CF-Justice Center-LR 960621yam/ ATEC Associates, Inc. 11356 Mathis Avenue Dallas, Texas 75229 (214) 556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Criminal Justice Center Date Sampled: 06/21/96 Client: City of Coppell Our Report No: 25-02-96-00068.42 Field Test Data Location of Pour when Sampled: Paving, 9'E and 4'S of NE Comer of Drive Contractor First South Contractors Supplier/Plant: Redi-Mix/1 Sampled By: J. Travis Delivery Ticket No.: 18026 Time: Batched: 10:40 Sampled: 11:20 Truck Number: 161 Load Size: 9 cu.yds. Temperature: Air: 90°F Concrete: 84°F Mix ID No.: 720 Slump: 4.0 in. Air Content: 4.6% Water Added on site: 15 gals. Compressive Strength Test Results Specimen Type_ Cylinder Test Method: ASTM C-39, ASThI C-1231 x AST1tii C-617 Set. No. Specimen No. Type Curu-g Date Tested .Age Days. Failure Load, 1bs, Specimen Area (sq. in.) Compres5sive Strength, PSI' 1 1753 Lab 06-28 7 76140 2.690 1 1754 Lab 07-19 28 101,820 3,600 1 1755 Lab 07-19 28 108,920 3,850 1 1756 Lab 07-19 Hold SPECIFIED STRENGTH 28 3,000 Kemarks: Respectfully submitted, ^ /. This report represents only the materials tested and may or may not be representative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.