Valley R Plaza A-CS 970326MAR -27 -1997 07:16
r�
March 26, 1997
TEXAS INDUSTRIES, INC.
TEXAS INDUSTRIES
1341 W MOCKINGBIRD LAND • DALLAS, TEXAS 76247 • 97PI542'6700
Stovall Construction
P.Q. Box 1185
Kennedale, TX 76060
Attn: Project Superintendent
RE: McDonald's - City of Coppell
8274
P.01
The attached concrete mix design utilizing the appropriate ASTM
C -33 or ASTM C -330 aggregate is proposed for use on the above
referenced project for ready -mixed concrete to be furnished by
TXI.
To ensure that the correct mix is delivered to your project,
please order by the mix design number which appears in the upper
left hand corner of the mix design.
Texas Industries certifies that the above mix design, when
ordered by specified design identity, and delivered by TXI, will
meet or exceed the indicated design strength at the designated
age when tested in accordance with the applicable and current
ASTM Standards C 31, C 39, C 78, C 172, C 293, applicable
provisions of C 94, and evaluated in accordance with applicable
provisions of the ACI 318 Building Code.
TXI would like to be included on your mailing list to receive all
test reports. ASTM C 94 entitles a manufacturer to receive
copies of all test reports when strength of concrete is used as a
basis for acceptance.
Contact us if you have any questions or require any additional
information. Please notify TXI of approval of the proposed mix
design prior to its use. Failure to notify us prier to first
placement shall constitute acceptance. To ensure that the proper
mix design is ordered, please send a copy of this letter, after
approval, to the above referenced project to be used by the
person ordering the concrete for this job.
Sincerely,
Texas Industries
&ZZL &44
Bruce Bach
Customer Service
Representative
MAR -27 -1997 07:17 TEXAS INDUSTRIES, INC.
Mix #: 8274
Description: 6.00SK ADMIX /AEA 1 "CS
Strength: 4000 psi m 28 Days
HAND PLACED PAVING
Maximum Coarse Aggregate:
Maximum Water /Cement Ratio:
Cement /Cementitious Content:
Maximum placement Slump:
Air Entraining Agent:
Admixture:
1" - #4 CRUSHED STONE
5.17 gal /sack or 0.457 lbs /lb
6.00 sacks (per cubic yard)
4.00 inches
ASTM C -260
ASTM C -494 Type A or D
MATERIAL QUANTITIES PER 1.0 CUBIC YARD AT S.S.D
564 lbs. ASTM C 150 TYPE I CEMENT
1840 lbs. 1" - #4 CRUSHED STONE
1273 lbs. CONCRETE SAND
258 lbs. or 31.0 Gallons of Water
2.0 to 4.0 oz /cwt of ASTM C -494 Type A
Specified Air Content: 3.0k - 6.0t
Placement Slump: 3.00 + or - 1.00 inches
P.02
MAR -27 -1997 07:17 TEXAS INDUSTRIES, INC. P.03
PUMPING RECOMMENDATIONS
1. 5" minimum diameter lines with no reduction to smaller
lines.
2. Keep rubber hose to absolute minimum length and plan pipe
with as few 90 degree angles as possible.
3. Samples for slump and strength tests should be taken 0
discharge and of hose for strength guarantee to be valid.
4. To prime pump lines, a minimum of 8.0 sack grout should be
used for lubrication. In the case of strength concrete,
equivalent strength grout should be used if the grout
remains in the placement.
5. Pump mixes are based on minimum cement content pumped at
ground level. As Vump line increases in length or height
and /or layout configuration changes, additional cement may
be required to assure strength and pumpability at additional
cost to the contractor.
6. TXI cannot control, and is therefore not responsible for
excessive loss of entrained air content when loss occurs as
a result of boom configuration or free fall discharge from
hose. To ensure minimum air loss when pumping, maintain a
continuous flow of concrete through the entire length of
pipe and do not subject concrete to free fall.
we are enclosing all available back up data for the referenced
mix design(s). if the strength information is not available, or
is insufficient, confirmation tests may have to be conducted by
your laboratory.
MAR -27 -1997 07:17 TEXAS INDUSTRIES, INC. P.04
Ttus IMMTIUZB
calwraisra IDWIGH Jr4AL &TZOx
Data.
