Loading...
CF-Justice Center-LR 960515~~~~ ~- ATEC Associates, Inc. '~ 11356 Mathis Avenue Dallas, Texas 75229 (214) 556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Criminal Justice Center Date Sampled: 05/15/96 Client: City of Coppell Our Report No: 25-02-96-00068.31 Field Test Data Location of Pour when Sampled: Holding Cells, CMU Walls F to G & 1 to 1.7 Contractor I7t><ratex Const. Supplier/Plant: Site Sampled By: A. Rodriquez Delivery Ticket No.: --- Time: Batched: 11:00 Sampled: 11:00 Truck Number: --- Load Size: -- cu.yds. Temperature: Air: 78°F Concrete: 88°F Mix ID No.: Type 'S' Stump: 3.0 in. Air Content: --% Water Added on site: -- gals. Compressive Strength Test Results Specimen Type: Cyt. 2° X 2" X' 2" Test Method: ASTM C~9, ASTM C-1231 ASTM 6-617 Set No. Specimen No. Type Cueing Date Tested Age Days Faihire Load, Ibs. Specimen Area (sq. in.) Compressive Strength,. PSI 1 1270 Lab OS-22 7 11,860 4.0 2,970 1 1271 Lab 06-12 28 14,300 4.0 3,575 1 1272 Lab 06-12 28 13,460 4.0 3,370 SPECIFIED STRENGTH 28 1.~ Remarks: Respectfully submitted, -'~_ This report represents only the materials tested and may or may not be rep esentative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.