Coppell Trade 2-LR061031FAR~00 CONSULTANTS, INC.
11440 Reeder Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
Page 1 of 1
WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Commercial
Project: Coppell Trade Center Building D
Coppell, Texas
Injection Contractor: Mcfadden & Miller
Date of Service: 10/31/06
Project No: M06-1165
Location: Building pad, west half
Area injected previously: Approximately 37,600 square feet of 1St pass
Area injected (on this day): Approximately 9,500 square feet of 1St pass
Area injected (to date): Approximately 47,100 square feet of 1St pass
Gallons of Water used: 60,000
Surfactant Used: lgallon / 3,500 gallons of water
Injection Pressure (psi): 100
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12-18
Total Depth of Injection (feet): 12
Remarks:
Time
Start 7:30 a.m. / 2:00 p.m.
End 9:00 a.m. / 3:00 p.m.
Saecified Requirements
as per manufacturer
50 psi-100psi
5 feet (max.)
12 inches
12 feet
Water Meter Reading
8442500
8502500
Technician: Joshua Solon
Distribution: Holt Lansford Commercial -Ken Newman
Mcfadden & Miller -Jon Jacobson
City of Coppell -Lee Stone
Checked by:
LIMITATIONS: This report presents test results (at particular locations noted) based on data obtained from specific samples selected for testing. Fargo Consultants, Inc. assumes no