WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Commercial
Project: Coppell Trade Center Building D
Coppell, Texas
Injection Contractor: Mcfadden & Miller
Date of Service: 11/02/06
Project No: M06-1165
Location: Building pad -east half
Area injected previously: Approximately 11, 500 square feet of 4th pass
Area injected (on this day): Approximately 16,000 square feet of 4th pass
Area injected (to date): Approximately 27,500 square feet of 4th pass
Gallons of Water used: 65,000 Specified Requirements
Surfactant Used: /gallon / 3,500 gallons of water as per manufacturer
Injection Pressure (psi): 80 50 psi-100psi
Injection Probe Spacing (feet): 5 5 feet (max.)
Injected Depth Interval (in.) until refusal: 12 12 inches
Total Depth of Injection (feet): 12 12 feet
Remarks:
Time Water Meter Reading
Start 7:30 a.m. / 2:00 p.m. 8558500
End 9:00 a.m. / 3:00 p.m. 8623500
Technician: William Youngstrom Checked by:
Distribution: Holt Lansford Commercial -Ken Newman
Mcfadden & Miller -Jon Jacobson
City of Coppell -Lee Stone
LIMITATIONS: This report presents test results (at particular locations noted) based on data obtained from specific samples selected for testing. Fargo Consultants, Inc. assumes no
responsibility for variation in quality, performance, feature or conditions beyond its control. This report is far die exclusive use of the person(s) [o whom it is addressed
and may not be reproduced except in full without the written approval of Fargo Consultants, Inc.
Geotechnical Engineering • Consbz~ction Materials Testing • Environmental Services
www. dallasfargo. com