Loading...
SC-Coppell MSN-LR 980516FUGRO SOUTH, INC. 2880 Virgo Lane; Dallas, Texas 75229 Ph (972) 484 -8301; Fax (972) 620 -7328 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Coppell ISD Report Date: May 16, 1998 PROJECT: Coppell Middle School North Sitework Coppell, Texas Project No.: 0771 -2094 GRO SAMPLE DATE: April: 15,1998 CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP. (°F) (ASTM C -1064) TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: K. A. Sparks 615887 CONCRETE SUPPLIER: 81 PLANTITRUCK: 80 MIX ID NUMBER: 12:05 AIR ( %) (ASTM C -231) : 1:00 WATER ADDED (gal): Partly cloudy SLUMP (in.) (ASTM C -143) : Paving: Sidewalk, southwest corner of building, east NUMBER Pioneer 74 827 10 5 10 feet south, 50 feet CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6 "'x 12'x,; 28.27 square Inches TOTAL COMPRESSIVE REQUIRED COMPRESSIVE CYLINDER AGE DATE LOAD STRENGTH STRENGTH NUMBER (days) TESTED (pounds) (psi) (psi) CNS 250 7 04/22/98 73100 2586 3000/28 days CNS 251 28 05/13/98 110000 3891 CNS 252 28 05/13/98 108000 3820 CNS 253 Hold Fracture mode is (A) unless otherwise noted Specifications: Making & ASTM C -31 Testing ASTM C -143, Types of z i Curing: i Methods: ASTM C -39 i Fracture: A® B® C D REMARKS: Technician: Pompey McGee FUGRO- McCLELLAND (SOUTHWEST), INC. Checked By: SMH /rm Distribution: Coppell ISD - Mickey Harper City of Coppell - Garreth Campbell K A Sparks Contractors, Inc. - E. J. Williams (2) SHW Group - Joe Craddock K A Sparks Contractors, Inc. - Jim Schooler SHW Group - Mike Elmore