Valley R Plaza 2-CS 98030503/05/97 10:00 BMH /ASBUILTUSA /CRIS 214 -358 -1600
A S - B U I L T U S A
March 5, 1997
Ken Griffin
Engineering Dept.
255 Parkway Blvd.
CoppelI, TX
Re: Valley Ranch Plaza
817 MacArthur Blvd.
Dear Ken,
PAGE 2 OF 6
The city requires concrete paving to be placed over lime stabilized soil. You indicated to
us that we could eliminate the lime if either the thickness is increased or the strength is
increased to 4000 P.S.I. We have elected to increase the strength of the concrete to 4000
P.S.I. and eliminate the lime stabilization. "Phis exceeds the recommendation in our soils
report. Enclosed with this letter is the concrete design mix that we plan on using and
have approved.
I f you have any further concerns, please feel free to contact us.
Sincerely,
=7 a
L
Ross Floyd
BMH Architects, Inc.
3237 W. Northwest Hwy., Ste. 101
Dallas, Texas 75220
cc: John L;vans
N.C. Inc.
0 A Rt�f►
�.p < �J►
OF
�l 3sA� r
* ARCHITECTURE * INTERIORS " SPACE PLANNING * ENVIRONMENTAL *
3237 W, Northwest Highway - Suite 101 - Dallas, "Texas 75220 - (2 ]4} 350 -1200 - fax (214) 358 -1600
03/05/97 10:00 BMH /ASBUILTUSA /CRIS 214 -358 -1600
Mix #: 8273
Description: 5.50SK ADMIX /AEA 1 11 CS
Strength: 4000 psi Q 28 Days
PAVING
Maximum Coarse Aggregate: 1 -
Maximum Water /Cement Ratio: 5.64
Cement /Cementitious Content: 5.50
Maximum Placement Slump: 4.00
Air Entraining Agent: ASTM
Admixture: ASTM
PAGE 3 OF 6
#4 CRUSHED STONE
gal /sack or 0.499 lbs /lb
sacks (per cubic yard)
inches
C -260
C -494 Type A or D
MATERIAL QUANTITIES PER 1.0 CUBIC YARD AT S.S.D
517 lbs. ASTM C 150 TYPE I CEMENT
1840 lbs. 1 - ##4 CRUSHED STONE
1312 lbs. CONCRETE SAND
258 lbs. or 31.0 Gallons of Water
2.0 to 4.0 oz /cwt of ASTM C -494 Type A
Specified Air Content: 3.Ot - 6.Ot
Placement Slump: 3.00 + or - 1.00 inches
'f
DjtLe
.fir 1�
03/05/97 10:01 BMH /ASBUILTUSA /CRIS 214 -358 -1600 PAGE 4 OF 6
PUMPING RECOMMENDATIONS
1. 5 minimum diameter lines with no reduction to smaller
lines.
2. Keep rubber hose to absolute minimum length and plan pipe
with as few 90 degree angles as possible.
3. Samples for slump and strength tests should be taken @
discharge end of hose for strength guarantee to be valid.
4. To prime pump lines, a minimum of 8.0 sack grout should be
used for lubrication. In the case of strength concrete,
equivalent strength grout should be used if the grout
remains in the placement.
5.' Pump mixes are based on minimum cement content pumped at
ground level. As pump line increases in length or height
and /or layout configuration changes, additional cement may
be required to assure strength and pumpability at additional
cost to the contractor.
6. TXI cannot control, and is therefore not responsible for
excessive loss of entrained air content when loss occurs as
a result of boom configuration or free fall discharge from
hose. To ensure minimum air loss when pumping, maintain a
continuous flow of concrete through the entire length of
pipe and do not subject concrete to free fall.
We are enclosing all available back up data for the referenced
mix design (s). If the strength information is not available, or
is insufficient, confirmation tests may have to be conducted by
your laboratory.
Cement, aggregate, and admixture certification have already been
submitted.
