Stoneleigh P1-LR 980413ALPHA TESTING, INC. 2209 Wisconsin St. I 100 Dallas, Texas 75229 (214) 620 -8911 TESTED FOR: FIRST WORTHING COMPANY DALLAS, TEXAS PROJECT: STONELEIGH AT RIVERCHASE COPPELL, TEXAS REPORT OF CONCRETE COMPRESSION TEST DATE OF ISSUE: OUR REPORT NO.: APRIL 13, 1998 97060 -120 FIELD DATA PAVING: 40' EAST & 15' SOUTH OF NE CORNER OF LOCATION OF CONCRETE PLACEMENT BUILDING 2 MIX PROPORTIONS (SSD) N/A CEMENT N/A WATER N/A FINE AGGREGATE N/A COARSE AGGREGATE N/A ADMIXTURE N/A COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6" X 12 ") (ASTM C -39) LAB TYPE DATE AGE TOTAL AREA COMPRESSIVE NO. CURING TESTED DAYS LOAD STRENGTH, PSI 137 LAB 04/20/98 7 88,319 28.27 3,120 138 LAB 05/11/98 28 111,929 28.27 3,960 139 LAB 05/11/98 28 99,545 28.27 3,520 140 LAB HOLD H 28.27 Specifications 28 3, 000 * CONTRACTOR INFORMED OF LOW AIR CONTENT AND HIGH SLUMP COMPU DATA- CGO10e3 -34 REMARKS ❑ Cylinders made by ALPHA representative. ❑ Cylinders made by Architect's or Contractor's representative. ❑ Cylinders picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. ❑ Compression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. ❑ Respectfully Submitted / l ` ALPHA TESTING, INC. (.- PAT STETTNER 04/13/98 DATE PLACED 11 :45 TIME SLUMP (ASTM C -143) 6 * AIR CONTENT (ASTM C -231 ❑ OR C -173 ❑ )2* AIR TEMPERATURE 86 CONCRETE TEMPERATURE 83 DATE RECEIVED 04/14/98 FIELD DATA SUBMITTED BY F. M. MIX DATA SUBMITTED BY RED I - M I X SPECIMENS CAPPED IN ACCORDANCE WITH ASTM C -617 ❑ OR C -1231 ❑ MIX PROPORTIONS (SSD) N/A CEMENT N/A WATER N/A FINE AGGREGATE N/A COARSE AGGREGATE N/A ADMIXTURE N/A COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6" X 12 ") (ASTM C -39) LAB TYPE DATE AGE TOTAL AREA COMPRESSIVE NO. CURING TESTED DAYS LOAD STRENGTH, PSI 137 LAB 04/20/98 7 88,319 28.27 3,120 138 LAB 05/11/98 28 111,929 28.27 3,960 139 LAB 05/11/98 28 99,545 28.27 3,520 140 LAB HOLD H 28.27 Specifications 28 3, 000 * CONTRACTOR INFORMED OF LOW AIR CONTENT AND HIGH SLUMP COMPU DATA- CGO10e3 -34 REMARKS ❑ Cylinders made by ALPHA representative. ❑ Cylinders made by Architect's or Contractor's representative. ❑ Cylinders picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. ❑ Compression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. ❑ Respectfully Submitted / l ` ALPHA TESTING, INC. (.- PAT STETTNER 5 PLANT 5 52724 DELIVER TICKET NO 5 COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6" X 12 ") (ASTM C -39) LAB TYPE DATE AGE TOTAL AREA COMPRESSIVE NO. CURING TESTED DAYS LOAD STRENGTH, PSI 137 LAB 04/20/98 7 88,319 28.27 3,120 138 LAB 05/11/98 28 111,929 28.27 3,960 139 LAB 05/11/98 28 99,545 28.27 3,520 140 LAB HOLD H 28.27 Specifications 28 3, 000 * CONTRACTOR INFORMED OF LOW AIR CONTENT AND HIGH SLUMP COMPU DATA- CGO10e3 -34 REMARKS ❑ Cylinders made by ALPHA representative. ❑ Cylinders made by Architect's or Contractor's representative. ❑ Cylinders picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. ❑ Compression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. ❑ Respectfully Submitted / l ` ALPHA TESTING, INC. (.