WATER PRESSURE INJECTION
OBSERVATION REPORT
Client: Holt Lunsford Commercial
Project: Coppell Trade Center Building D
Coppell, Texas
Date of Service: 10/18/06
Project No: M06-1165
Injection Contractor: Mcfadden & Miller
Location: Building D, east half- 2° pass
Area injected previously: Approximately 32,700 square feet of 2°d pass
Area injected (on this day): Approximately 11,000 square feet of 2"d pass
Area injected (to date): Approximately 43,700 square feet of 2°d pass
Gallons of Water used: 52,000
Surfactant Used: lgallon / 3,500 gallons of water
Injection Pressure (psi): 100
Injection Probe Spacing (feet): 5
Injected Depth Interval (in.) until refusal: 12
Total Depth of Injection (feet): 12
Remarks:
Time
Start 8:00 a.m. / 2:00 p.m.
End 10:00 a.m. / 3:00 p.m.
Technician: Joshua Solon
Distribution: Holt Lansford Commercial -Ken Newman
Mcfadden & Miller -Jon Jacobson
City of Coppell -Lee Stone
Specified Repuirements
as per manufacturer
50 psi-100psi
5 feet (max.)
12 inches
12 feet
Water Meter Reading
7852500
7904500
Checked by:
LIMITATIONS: This report presents test results (at particular locations noted) based on data obtained from specific samples selected for testing. Fargo Consultants, Inc. assumes no
responsibility for variation in quality, perfonnaoce, feature or conditions beyond its control. This report is for the exclusive use of the person(s) to whom it is addressed
and may not be reproduced except in full without the written approval of Fargo Consultants, Inc.