CONCRETE MIX DESIGN 9604
CLIENT: C W 'YOUNG CONSTRUCTION October 6,1 "7
PROJECT: SPUR 553 @ DENTON TAP RD.
LOCATION: COPPELL, TEXAS
MIX 0604 DESIGN SPECIFICATIONS: 420016 sack- WRAIAEA
REQUIRED STRENGTH: 4200 PSI A 28 DAYS
CEMENT: ASTM C1S0 TYPE III
MAXIMUM PLACEMENT SLUMP: 4 INCH
CUAKSE AGGREGATE: ASTM C33 SIZE NOA7
AIR ENTRAINING ADMIXTURE: ASTM 0260
WATER REDUCING ADMIXTVREt ASTM C494(TYPE D)
WATLR/CEMENMIOUS RATIO: 0.50 LUMB
.MATERIALS: ONE CUBIC YARD WEIGHTS (SSD)
CEMENT:
COARSE AGGREGATE:
FINE AGGREGATE:
WATER:
ADMIXTURE ASTM 0260:
ADMEMRE ASTM C494:
564 LBS
1850 LBS
1182 LBS
282 LBS
2.8 O S
16.9 OZ5
PLEASE NOTE
VOLUMES
2.87
11.06
7.20
4.52
1.35
27.00 CF
ASTM C94 STANDARD SPECIFICATIONS FOR READY MIXED CONCRETE STATES AS FOLLOWS:
,, VMXN THE CONCRETE STUNGY'H IS USED AS A BASIS FOR ACCWFTANCE, THE
MANUFACTURER SHALL BE ENTITLED TO COPIES OF TEST REPOR'T'S.. THE INDIVIDUAL WHO
SAMPLES AND JESTS CONCRETE MUST BE CERTIFIED ACI LEVEL L"
ADDITIONAL WATER ADDED IN EXCESS OF SPECIFIED SLUMP IS AT CUSTOMERS IIISIL
TO ENSURE PROPER DESIGN ORDER BY MIX #604