CF-Justice Center-LR 960219~3/ ATEC Associates, Inc. 11356 Mathis Avenue Dallas, Texas 75229 (214) 556-2204 METRO 263-1681 REPORT OF CONCRETE COMPRESSION TEST Project: Coppell Justice Center Date Sampled: 02-19-96 Client: City of Coppell Our Report No: 25-02-95-00068.09F Field Test Data Location of Pour when Sampled: Piers E-1, J-1.4, D.5-1, D-1, C-1 Contractor Mid-South Supplier/Plant: Redi-Mix Sampled By: E. Finney Delivery Ticket No.: 98345 Time: Batched: 11:03 Sampled 12:05 Truck Number: 196 Load Size: 9 cu. yds Temperature: Air: 79°F Concrete 72°F Mix ID No.: 723 Shunp: 4.5 in. Air Content ---% Water Added on site: 0 gals. Com.~ressive Strength Test Results Specimen Typr. Cyb. 6" X' IZ" Test Method: ASTM C-39, A51M C-1231 X ASTM C-fi17 Set No. _ specimen No. Type Curing Date Teded Age Days Failure Load, lbs. Specimen Area tag. in.) Compressive Strength, PSI 1 9217 Lsb 02-26 7 96,120 28.27 3,400 1 9218 Lab 03-18 28 126,580 28.27 4,480 l 9219 Lsb 03-18 28 115,120 28.27 4,070 1 9220 Lab 03-18 Hold SPECIFIED STRENGTH 28 3,000 P.mar C' .V lr: E'r lameter = - In. :In ess noted othen~~iSe. Respectfully submitted, This report represents only the materials tested and may or may not be representative of identical or similar materials. This report shall not be reproduced except in its entirety and with the express written permission of ATEC Associates, Inc.