Loading...
Gateway BP(1.4)-LR070105CONCRETE COMPRESSIVE STRENGTH TEST 'Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 3:09am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 947 Ticket No: 7373839 Mix I.D. No.: 1261 Water Added Onsite Before Test: 10 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, oF: Ambient Temperature, oF: Plastic Unit Weight, pcf: Result 5.00 5.0 55 42 Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 Specification Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 Date Tested 12/13/2006 01/03/2007 01/03/2007 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 lierracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Sample Information Date Cast: December 6, 2006 Sampled by: Jesus Rojas Weather Conditions: Clear Accumulative Yards: 80/700 Placement Method: Pump Sample Locations: Set #1, see attached sketch Placement Location: Pavement, see attached sketch Time: 3:45am Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 118,290 4,180 28 149,700 5,290 28 155,930 5,510 Average (28 Days) 5,400 Comments: Not tested for plastic unit weight. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 7 01- SKS/R01- Future Key CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 4:11 am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 959 Ticket No: 7173847 Mix I.D. No.: 1261 Water Added Onsite Before Test: 0 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, oF: Ambient Temperature, oF: Plastic Unit Weight, pcf: Result 6.00 6.0 55 48 Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 2 1 6.00 28.27 2 2 6.00 28.27 2 3 6.00 28.27 Specification Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Sample Information Date Cast: December 6, 2006 Time: 4:45am Sampled by: Jesus Rojas Weather Conditions: Clear Accumulative Yards: 160/700 Placement Method: Pump Sample Locations: Set #2, see attached sketch Placement Location: Pavement, see attached sketch Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 12/13/2006 7 75,190 2,660 01/03/2007 28 103,680 3,670 01/03/2007 28 106,910 3,780 Average (28 Days) 3,730 Comments: Not tested for plastic unit weight. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 7 01- SKS/R01- FVlure Key CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 6:01 am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 7059 Ticket No: 629556 Mix I.D. No.: 1261 Water Added Onsite Before Test: OGallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, °F: Ambient Temperature, °F: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 3 1 3 2 3 3 Result 6.00 8.0 53 43 Diameter Area (inches) (sq. inches) 6.00 28.27 6.00 28.27 6.00 28.27 Specification Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 lierracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Sample Information Date Cast: December 6, 2006 Sampled by: Jesus Rojas Weather Conditions: Clear Accumulative Yards: 300/700 Placement Method: Pump Sample Locations: Set #3, see attached sketch Placement Location: Pavement, see attached sketch Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Time: 6:30am Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 12/13/2006 7 57,570 2,040 01/03/2007 28 87,560 3,100 01/03/2007 28 89,760 3,170 Average (28 Days) 3,140 Comments: Not tested for plastic unit weight. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 7 01.SKSM01- Fulure Kay CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 6:48am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 7070 Ticket No: 6295570 Mix I.D. No.: 1261 Water Added Onsite Before Test: OGallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, oF: Ambient Temperature, oF: Plastic Unit Weight, pcf: Result 6.50 6.0 53 43 Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 4 1 6.00 28.27 4 2 6.00 28.27 4 3 6.00 28.27 Specification Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 Sample Information December 6, 2006 Jesus Rojas Date Cast: Sampled by: Weather Conditions: Clear, sunny Accumulative Yards: 370/700 Placement Method: Pump Sample Locations: Set #4, see attached sketch Placement Location: Pavement, see attached sketch Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Comments: Does not comply with specified strength. Not tested for plastic unit weight. lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Time: 7:30am Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 12/13/2006 7 50,690 1,790 01/03/2007 28 74,950 2,650* 01/03/2007 28 80,080 2,830* Average (28 Days) 2,740 NOTE: The strength should be considered satisfactory because it meets ACI- 318 5.6.3.3 (see attached Statistical Analysis of Concrete Mixtures Report, dated 01/05/07. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 7 01- 51C5IRO, -FVMxe Key CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 7:29am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 7024 Ticket No: 7173866 Mix I.D. No.: 1261 Water Added Onsite Before Test: 0 Gallons Water Added Onsite After Test: 10 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, 0F: Ambient Temperature, OF: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 5 1 5 2 5 3 6.00 6.00 6.00 Result 5.50 5.9 57 50 Diameter Area (inches) (sq. inches) 28.27 28.27 28.27 Specification Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 lierracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Sample Information Date Cast: December 6, 2006 Sampled by: Jesus Rojas Weather Conditions: Clear, sunny Accumulative Yards: 490/700 Placement Method: Pump Sample Locations: Set #5, see attached sketch Placement Location: Pavement, see attached sketch Comments: Not tested for plastic unit weight. