Loading...
CF-Justice Center-LR 960708ATEC Associates, Inc. 11356 Mathis Avenue Dallas, Texas 75229 (214) 556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Coppell Justice Center Date Sampled: 07/08/96 Client: City of Coppell Our Report No: 25-02-96-00068.46A Field Test Data Location of Pour when Sampled: Dempster Enclosure Grid Beam Contractor Duratex Construction Supplier/Plant: Mid-Cities Ready-Mix Sampled By: C. Delgado Delivery Ticket No.: 16581 Time: Batched: 12:45 am Sampled: 1:43 Truck Number: 446 Temperature: Air: 98°F Concrete: 102°F Load Size: 7 cu.yds. Slump: 4.5 in. Air Content: ---~ Mix ID No.: Mix 9351 Water Added on site: 0 gals. Compressive Strength Test Results Specimen Type: Cylinder 6" X 12" Test Method: ASTM ~-3$ ASTM C-1231. ASTM C-617 Set No, ' Specimen'No. Type Curing Date Tested Age Days. Failure Load, Ibs. Specimen Area (sq. in.} Compressive Strength, PSI 1 1983 lab 07-15 7 84,160 28.27 2,980 1 1984 Lab 08-OS 28 113,580 28.27 4,020 1 1985 lab O8-OS 28 107,840 28.27 3,810 1 1986 Lab 08-OS Hold SPECIFIED STRENGTH 28 3,000 Remarks: Cylinder diameter = 6.00 in. unless noted otherwise. * Contractor was notified of temperature Respectfully submitted, .~-, ~' -~-~ •h This report represents only the materials tested and may or may not be representative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.