03/05/97 10:02 BMH /ASBUILTUSA /CRIS 214 -358 -1600 PAGE 5 OF 6
Tans n=Snals
C0NC8SPH DESIGN WJUVATION
Date: 02/14/97 •• Statistics Compiled from Independent Laboratory Test Specimens ••
Mix Bhumberc 8277 Strength: 4000 pat 0 28 Days
78 Day Test Data
Temperature
Test
Plant
(Fahrenheit)
Placement
Percent
--- - - - - --
28 Day
-- - - - - --
Cumulative
Number
Date
Number
Ambient
Concrete
Slump {in)
of Air
PSI
Moving
-
- --
--- -- --
1
-
PSI 2
PSI Avg
Average
Avg of 3
Range
1
09/10/96
18
68
80
4.00
4.54
- - -- --
4800
- -- -- --
4590
- - -----
4695
4695
2
09/10/96
18
68
81
4.50
4.24
4740
4720
4730
4713
210
3
09/17/96
18
74
64
5.50
5.24
4240
4400
4320
4582
4582
20
160
4
09/17/96
18
64
63
4.50
4 -84
5020
4700
4860
4651
4637
320
5
09/17/96
18
68
80
5.50
4.54
4480
4540
4510
4623
4563
60
6
09/17/96
18
67
80
5.50
5.04
4760
4560
4660
4629
7
09/23/96
31
73
83
4.75
4.94
4540
4340
4440
4602
4677
200
8
09/23/96
31
74
83
5.00
4.74
4537
200
4470
4360
4415
4579
4505
110
9
09/23/96
31
75
84
5.00
4.84
4400
4320
4360
4554
4405
80
10
09/23/96
31
75
84
4.75
4.84
4340
4220
4280
4527
4352
120
11
09/25/96
41
69
83
5.00
5.34
4760
4630
4695
4542
4445
130
12
09/25/96
41
71
84
5.00
5.24
4830
4580
4705
4556
4560
250
13
09/27/96
41
55
74
4.75
5.04
4670
4540
4605
4560
4668
130
14
09/27/96
41
57
73
5.00
4.94
4600
4730
4665
4567
4658
130
15
10/24/96
31
71
5.50
5.64
4040
4060
4050
4533
4440
20
16
10/24/96
31
74
5.50
5.54
4190
4060
4125
4507
4280
130
17
10/24/96
31
72
5.00
5.94
4300
4290
4295
4495
4157
10
18
10/31/96
31
64
77
4.50
3.14
4820
4910
4865
4515
4428
90
19
10/31/96
31
63
77
5.00
3.24
5080
5120
5100
4546
4753
40
20
10/31/96
18
60
75
5.00
4.34
5090
4980
5035
4571
5000
110
21
10/31/96
18
63
74
5.25
3.14
5120
5150
5135
4597
5090
30
22
10/31/96
18
62
73
4 -50
4.04
4750
4800
4775
4605
4982
50
23
10/31/96
18
61
74
6.00
3.7%
4490
4410
4450
4599
4787
80
24
10/31/96
18
62
71
4.50
4.5%
5010
5070
5040
4617
4755
60
25
11/01/96
31
73
5.00
4.6t
4670
4590
4630
4618
4707
80
26
11/12/96
18
76
73
4.75
5.3V
4480
4250
4365
4608
46'8
230
27
11/13/96
31
78
75
4.00
N/A
4710
4S40
4625
4609
4540
170
28
11/13/96
18
66
64
5.00
2.54
4260
4120
4190
4594
4393
140
29
11/13/96
18
66
S9
4.75
2.84
4640
43SO
4495
4590
4437
290
30
11/22/96
18
61
- - ----
13
---- --
4.50
--- ------
4.54
---
4680
4520
4600
4591
4428
160
'"' Averages
'••
67
76
4.92
---
4.5%
03/05/97 10:03 BMH /ASBUILTUSA /CRIS 214 -358 -1600 PAGE 6 OF 6
COMMENTARY OF STATISTICAL EVALUATION OF CONCRETE DESIGN RESULTS
Mix Nun: 8273 Strength: 4000 psi 0 28 Days
Paragraph 5.5 of ACI 318 -89 provides that as data becomes
available during construction, the amount by which (F'cr) must
exceed the specified value of (F'c) may be reduced, provided:
(a) 30 or more test results are available and average of
test results exceeds that required by Section 5.3.2.1,
using a standard deviation calculated in accordance
with Section 5.3.1.1, or
(b) 15 to 29 test results are available and average of test
results exceeds that required by Section 5.3.2.1, using
a standard deviation calculated in accordance with
Section 5.3.1.2.
The required average compressive strength has been calculated
using a standard deviation calculated in accordance with
ACI 318 -89 Section 5.3.1.1 or Section 5.3.1.2 and is the larger
value of these calculations:
F'cr = F' c + 1. 34 (SD)
4000 + 1.34( 283.1)
4379
F'cr = F'c + 2.33(SD) - 500
= 4000 + 2.33( 283.1) - 500
= 4160
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests ..........................
30
Maximum Value ............................
5135
psi
Minimum Value ............................
4050
psi
Range ..... ...............................
1085
psi
Average Strength .........................
4591
psi
Standard Deviation .......................
283
psi
Required Average Strength to satisfy
minimum probability conditions of
ACI 318 -89 Section 5.3.2.1 ...............
4379
psi
Design excess beyond code requirements...
212
psi