Loading...
CF-Justice Center-LR 960516~~i ATEC Associates, Inc. 11356 Mathis Avenue Dallas, Texas 75229 (214) 556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Criminal Justice Center Date Sampled: 05/16/96 Client: City of Coppell Our Report No: 25-02-96-00068.33A Field Test Data Location of Pour when Sampled: 1st lift 2 hour fire wall .r ,' ~~ ~`' Contractor Mid South Builders Supplier/Plant: On-Site Mixer Sampled By: L. Ratcliff Delivery Ticket No.: --- Time: Batched: 1:30 Sampled: 1:30 Truck Number: --- Load Size: -- cu.yds. Temperature: Air: 93°F Concrete: 78°F Mix ID No.: --- Slump: 2. in. Air Content: ---~ Water Added on site: -- gals. Compressive Strength Test Results S~ecimet Type _Cp1: 3" X 6" Test Method: ASTM C-39, ASTM C-1231 AS'I'M C-6t7 X Set No. Specimen No. Type Curing Date Tested Age Daps Failure Load, ms. Specimen Area (sq. in.) Compre5slve Strength, PSI 1 1324 Lab OS-23 7 24,720 7.07 3,500 1 1325 Lab 06-13 28 36,500 7.07 5,160 1 1326 Lab 06-13 28 34,400 7.07 4,870 1 1327 lab 06-13 Hold SPECIFIED STRENGTH 28 2,000 Remarks: Respectfully submitted, ~---~~ This report represents only the materials tested and may or may not be r esentative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.