ST9902-LR061208 Concrete Compression Test Report eM J ENGINEERING, INC. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Project: City of Coppell West Sandy Lake Road Reconstruction Report Distribution: (1) City of Coppell (1) City of Coppell (1) Tiseo Paving Company (1) Teague Nail & Perkins CMJ Report No.: 687-5192-197 Report Date: 12/28/2006 Strength Slump Air Content Specifications 3600 psi @ 28 Days 5 in max 3 % min 6 % max n/a 400 F min Placement Date Sampled By Weather Supplier/Mix Air Content Method Test Data 11/28/2006 Brent Talcott Partly Cloudy/Light Breeze Redi Mix/732 ASTM C231 Concrete Temperature Ambient Temperature Ticket Number: Slump: Concrete Temperature: Placement Location: 181146 5in 770 F Paving: Time Batched: 08:42 Air Content: 4.2 % Ambient Temperature: 77" F Sandy Lake Rd, Median Tips at Intersection with Royal Lane Time Sampled: 09:40 Unit Weight: N/A Yardage (c.y.): 10 of 10 Sample Location: East Median Tip Concrete Compression Test Results Cylinder Age Max Load Area Strenth Fracture Set# # Test Date (days) (Ibs. force) (sq.in.) (pSI Type 01 SLR11280601 12/05/2006 7 163260 28.18 5790 E-columnar 01 SLR 11280602 12/26/2006 28 181420 28.09 6460 01 SLR 11280603 12/26/2006 28 181860 28.09 6470 01 SLR 11280604 Hold 28 day average 6470 Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231. o Gallons of Water Added On-Site CMJ Engineering, 'nc R. Carl Lee, S.E.T. Vice President/CMT Manager LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. 01 Pagelofl .. eM J ENGINEERING, INC. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Concrete Compression Test Report Client: Project: City of Coppell West Sandy Lake Road Reconstruction Report Distribution: (1) City of Coppell (1) City of Coppell (1) Tiseo Paving Company (1) Teague Nail & Perkins CMJ Report No.: 687-5192-198 Report Date: 12/28/2006 3 % min 6 % max n/a 400 F min Placement Date Sampled By Weather Supplier/Mix Air Content Method Test Data 11/28/2006 Richard Jones Partly Cloudy/Light Winds Southern Star/9618-B ASTM C231 Strength Slump Air Content Concrete Temperature Ambient Temperature Specifications 3600 psi @ 28 Days 4 in max Sample Location: 1538416 Time Batched: 13:20 Time Sampled: 14:15 3.75 in Air Content: 3.5 % Unit Weight: N/A 800 F Ambient Temperature: 74' F Yardage (c.y.): 7.5 of 7.5 Rip Rap: Downward Slope on the North Edge of Westbound Sandy Lake Rd just East of Entrance to 944 Sandy Lake Rd Rip Rap: Downward Slope on the North Edge of Westbound Sandy Lake Rd just East of Entrance to 944 Sandy Lake Rd Ticket Number: Slump: Concrete Temperature: Placement Location: Concrete Compression Test Results Cylinder Age Max Load Area Stren~th Fracture Set # # Test Date (days) (Ibs. force) (sq.in.) (pSI Type 02 SLR11280605 12/05/2006 7 123920 28.18 4400 E-columnar 02 SLR 11280606 12/26/2006 28 146640 28.09 5220 E-columnar 02 SLR 11280607 12/26/2006 28 149500 28.09 5320 C-cone/shear 02 SLR11280608 Hold 28 day average 5270 Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231. o Gallons of Water Added On-Site CMJ Engineerin ,I c R. Carl Lee, S.E.T. Vice President/CMT Manager LIMITATIONS: The test results presented in this report apply only to the specific samples, I s, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. OJ Page 1 of I Concrete Compression Test Report eM J ENGINEERING, INC. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Project: City of Coppell West Sandy Lake Road Reconstruction Report Distribution: (1) City of Coppell (1) City of Coppell (1) Tiseo Paving Company (1) Teague Nail & Perkins CMJ Report No.: 687-5192-197 Report Date: 12/08/2006 Strength Slump Air Content Specifications 3600 psi @ 28 Days 5 in max 3 % min 6 % max Placement Date Sampled By Weather Supplier/Mix Air Content Method Test Data 11/28/2006 Brent Talcott Partly Cloudy/Light Breeze Redi Mix/732 ASTM C231 Concrete Temperature n/a Ambient Temperature 400 F min 1.11111111,111 Ticket Number: 181146 Time Batched: 08:42 Time Sampled: 09:40 Slump: 5 in Air Content: 4.2 % Unit Weight: N/A Concrete Temperature: 770 F Ambient Temperature: 770 F Yardage (c.y.): 10 of 10 Placement Location: Paving: Sandy Lake Rd, Median Tips at Intersection with Royal Lane Sample Location: East Median Tip Concrete Compression Test Results Cylinder Age Max Load Area Set # # Test Date (days) (Ibs. force) (sq.in.) 01 SLR11280601 12/05/2006 7 163260 28.18 01 SLR11280602 12/26/2006 28 01 SLR11280603 12/26/2006 28 01 SLR11280604 Hold Stren.9th (pSI) 5790 Fracture Type E-columnar Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231. o Gallons of Water Added On-Site CMJ Engineering, I C R. Carl Lee, S.E.T. Vice President/CMT Manager LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. 01 Page 1 of 1 Concrete Compression Test Report eM J ENGINEERING, INC. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Project: City of Coppell West Sandy Lake Road Reconstruction Report Distribution: (1) City of Coppell (1) City of Coppell (1) Tiseo Paving Company (1) Teague Nail & Perkins CMJ Report No.: 687-5192-198 Report Date: 12/08/2006 Strength Slump Air Content Concrete Temperature Ambient Temperature Specifications Test Data 11/28/2006 Richard Jones Partly Cloudy/Light Winds Southern Star/9618-B ASTM C231 3600 psi @ 28 Days 4 in max 3 % min 6 % max n/a 40. F min Placement Date Sampled By Weather Supplier/Mix Air Content Method Cylinder Age Max Load Area Set # # Test Date (days) (Ibs. force) (sq.in.) 02 SLR11280605 12/05/2006 7 123920 28.18 02 SLR 11280606 12/26/2006 28 02 SLR11280607 12/26/2006 28 02 SLR11280608 Hold Ticket Number: Slump: Concrete Temperature: Placement Location: Sample Location: 1538416 Time Batched: 13:20 Time Sampled: 14:15 3.75 in Air Content: 3.5 % Unit Weight: N/A 800 F Ambient Temperature: 740 F Yardage (c.y.): 7.5 of 7.5 Rip Rap: Downward Slope on the North Edge of Westbound Sandy Lake Rd just East of Entrance to 944 Sandy Lake Rd Rip Rap: Downward Slope on the North Edge of Westbound Sandy Lake Rd just East of Entrance to 944 Sandy Lake Rd Concrete Compression Test Results Stren,gth (pSI) 4400 Fracture Type E-columnar Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064. and C617 or C1231. o Gallons of Water Added On-Site CMJ Engineering, In LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. o I Page 1 of 1