Stoneleigh P1-LR 980402A ALPHA TESTING, INC. 2209 Wisconsin St. Suite 100 DaW, Texas 75229 (214) 620 -8911 TESTED FOR: FIRST WORTHING COMPANY DALLAS, TEXAS STONELEIGH AT RIVERCHASE PROJECT. COPPELL, TEXAS REPORT OF CONCRETE COMPRESSION TEST DATE OF ISSUE: OUR REPORT NO.: APRIL 2, 1998 97060 -109 RELD DATA PAVING: 45' SOUTH & 40' EAST OF SE CORNER OF LOCATION OF CONCRETE PLACEMENT BUILDING 17 COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6- X 12 ") (ASTM C-39) LAB NO. 04/02/98 DATE TESTED 5 DATE PLACED 07:45 PLANT 52242 TIME 5 DELIVER TICKET NO N/A SLUMP (ASTM 0.143) 5 ❑) MIX PROPORTIONS (SSD) CEMENT N/A AIR CONTENT (ASTM C -231 ❑ OR C -173 67 149,984 N/A AIR TEMPERATURE 70 WATER N/A CONCRETE TEMPERATURE 04/03/98 FINE AGGREGATE N/A DATE RECEIVED LAB COARSE AGGREGATE H FIELD DATA SUBMITTED BY F. M. ADMIXTURE N/A MIX DATA SUBMITTED BY RED I - M I X SPECIMENS CAPPED IN ACCORDANCE WITH ASTM C-617 ❑ OR C -1231 ❑ COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6- X 12 ") (ASTM C-39) LAB NO. TYPE CURING DATE TESTED AGE DAYS TOTAL LOAD AREA COMPRESSIVE STRENGTH, PSI 97 LAB 04/09/98 7 81,716 28.27 2,890 98 LAB 04/30/98 28 149,984 28.27 5,300 99 LAB 04/30/98 28 148,780 28.27 5,260 100 LAB HOLD H 28.27 Specifications 28 3,000 REMARKS IXCylinders made by ALPHA representative. ❑ Cylinders made by Architect's or Contractor's representative. L<CylInd, s picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. C- Compression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. In-1 ad AT STETTNER ALPHA TESTING, INC. 2208 Wisconsin St. Suite 100 Dabs, Texas 75229 (214) 620 -8911 FIRST WORTHING COMPANY TESTED FOR: DALLAS TEXAS STONELEIGH AT RIVERCHASE PROJECT: COPPELL, TEXAS REPORT OF CONCRETE COMPRESSION TEST DATE OF ISSUE: OUR REPORT NO.: APRIL 2, 1998 97060 -108 FIELD DATA PAVING: 45' SOUTH & 10' WEST OF SE CORNER OF LOCATION OF CONCRETE PLACEMENT BUILDING 17 DATE TESTED AGE DAYS 04/02/98 AREA DATE PLACED 06: 5 5 PLANT TIK 5 DELIVER TICKET NO SLUMP (ASTM C-143) 2,940 MIX PROPORTIONS (SSD) AIR CONTENT (ASTM C -231 ❑ OR C -173 ❑ ) 65 CEMENT AIR TEMPERATURE 28.27 WATER CONCRETE TEMPERATURE LAB FINE AGGREGATE DATE RECEIVED 04/03/98 COARSE AGGREGATE FIELD DATA SUBMITTED BY F • M • ADMIXTURE MIX DATA SUBMITTED BY RED I - M I X SPECIMENS CAPPED IN ACCORDANCE WITH ASTM C-617 ❑ OR C -1231 ❑ COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6" X 12'7 (ASTM G39) LAB NO. TYPE CURING DATE TESTED AGE DAYS TOTAL LOAD AREA COMPRESSIVE STRENGTH, PSI 93 LAB 04/09/98 7 83,111 28.27 2,940 94 LAB 04/30/98 28 138,718 28.27 4,910 95 LAB 04/30/98 28 156,950 28.27 5,550 96 LAB HOLD H 28.27 Specifications 28 370:0 0 5 52236 N/A N/A N/A N/A N/A N/A �� REMARKS 4 Cylinders made by ALPHA representative. ❑ Cylinders made by Archftect's or Contractor's representative. lindens picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. Ems i mpression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. Respecttu S miffed G, INC. PAT STETTNER A ALPHA TESTING, INC. 2209 Wisconsin St. suite 100 Dallas, Tom 75229 (214) 620 -8911 FIRST WORTHING COMPANY TESTED FOR: DAL TEXAS STONELEIGH AT RIVERCHASE PROJECT: COPPELL, TEXAS REPORT OF CONCRETE COMPRESSION TEST DATE OF ISSUE: OUR REPORT NO.: APRIL 2, 1998 97060 -107 FIELD DATA PAVING: 60' WEST & 25' SOUTH OF SW CORNER OF LOCATION OF