- PAT STETTNER * CONTRACTOR INFORMED OF LOW AIR CONTENT AND HIGH SLUMP COMPU DATA- CGO10e3 -34 REMARKS ❑ Cylinders made by ALPHA representative. ❑ Cylinders made by Architect's or Contractor's representative. ❑ Cylinders picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. ❑ Compression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. ❑ Respectfully Submitted / l ` ALPHA TESTING, INC. (.- PAT STETTNER ALPHA TESTING, INC. 2209 Wisconsin St. / Suite 100 Dallas, Texas 75229 (214) 620 -8911 TESTED FOR: FIRST WORTHING COMPANY DALLAS, TEXAS PROJECT: STONELEIGH AT RIVERCHASE COPPELL, TEXAS REPORT OF CONCRETE COMPRESSION TEST DATE OF ISSUE: APRIL 13, 1998 OUR REPORT NO.: 97060-121 FIELD DATA PAVING: 35' SOUTH & 15' WEST OF SE CORNER OF LOCATION OF CONCRETE PLACEMENT BUILDING 3 04/13/98 PLANT 5 DATE PLACED 13 : 4 0 DELIVER TICKET NO 52744 TIME SLUMP (ASTM C -143) 6.5* MIX PROPORTIONS (SSD) N/A AIR CONTENT (ASTM C -231 ❑ OR C -173 ❑ )4 CEMENT N/A AIR TEMPERATURE 90 WATER N/A CONCRETE TEMPERATURE 85 FINE AGGREGATE N/A DATE RECEIVED 04/14/98 COARSE AGGREGATE N/A FIELD DATA SUBMITTED BY F M ADMIXTURE N/A MIX DATA SUBMITTED BY RED I - M I X 101,007 28.27 SPECIMENS CAPPED IN ACCORDANCE WITH ASTM C -617 ❑ OR C -1231 ❑ 144 LAB COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6" X 12 ") (ASTM 0-39) LAB NO. TYPE CURING DATE TESTED AGE DAYS TOTAL LOAD AREA COMPRESSIVE STRENGTH, PSI 141 LAB 04/20/98 7 87,032 28.27 3,080 142 LAB 05/11/98 28 95,589 28.27 3,380 143 LAB 05/11/98 28 101,007 28.27 3,570 144 LAB HOLD H 28.27 Specifications 28 * CONTRACTOR INFORMED OF HIGH SLUMP COM PU DATA- CGO1083 -34 REMARKS [;�` made by ALPHA representative. ❑ Cylinders made by Architect's or Contractor's representative. 2r'-Cylinders picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. ompression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. El Respectfully Submitted HAT S G NC. T S TTNER A / //, ALPHA TESTING, INC. 2209 Wisconsin St., Suite 100 Dallas, Texas 75229 (972) 620 -8911 TESTED FOR FIRST WORTHING COMPANY DALLAS, TEXAS PROJECT STONELEIGH • RIVERCHASE COPPELL, TEXAS TEST DATA: REPORT OF FIELD COMPACTION TESTS DATE APRIL 13, 1998 OUR REPORT NO. 97060 -122 NO T DATE ELEV. DEPTH NUMBER OPTIMUM MOISTURE MAXIMUM LAB DRY DENSITY IN PLACE MOISTURE IN PLACE DRY DDEENSITY SON COMMENT' CLUB HOUSE: 45' N & 15' E OF NE CORNER OF BUILDING 19 264 RIGHT OF WAY: 40' N & 20' W OF NE CORNER 262 04/13/98 FG 6 9.2 115.9 12.3 111 96 1 —A 263 04/13/98 FG 6 9.2 115.9 11.5 110 95 1 —A 264 04/13/98 FG 6 9.2 115.9 11.4 111 96 1 —A 265 04/13/98 FG 6 9.2 115.9 10.5 112 97 1 —A TEST LOCATION: A'pwDnAC:H ANTI RTr.WT n1r WAY LANE (FLEX BASE) 262 MAIN APPROACH TO CLUB HOUSE: 15' N & 85' W OF NW CORNER OF BUILDI 3 263 MAIN APPROACH TO CLUB HOUSE: 45' N & 15' E OF NE CORNER OF BUILDING 19 264 RIGHT OF WAY: 40' N & 20' W OF NE CORNER OF BUILDING 19 265 RIGHT OF WAY: 40' N & 70' W OF NE CORNER OF BUILDING 19 Z 1 6E E FNC.. 1. FILL A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADE B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS ub 3. LIME STABILIZED C. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS 4. CEMENT TREATED D. RETEST TING CG01083 -18