CF-Justice Center-LR 960624~~ r ATEC Associates, Inc. 11356 Mathis Avenue Dallas, Texas 75229 (214)556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Coppel Justice Center Date Sampled: 06/24/96 Client: City of Coppell Our Report No: 25-02-96-00068.43A Field Test Data Location of Pour when Sampled: NW End of Building (Side-Walk) Contractor Duratex Construction Supplier/Plant: Redi/Mix/1 Sampled By: C. Delgado Delivery Ticket No.: 18146 Time: Batched: 10:35 Sampled: 11:37 Truck Number: 189 Load Size: 9 cu.yds. Temperature: Air: 96°F Concrete: 97°F Mix ID No.: 720 Slump: 7.0 in. Air Content: 3.2 % Water Added on site: 0 gals. Compressive Strength Test Results Specimen Type .Cyl. 6" x 12" Test Method: ASTM C-39, ASTM C-1231. X ASTM C-617 `Set No. Specimen No. Type Ctung Date Tested 'Age Days Failure Load, Ibs. Specimen Area (sq. ia.) Compressive Strength, PSI 1 1793 Lab 07-01 7 60,480 28.27 2,140 1 1794 Lab 07-22 28 82,180 28.27 2,910 1 1795 Lab 07-22 28 88,320 28.27 3,120 1 1796 Lab 08-19 Hold SPECIFIED STRENGTH 28 3.~ Remarks: Cylinder diameter = 6.00 in. unless noted otherwise. Average 28 day strength of 3020 psi exceeds required strength. Respectfully submitted, This report represents only the materials tes~ed~tld may oi~ may not be representative of identical or similaz materials. This report shall not be reproduce except in Its, entirety and with the express written permission of ATEC Associates, Inc.