St Ann Catholic-LR070110CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061334.0019 Ireirracon Service Date: November 14, 2006 8901 carpenter Frwy, Ste #loo Dallas, Texas 75247 (214) 630 -1010 Client: Report Date: January 10, 2007 St Ann Catholic Church Project: St. Ann Catholic Parish Attn: Jennifer Lindsey New Addition 180 Samuel Blvd / 180 Samuel Blvd. Coppell TX 75019 Coppell, TX Project No.: 94061334 Material Information Specified Strength: 3600 psi @ 28 Days Batch Time: 7:10 AM Plant: 6 Supplier: Lattimore Materials Co Truck No: 976 Ticket No: 6294057 Mix I.D. No.: 1701 Water Added Onsite Before Test: 20 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Result Slump, inches: 6.50 Air Content, %: 5.4 Concrete Temperature, of 70 Ambient Temperature,oF: 68 Plastic Unit Weight, pcf: 143.2 Laboratory Test Data Set Specimen Diameter Area No. _ ID (inches) ( sq. inches 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 4 6.00 28.27 Sample information Date Cast: November 14, 2006 Time: 7:45 AM Sampled by: Mario A. Garcia Weather Conditions: Accumulative Yards: 20/250 Placement Method: Direct Discharge Sample Locations: Set 1 on sketch Placement Location: Paving, N of new addition. E of existing church, refer to attached sketch Specification Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days (lbs) (psi) 11/21/2006 7 114,040 4,030 12/12/2006 28 141,790 5,010 12/12/2006 28 140,840 4,980 Average (28 Days) 5,000 01/09/2007 56 151,470 5,360 Comments: Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 3 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94061334.0019 Service Date: November 14, 2006 Irerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Client: Report Date:January 10, 2007 St Ann Catholic Church Project: St. Ann Catholic Parish Attn: Jennifer Lindsey New Addition 180 Samuel Blvd 180 Samuel Blvd. Coppell TX 75019 Coppell, TX Project N o.: 94061334 Material Information Sample Information Specified Strength: 3600 psi @ 28 Days Date Cast: November 14, 2006 Time: 9:15 AM Sampled by: Mario A. Garcia Batch Time: 8:30 AM Plant: 6 Weather Conditions: Sunny Supplier: Lattimore Materials Co Accumulative Yards: 110/250 Truck No: 944 Ticket No: 6294069 Placement Method: Direct Discharge Mix I.D. No.: 1701 Sample Locations: Set 2 on sketch Water Added Onsite Before Test: 5 Gallons Placement Location: Paving, N of new addition. E of existing Water Added Onsite After Test: 5 Gallons church, refer to attached sketch Field Test Data Test Result Slump, inches: 6.50 Air Content, %: 6.3 Concrete Temperature, OF: 70 Ambient Temperature,OF: 65 Plastic Unit Weight, pcf: 142.0 Laboratory Test Data Maximum Compressive Set Specimen Diameter Area No. ID (inches) (s q. inches 2 1 6.00 28.27 2 2 6.00 28.27 2 3 6.00 28.27 2 4 6.00 28.27 Specification Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Comments: Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM. AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 3 ° P ; F°° , Age at Maximum Compressive Date Test Load Strength Tested (days (lbs) (psi) 11/21/2006 7 127,210 4,500 12/12/2006 28 140,300 4,960 12/12/2006 28 117,310 4,150 Average (28 Days) 4,560 01/09/2007 56 137,840 4,870 Comments: Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM. AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 3 ° P ; F°° , CONCRETE COMPRESSIVE STRENGTH TEST Irerracon Report Number: 94061334.0019 Service Date: November 14, 2006 Dall Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Client: Report Date: January 10, 2007 St Ann Catholic Church Project: St. Ann Catholic Parish Attn: Jennifer Lindsey New Addition 180 Samuel Blvd 180 Samuel Blvd. Coppell TX 75019 Coppell, TX Project No.: 94061334 Material Information Specified Strength: 3600 psi @ 28 Days Batch Time: 10:55 AM Plant: 6 Supplier: Lattimore Materials Co Truck No: 7023 Ticket No: 6294096 Mix I.D. No.: 1701 Water Added Onsite Before Test: OGallons Water Added Onsite After Test: 0 Gallons Sample Information Date Cast: November 14, 2006 Time: 11:30 AM Sampled by: Mario A. Garcia Weather Conditions: Partly cloudy Accumulative Yards: 210/250 Placement Method: Direct Discharge Sample Locations: Set 3 on sketch Placement Location: Paving, N of new addition. E of existing Air Content, %: church, refer to attached sketch Field Test Data Test Result Specification Test Metho Slump, inches: 6.50 ASTM C143 Air Content, %: 8.8 ASTM C231 Concrete Temperature, oF: 75 ASTM C1064 Ambient Temperature,01F. 73 ASTM C1064 Plastic Unit Weight, pcf: 139.2 ASTM C138 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) ( sq. inches Tested (days (lbs) (psi) 3 1 6.00 28.27 11/21/2006 7 119,390 4,220 3 2 6.00 28.27 12/12/2006 28 115,180 4,070 3 3 6.00 28.27 12/12/2006 28 134,310 4,750 Average (28 Days) 4,410 3 4 6.00 28.27 01/09/2007 56 126,750 4,480 Comments: NOTE: Dustin with Frank Dale Construction was notified of high slump and air content in testing. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Field Results Reported To: Dustin w /Frank Dale Constructi Terracon Rep: Mario A. Garcia Report Distribution (1) St Ann Catholic Church (1) Tech niStructures (1) City of Coppell TX (1) Pacheco Koch Consulting Engineers Reviewed by: (1) City of Coppell TX A. Bulent Ethem, P.G. (1) Page Southerland Page Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 3 -* ° 10 F°O .,, %PAV'(A �,r o^ I(' f 4 ' � F e;keC, t Y f l y_ Ter•racon Report No. 94061334.0019 Dated 11/14/06 { I � 4 f � i 5