CF-Justice Center-LR 960711ATEC Associates, Inc. 11356 Mathis Avenue Dallas, Texas 75229 (214)556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Coppel Justice Center Date Sampled: 07/11/96 Client: City of Coppell Our Report No: 25-02-96-00068.47 Field Test Data Location of Pour when Sampled: Facing Brick in row 10 along line 4 from A.5 to B-8 Contractor Mid South Supplier/Plant: Batched on site Sampled By: L. Itatcliff Delivery Ticket No.: ----- Time: Batched: 10:30 Sampled: 11:00 Truck Number: --- Temperature: Air: 81°F Concrete: 78°F Load Size: -- cu.yds. Slump: --- in. Air Content: ---% Mint ID No.: Type N Water Added on site: 0 gals. Compressive Strength Test Results Spedmen Type: Cubes 2" :st 2" Test Method: AS"rM C-39„ ASTM C-1231 ASThl C-617 Set No. Specimen No. Type Curing. Date Tested Age Daps ' ,Failure Load, ibs. Specimen Area (sq. fu.) Compressive Strength, FSL 1 2105 Lab 07-18 7 4,000 4.0 1,000 1 2106 Lab 08-08 28 5,740 4.0 1,440 1 2!~J7 Lab 08-08 28 5,860 4.0 1,470 SPECIFIED STRENGTH 28 750 Remarks: (Type N Mortar Mix) Respectfully submitted, i_ This report represents only the materials tested and may or may not be representative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.