Coppell Trade 2-LR061017FGD _
~,
FARC:C CON.9UL't'AIV'Pki, INC.
11440 Reeder Rd. • Dallas,'I'exas ?5229
Tel. 214-352-4100 Fax. 214-352-4811
Pagelofl
WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Commercial
Project: Coppell Trade Center Building D
Coppell, Texas
Injection Contractor: McFadden and Miller
Date of Service: 10/17/06
Project No: M06-1165
Location: Building pad, east half - 2n pass
Area injected previously: Approximately 23,400 square feet of 2°d pass
Area injected (on this day): Approximately 9,300 square feet of 2 pass
Area injected (to date): Approximately 32,700 square feet of 2"d pass
Gallons of Water used: 56,000
Surfactant Used: /gallon / 3,500 gallons of water
Injection Pressure (psi): 100
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12-18
Total Depth of Injection (feet): 12
Remarks:
Time
Start 7:00 a.m.
End 2:57 p.m.
Technician: Joshua Solon
Distribution: Holt Lansford Commercial -Ken Newman
Mcfadden & Miller -Jon Jacobson
City of Coppell -Lee Stone
Specified Requirements
as per manufacturer
50 psi-100psi
5 feet (max.)
12 inches
12 feet
Water Meter Reading
7,796,500
7,852,500
Checked by:
LIMITATIONS: This report presents test results (a[ particular locations noted) based on data obtained from specific samples selected for testing. Fargo Cousultants, Inc. assumes no
responsibility for variation in quality, performance, feature or conditions beyond its control. This report is for the exclusive use of the person(s) to whom it is addressed
and may not be reproduced except in full without the written approval of Fargo Consultants, Inc.
Geotechnical Engineering ~ Constrc~etion Materials Testi~zg • Environmental Services
www. dallasfargo. com