CF-Justice Center-LR 960711ATEC Associates, Inc.
11356 Mathis Avenue
Dallas, Texas 75229
(214)556-2204
METRO 263-1681
REPORT OF CONCRETE COMPRESSION TEST
Project: Coppel Justice Center Date Sampled: 07/11/96
Client: City of Coppell Our Report No: 25-02-96-00068.47
Field Test Data
Location of Pour when Sampled: Facing Brick in row 10 along line 4 from A.5 to B-8
Contractor Mid South Supplier/Plant: Batched on site
Sampled By: L. Itatcliff Delivery Ticket No.: -----
Time: Batched: 10:30 Sampled: 11:00 Truck Number: ---
Temperature: Air: 81°F Concrete: 78°F Load Size: -- cu.yds.
Slump: --- in. Air Content: ---% Mint ID No.: Type N
Water Added on site: 0 gals.
Compressive Strength Test Results
Spedmen Type: Cubes 2" :st 2" Test Method: AS"rM C-39„ ASTM C-1231 ASThl C-617
Set
No. Specimen No. Type
Curing. Date Tested Age Daps ' ,Failure Load, ibs. Specimen Area (sq.
fu.) Compressive
Strength, FSL
1 2105 Lab 07-18 7 4,000 4.0 1,000
1 2106 Lab 08-08 28 5,740 4.0 1,440
1 2!~J7 Lab 08-08 28 5,860 4.0 1,470
SPECIFIED STRENGTH 28 750
Remarks: (Type N Mortar Mix)
Respectfully submitted,
i_
This report represents only the materials tested and may or may not be representative of identical or similar materials.