CONCRETE PLACEMENT BUILDING 17 04/02/98 TYPE CURING 5 DATE PLACED 05: 05 PS 52226 TIME 5 DELIVER TICKET NO N/A SLUMP (ASTM C-143) 4 MIX PROPORTIONS (SSD) N/A AIR CONTENT (W M C -231 ❑ OR C -173 ❑ ) 56 CEMENT N/A AIR TEMPERATURE 6 0 WATER N/A CONCRETE TEMPERATURE 04/03/98 FINE AGGREGATE N/A DATE RECEIVED COARSE AGGREGATE N/A FIELD DATA SUBMITTED BY F • M • ADMIXTURE 28.27 MIX DATA SUBMITTED BY RED I — M I X 92 LAB SPECIMENS CAPPED IN ACCORDANCE WITH ASTM C -617 ❑ OR C -1231 ❑ H COMPRESSION TEST RESULTS (NOMINAL CYLINDER SIZE 6" X 12') (ASTM C -39) LAB NO. TYPE CURING DATE TESTED AGE DAYS TOTAL LOAD AREA COMPRESSIVE STRENGTH, PSI 89 LAB 04/09/98 7 88,598 28.27 3,130 90 LAB 04/30/98 28 147,060 28.27 5,200 91 LAB 04/30/98 28 139,191 28.27 4,920 92 LAB HOLD H 28.27 Specifications 28 1 3, 0 0 0 REMARKS IX<inders made by ALPHA representative. ❑ Cylinders made by Archliect's or Contractor's representative. lS a Cylinders picked up by ALPHA laboratory. ❑ Cylinders delivered to ALPHA laboratory. C?L�mpression test results comply with applicable specifications. ❑ Compression test results do not comply with applicable specifications. El bmitted ALPHA NG, INC. PAT STETTNER AV f rU C-7 110U : Z ALPHA TESTING, INC. Daily Field Report 2209 Wisconsin, Suite 100 Dallas, Texas 75228 TESTED FOI��t orb r ..�� ,i},,� –_ _ =D�� ___ _ Z _ / � ____ I e l PROJECT NAME 'RPT'* Q' Q WEATHER f TEIII[P::. "` ' • !b': * TECHNICIAN � THE ALPHA TECHNICIAN . F OAf� FENCED PROJECT AS REQUESTED TO MONITOR TYPE ON -GOING WORK AND PERFORM FIELD TE$TMIO REQUESTED. S.G. SUBGRADE FOR WAS OBSERVED TO VERIFY; t j s] -HAD BEEN PREPARED IN GENERAL ACCORDANCE WITH [Geotechnicai fr000lif . ,,, • t's MIy standards]. '.,..ia� !1 'CIO.. f. MA WHIILE ON SITE TH1= r s SOIL : SAMPLE(S) FOR LABORATORY PICK�I/P j S) [was] [were] OBTAINED FROM THE FOLLOWING LOCATION(S): F D T A TOTAL OF _ FIF [ stabilized soils] �� . [am attached rsport [site representative was complete] (J [ws;] (wel PERFORMED ON [fill] [select fill] [natural sg] cf AREA(S). , o! #pinpsCtion testing] Ils, . r�rted.xh`att %,results would be available as soon as laboratory testing was GRADATION WHILE ON SITE THE TECHNICiAN.PERFORMED FIELD GRADATION(S) TEST(S) ON THE [Lime stabilized] [cement if ko MATERIALS. SEE ATTACHED REPORT FO m' R TEST RESULTS PRE -POUR THE TECHNICIAN OBSERVED THE PRE -POUR CONDITION OF THE TECHNICIAN OBSERVED THEAW*s) FOR PROPER [vapor barrier] [Grade beam size] [steel reinforcing] AND [post tension cable layout]: [No deficiencies were noted during the observation] [The following exceptions were noted]: CONCRETE HE TECHNICIAN MOLDED I SET {S) OF / jtest cylinde [fiex�boaass] � [pees Meal M concrete] [nw"' IVP"t] PLACED FOR ,� ON THIS DATE. LAB TEST LABORATORY TEST RESU TS FOR ALL RELATED ITEMS REFERENCED ABOVE WILL FOLLOW ON A SEPERATE REPORT. WHO 4ta��NFORMED AS INFORMED OF ALL OBSERVATIONS AND FIELD TEST RESULTS. CANCEL THAT NO TESTING WOULD BE REQUIRED FOF AS TYPE AT THE COMPLETION OF THE SCHEDULED TESTING THE TECHNICIAN RETURNED TO THE DALLAS OFFICE. (972) 620-011 L'�L'J.L�' LLVJCLV r tVt yr r. �t,4w a a: 1 V rtb�tr 9��i:o D Of Aweximt C iwa Name ` .esr G 3 , � j: t ,.� G � / + � fs (�/ R / - e� W M Lab /� / t Name ✓ LgAt [ 6W Ar- k .J� ��w.S�CW ' &cw ` $W&er 1 /l X L.O i!C .--4 / . N Technician Name �'�' SS'oCj�cation.