAY TEST RESULT INDICATES A MARGINAL 28-DAY COMPRESSIVE STRENGTH
* 28-DAY TEST RESULTS NON-COMPLIANT; CONTRACTOR NOTIFIED VIA FAX ON 12/05/2006.
"HOLD" CYLINDER TO BE TESTED AT 56 DAYS.
CMJ Engineering, In
LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity, Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page I of I
Concrete Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-183
Report Date: 11/17/2006
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Test Data
11/07/2006
Zach Hartgraves
Foggy
Southern Star/1618-B
ASTM C231
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
3600 psi @ 28 Days
4 in max
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
1449353
4in
740 F
Inlet Top:
Time Batched: 07:36
Air Content: 5.0 %
Ambient Temperature: 550 F
Sta. 1+00.07, Storm Drain Lateral A5-2
Time Sampled: 08:10
Unit Weight: N/A
Yardage (c.y.): 7 of 7
Sample Location:
Inlet Top: Sta. 1 +00.07, Storm Drain Lateral A5-2
Concrete Compression Test Results
Cylinder Age Max Load Area
Set # # Test Date (days) (Ibs. force) (sq.in.)
01 SLR11070601 11/14/2006 7 134340 28.09
01 SLR11070602 12/05/2006 28
01 SLR11070603 12/05/2006 28
01 SLR11070604 Hold
Stren.9th
(pSI)
4780
Fracture
Type
C-cone/shear
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
CMJ Engineering, 'n
R. Carl Lee, S.E.T.
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, it s, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity, Our reports are produced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc.
01 Page I of I
Concrete Compression Test Report
eM J ENGINEERING, INC.
7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993
Client:
Project:
City of Coppell
West Sandy Lake Road
Reconstruction
Report Distribution: (1) City of Coppell
(1) City of Coppell
(1) Tiseo Paving Company
(1) Teague Nail & Perkins
CMJ Report No.: 687-5192-184
Report Date: 11/17/2006
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
Specifications
Test Data
11/07/2006
Zach Hartgraves
Clear/Sunny
On Site!
ASTM C231
3600 psi @ 28 Days
5 in max
3 % min 6 % max
n/a
400 F min
Placement Date
Sampled By
Weather
Supplier/Mix
Air Content Method
Cylinder Age Max Load Area
Set # # Test Date (days) (Ibs. force) (sq.in.)
02 SLR11070605 11/10/2006 3 61280 27.90
02 SLR11070606* 11/14/2006 7 71220 28.09
02 SLR11070607 12/05/2006 28
02 SLR11070608 12/05/2006 28
02 SLR11070609 Hold
Ticket Number:
Slump:
Concrete Temperature:
Placement Location:
Sample Location:
N/A
4.5 in
780 F
Paving:
Time Batched: 09:35 Time Sampled: 10:00
Air Content: 4.0 % Unit Weight: N/A
Ambient Temperature: 670 F Yardage (c.y.): 30 of 120
Median at Intersection of Sandy Lake Rd and North Point, West half of Median
2' South of North Curb at Sta. 27+00
Concrete Compression Test Results
Strength
(psi)
2200
2540
Fracture
Type
C-cone!shear
B-cone/split
Normal cylinder size: 6" x 12"
Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
o Gallons of Water Added On-Site
* 7-DAY TEST RESULT INDICATES A MARGINAL 28-DAY COMPRESSIVE STRENGTH
I
CMJ Engineering,,"nc
R. Carl Lee, S.E.T,
Vice President/CMT Manager
LIMITATIONS: The test results presented in this report apply only to the specific samples, item, and areas described within this report. The test results
do not pertain to any other samples, items or areas regardless of similarity, Our reports are pr duced solely for the exclusive use of our
client. This report or any portion of this report may not be reproduced without the written con ent of our client and CMJ Engineering, Inc.
01 Pagelofl