Town Center L1B2-LR 991007CONCRETE COMPRESSIVE STRENGTH TEST fBC ENGINEERING', INC. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Date of Service: 09/29/1999 Report No.: 9926334 Report Date 10/07/1999 Client No.: 26295000 Client: Ewing Properties, Inc. Attn: Mark Morris 14990 Landmark Blvd, #300 Dallas TX 75240 -6729 Project No.: 94991134 Project: Tom Thumb Denton Tap & Sandy Lake Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast compressive strength samples. PROJECT DATA CONTRACTOR: Hill & Wilkinson CONCRETE SUPPLIER: Lattimore PLANT: 7 SPECIFICATION REQUIREMENTS STRENGTH: 3000 psi @ 28 Days SLUMP: 5.0" Max AIR: N/A TEST METHOD: ASTM C -143 28 ASTM C -172 6.50 ASTM C -39 SAMPLE LOCATION: CYLINDER MARKED SET NO. 30' from south entrance MEASURED SLUMP DATE (inches) TESTED CONCRETE CLASS: 163 PLACEMENT DATE: 09/29/1999 BATCH TIME: 7:23am TIME SAMPLED: 8:37am BY: Joey Gordon WEATHER CONDITIONS: TEMPERATURE (F) - AIR TRUCK NO: 602 AIR CONTENT ( %): N/A PLACEMENT LOCATION: Fire lane next to the dock REPORT OF TESTS Clear 66 F CONCRETE: 86 F TICKET NO: 7077761 UNIT WEIGHT (pcf): N/A MAXIMUM AGE LOAD (days) (lbs.force) ACCUMULATIVE YARDS: 10 COMPRESSIVE STRENGTH FRACTURE (psi) TYPE 1 1 6.50 10/06/1999 7 110890 3920 1 2 6.50 10/06/1999 7 106250 3760 Average 3840 1 3 6.50 10/27/1999 28 1 4 6.50 10/27/1999 28 Technician Time: See Report #9926323 This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc. O1LL Page 1 of 2 CONCRETE COMPRESSIVE STRENGTH TEST fBC INGINEERING, INC. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Date of Service: 09129/1999 Report No.: 9926334 Report Date 10/07/1999 Client No.: 26295000 Client: Ewing Properties, Inc. Attn: Mark Morris 14990 Landmark Blvd, #300 Dallas TX 75240 -6729 MEASURED SLUMP (inches) Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast compressive strength samples. PROJECT DATA CONTRACTOR: Hill & Wilkinson CONCRETE SUPPLIER: Lattimore PLANT: 7 SPECIFICATION REQUIREMENTS STRENGTH: 3000 psi @ 28 Days SLUMP: 5.0" Max AIR: N/A TEST METHOD: ASTM C -143 ASTM C -172 ASTM C -39 SAMPLE LOCATION: 25' from north corner REPORT OF TESTS ACCUMULATIVE YARDS: 10 CYLINDER MARKED SET NO. 2 1 2 2 DATE AGE TESTED (days) CONCRETE CLASS: 163 PLACEMENT DATE: 09/29/1999 BATCH TIME: 8:15am TIME SAMPLED: 10:15am BY: Joey Gordon WEATHER CONDITIONS: Clear TEMPERATURE (F) - AIR 82 F CONCRETE: 90 F TRUCK NO: 753 TICKET NO: 6108087 AIR CONTENT (%): N/A UNIT WEIGHT (pcf): N/A PLACEMENT LOCATION: See page 1 Project No.: 94991134 Project: Tom Thumb Denton Tap & Sandy Lake Coppell, Texas MAXIMUM COMPRESSIVE LOAD STRENGTH (lbs. force) (psi) 7 109380 3870 7 110250 3900 Average 3890 FRACTURE TYPE 4.50 10/06/1999 4.50 10/06/1999 2 3 4.50 2 4 4.50 Sampled from truck. Technician: Joey Gordon Report Distribution: (1) Ewing Properties, Inc. (1) S.0 Companies (1) Tom Thumb Stores Division (1) Michael F. Twichell, Inc. 10/27/1999 28 10/27/1999 28 Started: Finished: fW Engineering, Inc. (1) Raymond L. Goodson, Jr. Engrs. (1) Hill & Wilkinson, Inc. Eugene Harbour (1) City of Coppell - Engr. Dept. Vice President This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc. 01LL Page 2 of 2