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 7 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Time: 8:OOam Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 12/13/2006 7 88,030 3,110 01/03/2007 28 125,870 4,450 01/03/2007 28 123,650 4,370 Average (28 Days) 4,410 01- SK$IR01 -FVM, Key CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 8:33am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 7059 Ticket No: 7173877 Mix I.D. No.: 1261 Water Added Onsite Before Test: OGallons Water Added Onsite After Test: 10 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, OF: Ambient Temperature, OF: Plastic Unit Weight, pcf: Result 5.50 5.5 58 55 Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 6 1 6.00 28.27 6 2 6.00 28.27 6 3 6.00 28.27 Specification Page 6 of 7 Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 lierracon 8901 Carpenter Fry, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Sample Information Date Cast: December 6, 2006 Sampled by: Jesus Rojas Weather Conditions: Clear, sunny Accumulative Yards: 580/700 Placement Method: Pump Sample Locations: Set #6, see attached sektch Placement Location: Pavement, see attached sketch Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Time: 9:OOam Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 12/13/2006 7 89,570 3,170 01/03/2007 28 112,080 3,960 01/03/2007 28 125,450 4,440 Average (28 Days) 4,200 Comments: Not tested for plastic unit weight. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. at- SKSIROt.iuture Ksy CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061357.0014 Service Date: December 6, 2006 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Material Information Specified Strength: 3000 psi 28 Days Batch Time: 9 :06am Plant: 7 Supplier: Lattimore Materials Co. Truck No: 7021 Ticket No: 7173882 Mix I.D. No.: 1261 Water Added Onsite Before Test: 10 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, Concrete Temperature, OF: Ambient Temperature, OF: Plastic Unit Weight, pcf: Laboratory Test Data Set Specimen No. ID 7 1 7 2 7 3 Report Distribution: (1) Hill Wilkinson LTD (1) Halff Assoc Inc (1) City of Coppell TX (1) Haverty Furniture Co Inc Diameter Area (inches) (sq. inches) 6.00 6.00 6.00 Terracon Rep: Jesus Rojas Result 6.50 5.5 58 55 28.27 28.27 28.27 Specification Report Date: January 05, 2007 Project: Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX Project No.: 94061357 lierracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Sample Information Date Cast: December 6, 2006 Sampled by: Jesus Rojas Weather Conditions: Clear, sunny Accumulative Yards: 650/700 Placement Method: Pump Sample Locations: Set #7, see attached sketch Placement Location: Pavement, see attached sketch Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 12/13/2006 7 60,790 2,150 01/03/2007 28 100,350 3,550 01/03/2007 28 97,840 3,460 Average (28 Days) 3,510 Comments: Not tested for plastic unit weight. Services Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Reviewed by: Time: 10:10am Hussein H. Abusaad, P.E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 7 of 7 01- SKSIR01 -FUMe Key c•••• Terracon Report No. 94061357.0014 Dated 12/06/2006 (Haverty Pavement Expansion) BETWEEN EXISTING JO|N| YY PAVEMENT AND NEW PAVEMENT. SAWCUT 874 LF REMOVE C CONNECT TO EXIST. CONCRETI u� o mmwRACON REPORT NO. INSTALL 372 OF 6" CURB STATISTICAL ANALYSIS OF CONCRETE MIXTURES Report Number: 94061357.0025 Service Date: January 5, 2007 Client: Hill Wilkinson LTD Attn: Gene Fort 800 Klein Rd Ste 100 Plano TX 75074 Specification Requirements: Concrete Class: 1261 Date 12/06/2006 12/06/2006 12/06/2006 12/06/2006 12/06/2006 12/06/2006 12/06/2006 12/07/2006 12/07/2006 12/07/2006 12/07/2006 12/07/2006 12/07/2006 Average Report Number 94061357.0014 94061357.0014 94061357.0014 94061357.0014 94061357.0014 94061357.0014 94061357.0014 94061357.0017 94061357.0017 94061357.0017 94061357.0017 94061357.0017 94061357.0017 3000 psi 28 Days Set 1 2 3 4 5 6 7 2 3 4 5 6 7 Report Date: Project: Project No.: PROJECT DATA REPORT OF TESTS Number Of Samples 2 2 2 2 2 2 2 2 2 2 2 2 2 Slump (in.) 5.00 6.00 6.00 6.50 5.50 5.50 6.50 5.25 5.00 5.50 5.50 5.50 5.00 Page 1 of 2 January 05, 2007 Haverty Pavement Expansion 770 Gateway Blvd. PO #14 -2155 Coppell, TX 94061357 Air Content 5.0 6.0 8.0 6.0 5.9 5.5 5.5 7.0 6.0 5.8 5.6 5.7 5.6 Concrete Temp (F) 55 55 53 53 57 58 58 55 55 53 55 54 53 lierracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Compressive Strength PSI 5400 3725 3135 2740 4410 4200 3505 3480 5300 4410 5490 5025 4795 of all sets of three consecutive strengths equals or exceeds the project specifications. Average of 13 sets 4280 PSI 28 days The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Running 3 Test Avg PSI 4087 3200 3428 3783 4038 3728 4095 4397 5067 4975 5103 11J61AR11 -FUWre Key STATISTICAL ANALYSIS OF CONCRETE MIXTURES Client: Hill Wilkinson LTD Terracon Rep: Hussein H. Abusaad, P.E. Report Distribution: (1) Hill Wilkinson LTD Page 2 of 2 lierracon Project Number:94061357 Report Number: 94061357.0025 (1) Halff Assoc Inc Reviewed by: (1) City of Coppell TX (1) Haverty Furniture Co Inc Hussein H. Abusaad, P.E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. 1 1-HW VRt t-F Wie Key