CF-Justice Center-LR 960606/~~ D ~~~Q . ATEC Associates, Inc. 11356 Mathis Avenue ~ ~ ~ 2 ~ HE(,'~ Dallas, Texas 75229 METRO 263 681 ~Op~~~O ~Q~~~ REPORT OF CONCRETE COMPRESSION TEST Project: Criminal Justice Center Date Sampled: 06/06/96 Client: City of Coppell Our Report No: 25-02-96-00068.41 Field Test Data Location of Pour when Sampled: Transformer Pad Contractor Duratex Construction Supplier/Plant: Redi/Mix Sampled By: A. Rodriquez Delivery Ticket No.: 17680 Time: Batched: 2:03 Sampled: 3:00 Truck Number: 169 Load Size: 9 cu.yds. Temperature: Air: 98°F Concrete: 91°F Mix ID No.: 720 Slump: 5.0 in. Air Content: 4.8 % Water Added on site: 5.0 gals. Compressive Strength Test Results Specimen Type: Cyl. 6"X12" Test Method: ASTM C-39, ASTM C-1231 X ASTM Cfi17 Set No. Specimen No. Type Cuing Date Tested Age Days Failure Load, Ibs. Specimen Area (sq, in.) Compressive Strength, PSI 1 1689 Lab 06-25 7 53,020 28.27 1,880 1 1690 Lab 07-16 28 82,060 28.27 2,900 1 1691 Lab 07-16 2S 81,340 28.27 2,880 1 1692 Lab 08-13 56 95,420 28.27 3,380 SPECIFIED STRENGTH 28 ~.~ emar s~ .v m er tameter = m. un ess noted otherwise. Respectfully submitted, /.. This report represents only the materials test and may or may not be representative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc. ~~~~ - . ~ . .~ ATEC Associates, Inc. .~ ~ 1. 1 ~ kt~~ D 11356 Mathis Avenue Dallas, Texas 75229 (214) 556-2204 ~ ~ ~ °'~'o~o ~„t° Q~~NI~i METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Criminal Justice Center Date Sampled: 06/06/96 Client: City of Coppell Our Report No: 25-02-96-00068.38 Field Test Data Location of Pour when Sampled: lOW + SN of SE Corner -Holding Cell Roof Slab Contractor Mid South Builders Supplier/Plant: Redi/Mix Sampled By: A. Rodriquez Delivery Ticket No.: 17017 Time: Batched: 1:21 Sampled: 1:30 Truck Number: 148 Load Size: 9 cu.yds. Temperature: Air: 95°F Concrete: 92°F Mix ID No.: 726 Slump: 5.0 in. Air Content: --% Water Added on site: 25 gals. Compressive Strength Test Results Specin:n~ Type: CpL 6"X12" Test Method: ASTM C-39, ASTM C-1231 X ASTM C-617 Set No. Specimen No. Type Curing Date Tested Age Dags Failure Load, lbs. Specimen. Area (sq. [n.) Compressive Strength, PSI 1 1538 Lab 06-13 7 85,500 28.27 3,020 1 1539 Lab 07-04 28 109,660 28.27 3.880 1 1540 Lab 07-04 28 111,680 28.27 3,950 1 1541 Lab 07-04 Hold SPECIFIED STRENGTH 28 3.~ emar y In er iameter = tn. u ess noted otherwise. Respectfully submitted, This report represents only the materials tested and may or may not be representative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.