Coppell Trade 2-LR061113/'1 _ ~"~.
FARCSO CONBi~LZ'a~'3'6, INC.
11440. Reeder Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
Page 1 of 1
WATER PRESSURE INJECTION
OBSERVATION REPORT
Client. H~It Lunsford Commercial
Project: C,~ppell Trade Center Building D
C~ppell, Texas
Injection Contractor: Mcfadden & Miller
Date of Service: 11/13/06
Project No: M06-1165
Location: Building pad -west half
Area injected previously: Approximately 0 square feet of 4th pass
Area injected (on this day): Approximately 19,500 square feet of 4th pass
Area injected (to date): Approximately 19,500 square feet of 4th pass
Gallons oiWater used: 41,000
Surfactant Used: lgallon / 3,500 gallons of water
Injection Pressure (psi): 90
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12
Total Depth of Injection (feet): 12
Remarks:
Time
Start 7:00 a.m. / 2:00 p.m.
End 9:30 a.m. / 3:00 p.m.
Technician: Gary Moore, C.E.T.
Specified Requirements
as per manufacturer
50 psi-100psi
5 feet (max.)
12 inches
12 feet
Water Meter Reading
9069000
9110600
~~ if
Checked by: °' ~ ~
Distribution: Holt Lansford Commercial -Ken Newman
Mcfadden & Miller-Jon Jacobson
City of Coppell -Lee Stone
LIMITATIONS: "fLis report presents test results (at particular locations noted) based on data obtained from specific samples selected for testing. Fargo Consultants, Inc. assumes no
responsibility for variation in quality, performance, feature or conditions beyond its control. This report is for the exclusive use of the person(s) to wham it is addressed
and may not be reproduced except in full without the written approval of Fargo Consultants, lnc.