03/26/97
•+ statistica
cowiled irw Iadepeadaat I.aboratery
Teat
Speclsena
+•
Mx NUabarl
8274
Strength:
4000 psi
a 2e Day,
28 Day Test Data
Temperature
Test
Plant
(Fahrenheit)
placement
Percent
Dumber
Date
Number
Ambient Concrete
Slump(in)
of Air
---------
28 Day Y
- -• - - - --
CZemvlativc
NOving
-- -- - --- --
---------
--- - ---
PSI 1
PSI 2
PSI Avg
Average
Avg of 3
Mange
1
10/02/96
89
7.00
4.0%
5490
5450
5470
5470
2
10/03/96
85
3.25
4.7t
4410
4410
3
10/03/96
s0
5.50
N/A
5200
5180
5240
4940
4
10/04/96
5040
5040
s0
5
10/04/96
80
4.00
3.8%
4990
4770
4880
5000
4843
220
82
S.So
5.Lt
4290
4470
4380
4976
4833
180
6
10/08/96
81
5.50
N/A
4630
4760
4695
4846
7
10/10/96
84
4.00
5.4t
4450
4470
4460
4652
130
8
10111196
83
4791
4512
20
9
10/14/96
4.00
4.Ot
4680
465o
4665
4775
4607
30
43
82
5.00
4.51
4650
4600
4625
4758
1583
50
10
10/15/96
43
94
5.00
4.Ot
4140
4150
414S
4697
4478
11
10116196
82
4.50
3.9t
4220
4210
4215
4653
10
12
10/16/96
43
B8
4.75
4.Ot
4260
4170
4215
4617
4328
10
13
10/16/96
43
85
4192
90
5.25
4.2t
4000
4040
4020
4571
4150
40
14
10/17/96
44
76 64
7.00
N/A
4650
4530
4590
4572
4275
120
15
10/18/96
43
63
4.50
3.9t
4760
4100
4730
4583
4447
60
16
10/19/96
43
92
6.00
3.81
4390
4130
4260
4563
4527
260
17
10/24/96
43
69
5.75
7.Ot
4180
4320
4250
4544
4413
140
le
10/25/96
71
4-So
6.04r
4960
4e10
4685
4563
4465
150
19
10/25/96
46
69 74
5.50
N/A
4390
4280
4335
4551
4490
110
70
10/31/96
92
3.00
4.6t
5080
S230
5155
4581
4792
250
21
11104/96
43
70
4.75
5.71
4530
4550
4540
4579
4677
20
22
11/04/96
43
70
5.00
5.9%
4710
4230
4270
4563
4638
20
23
11/05196
79
4.75
6.2t
4820
4860
4840
4575
4533
40
24
11/05/96
40
78 79
5.00
N/A
4510
4750
4630
4577
4563
240
25
11/06/96
83
5.50
4.Ot
4630
4630
4630
4579
4700
0
16
11/14/96
79
3.50
4.et
4310
4130
4220
4566
4493
Igo
27
11118196
74
3.00
4.7t
5440
5280
5360
4595
4737
160
26
11/20/96
40
79
5.50
4.51
4100
4090
4095
4577
4558
10
29
11/20/96
40
79
5.00
4.34
4260
4310
4235
4565
4563
50
30
11/23/96
41
54 67
5.00
N/A
4310
4520
4665
4569
4332
290
•66 Averages •
69 80
4.72
4.7t
MAR -27 -1997 07:18 TEXAS INDUSTRIES. INC. P.05
COMMENTARY OF STATISTICAL VALUATION OF CONCRETE DE9I(#N RESULTS
Mix NUM: 8274 Strength: 4000 psi 0 20 Days
Paragraph 5.5 of ACI 318 -89 provides that as data becomes
available during construction, the amount by which (F'cr) must
exceed the specified value of (F'c) may be reduced, provided:
(a) 30 or more test results are available and average of
test results exceeds that required by Section 5.3.2.1,
using a standard deviation calculated in accordance
with Section 5.3.1.1, or
(b) 15 to 29 test results are available and average of test
results exceeds that required by Section 5.3.2.1, using
a standard deviation calculated in accordance with
Section 5.3.1.2.
The required average compressive strenVth has been calculated
using a standard deviation calculated in accordance with
ACI 318 -89 Section 5.3.1.1 or Section 5.3.1.2 and is the larger
value of these calculation$:
F' cr = F' c
4000
= 4511
F' cr = F' c
4000
= 4388
+ 1.34(SD)
+ 1.34( 381.0)
+ 2.33(SD) - 500
+ 2-33( 381.0) - 500
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests ...........•...•...
30
_
Maximum Value
...................... ...
Minimum Value
5470
p
......................
4020
p
•
Averrage.Strength
1450
psi
.....................•
.. - ••
Standard Deviation
4569
psi
Required Average Strength to satisfy
381
psi
minimum probability conditions of
ACI 318 --89 Section 5.3.2.1........ .. .
4511
psi
Design excess beyond code requirements...
58
psi
TOTAL P.05