� Slump �"�` Air Set # Concrete uppTier Ticket # Tune T' Dispkk d BUM Lyle. Alolded Time Truck Unloaded Yds. O.f' Cone Unit r-4 P Nt STUMP (ft N ir 916 _52-Z,2.6 Q �O Z as OSoS ��� ��'� .S 3 SZZ�z • ���o p��.s O��s 2SQ ' �, �� Noted of any mem out of SpecUkadmv Tune Item (s) Signature of Person Not#ied X - Set # Air Temp. Conc. Temp. Req'd Strength Cy4 olded placement Location of Test Sample �O 3 1 a Alt ;hoc of S _�'� •.�`•- - - ------------------------------- -------- -- ----------------------------------------- mix cOtiTRO4 3 .5 5 3 4 3 L J i + Arrivti, lob 5 Leave Plant DISPATCH Start Pour Finish Pour. Leave Job Site Arrive Plant DENTON DALLAS FORT WORTH GAINESVILLE (940) 566 -1100 (972) 316 -0273 (817) 485 -4850 (940) 665 -2958 ADDITIONAL WATER ADDED TO THIS CONCRETE WILL REOUCF.,ITS ST AM ADDER IN EXCESS OF SPECIFIED SLUMP IS AT-.CU 7QMER'6tWK. l`�` —� W Slump Test YES NO Drivers are prohibited from delivering corhsr e e `Orid;�r tf9dk�s b power, Arid where site conditionyl if Cylinders Taken YES NO Permit the safe and proper operation of his equipment. DriVgCy� a(e nermittp eo beyond the curb line, except upon the authorization of the customer and his acceptan o \ flrlsk for arly� s \ � 1 bc , Adamage to the property Air Test YES, , NO or our equipment. This includes any wrecker or towing charges for getting out of the location. i" Water Added at Customer's Request ' gaIlons n v RECEIPT AND RELEASE PLAW "; TRUCK NO. LOAD SIZE SLUMP DRIVER NAME SALESMAN .. 1.76 10. fah! fl?w 1C41>±E.l t i't "3tei:d r +� CUSTOMER NO. PROD. NO. SOLD TO P.O. If JOB M DATE .4. 31G: TR`:T sr(:it ?Tfi. "t�f, t`Ohlk'RHY 11..c2 -B t7� 2-Apr-98 DELIVERY ADDRESS ZONE N MAPSCO M f 1:21 1; I vRkchp..:"E, i. OPf El. i 2B - i r SPECIAL DELIVERY INSTRUCTIONS '.1'i3f�,LI::�GH ,� EyF:Ctc >iiASE °,:'�!'�;' °• l:: +f,? f•EII'i ,t:rC! jl;rlt4 kiTtr`L.ttt.YlA : aE tii3 ui - -:5 5 TO 6ELT1JNE TO MACARTHUR. F' ,' rU ClI`JtuRC"1=iAGE Ft /IIF ITE'k AT saw AMOUNT f l gib. 431r't .1 Gl>tl. fail) 2 50. 00 ?" 2:3 I)AGK - A i R C'y 2 WARNING — IRRITATION TO THE SKIN AND EYES SUB TOTAL Cement polymer or freshly mixed concrete, grout or mortar may cause skin injury. Avoid contact with skin and wash exposed skin areas TAX promptly with water. If any cement powder or mixture gets into eyes, rinse Immediately and repeatedly with water and get prompt medical g!�••� y n Keep children away from cement powder and all freshly mixed cement products. TOTAL ; `1f IX CONTROL 3 5 5 3 5 3 ri L Arrive Job Site J Legve Plant oce 1 LGA M :11 _ . DISPATCH Start Pour Finish Pour Leave Job Site Arrive Plant DENTON DALLAS FORT WORTH GAINESVILLE 1 (} (940) 56&1100 (972) 3180273 (817) 4854850 (940) 885 -2858 7 j . ADDITIONAL WATER ADDED TO THIS CONCRETE WILL ,REDUCE ITS STRENGTF,!.,4NY,, Wy TER ADDED IN 'EXCESS OF ' SPECIFIED SLUMP I$_�1T"G ` ��j Slump Test YES NO Drivers are prohibited from delivering.�pon tceep��er th 'tluck'�n r, and where site conditions permit the safe and proper operation dF eyond the curb line, eq pment. ers ar t ttte�d.tZ" Cylinders Taken YES [0__ 'a t�1� \ , \� except upon the authorization of the customer and his accenc� o f or damage to the property Air Test YES hLL2.- ' 1. or our equipment. This includes an wrecker or towing char f r ett' ut of theloca4in. Water Added at HN Customer's Request gallons RECEIPT AND RELEASE X v 5+ TRUCK NO. LOAD SIZE SLUMP DRIVI� NAME SALESMAN 175 10.la .0" CRAIG EUDD CUSTOMER NO. PROD. NO. I SOLD TO P.O. N JOB M DATE 2368 FIRST WORTHING COMPANY 118 -B 02- Afar -g8 DELIVERY ADDRESS ZONE M MAPSCO N 1315 RIVERCHASE / COPPEL 11B -B SPECIAL DELIVERY INSTRUCTIONS STOHELEIGH 8 RIVERCHASE / \ /\ / \ / \DO NOT GO DOWN RIVERCHASE GO I -35 TO BELTLIHE /TO KACARTHUR R / TO RIVERCHASE R / /ENTER AT Y 10.00 200.00 250.00 723 5SACK -AIR CY 3 i i WARNING — IRRITATION TO THE SKIN AND EYES SUB TOTAL Cement polymer or freshly mixed concrete, grout or mortar may cause skin injury. Avoid contact with skin and wash exposed skin areas TAX promptly with water. If any cement powder or mixture gets into eyes, rinse immediately and repeatedly with water and get prompt _ medical attention. Keep children away from cement powder and all freshly mixed cement products. TOTAL K � MIX CONTROL 3 5 5 3 5 9 • Arrive Job Site Leave Plant DISPATCH Start Pour Finish Pouf Leave Job Site Arrive Plant DENTON DALLAS I FORT WORTH GAINESVILLE - 2 f (940) 566 -1100 (972) 316-0273 (817) 485 -4850 (940) 885 -2858 / - / 7 /Sy IN fA ir ONAL WATER ADDED TO THIS CONCRETE WILL REDUCE ITS STRENGTH.,ANY WATER ADDED IN EXCESS OF SPECIFIED SLUMP IS AT CUSTOMER'S RI u st VEES 1�0 Drivers are prohibited from delivering concrete except under the truck'I: own power, and where site conditionski0i Taken NO pe rmit the safe and proper operation of his equipment. Drivers are not permitted to beyond the curb line, except upon the authorization of the customer and his acceptance of risk for any loss or damage to the property NO or our equipment. This includes any wrecker or towing ctlarges for getting out of the location. dd d t � r SPECIAL DELIVERY INSTRUCTIONS v; STONELEIGH 0 R /\ /t /\ /ADO NOT -GO DOWN RIVERCNASE GO I -35 TO BELTLINE /TO MACARTHUR R / TO RIVERCHASE R / /ENTER AT 10.00 250.00 250.00 723 5SACK -AIR CY m z S� W < WARNING — IRRITATION TO THE SKIN AND EYES SUB TOTAL Cement polymer or freshly mixed concrete, grout or mortar may cause skin injury. Avoid contact with skin and wash exposed skin areas TAX promptly with water. If any cement powder or mixture gets Into eyes, rinse immediately and repeatedly with water and get prompt medical attention. Keep children away from cement powder and all freshly mixed cement products. 'TOTAL H Customer's Request gallons F RECEIPT AND RELEASE f fF�AMT ,e TRUCK NO. LOADSIZE SLUMP DRIVER NAME SALESMAN 00 I 0" IROBERT STAHR� . N CUSTOMER NO. PROJ. NO. SOLD TO P.O. N JOB M DATE 2368 IRST WORTHING COMPANY 11B -8 02- Apr -98. ,P 0 DELIVERY ADDRESS ZONE M I MAPSCO N -B 1315 RIVERCNASE / COPPEL 11B � r SPECIAL DELIVERY INSTRUCTIONS v; STONELEIGH 0 R /\ /t /\ /ADO NOT -GO DOWN RIVERCNASE GO I -35 TO BELTLINE /TO MACARTHUR R / TO RIVERCHASE R / /ENTER AT 10.00 250.00 250.00 723 5SACK -AIR CY m z S� W < WARNING — IRRITATION TO THE SKIN AND EYES SUB TOTAL Cement polymer or freshly mixed concrete, grout or mortar may cause skin injury. Avoid contact with skin and wash exposed skin areas TAX promptly with water. If any cement powder or mixture gets Into eyes, rinse immediately and repeatedly with water and get prompt medical attention. Keep children away from cement powder and all freshly mixed cement products. 'TOTAL H