CF-Justice Center-LR 960216Q~6ea~¢0
ATEC Associates, Inc. MAR 2 2 REI:'il
11356 Mathis Avenue ~j®~s° ~dab~ i.t'®~II~ttb
Dallas, Texas 75229 ~s'
(214)556-2204
METRO 263-1681
REPORT OF CONCRETE COMPRESSION TEST
Project: Coppell Justice Center Date Sampled: 02-16-96
Client: City of Coppell Our Report No: 25-02-95-00068.08E
Field Test Data
Location of Pour when Sampled: Piers J.6-3.3, K-3.1, J-3.1, H-3.1
Contractor Duratex Construction Supplier/Plant: Redi-Mix
Sampled By: B. Holt Delivery Ticket No.: 98236
Tune: Batched: 11:25 Sampled Truck Number: 110Load Size: 9 cu. yds
Temperature: Air: 49°F Concrete 60°F Mix ID No.: 723
Slump: 4.5 in. Air Content ---4b Water Added on site: 0 gals.
Compressive Strength Test Results
Specimen Typc._CyM. 6" X 12" `Test Melbod: ASTM C-39, ASTM C-1231 X ASTM C-617
Set
No. Specimen No. Typr
Curing Date Tested Age Daya Failure Load.
Iba. Specimen Ares
(sq. inJ' Compra+ive
Strength; PSl
1 9193 Lab 02-23 7 94,540 28.27 3,340
1 9194 Lab 03-IS 28 122,680 28.27 4,340
1 9195 Lab 03-IS 28 123,520 28.27 4,370
1 9196 Lab 03-IS Hold
SPECIFIED STRENGTH 28 3,~
Remarks: Cylinder diameter = 6.00 in. unless noted otherwise.
Respectfully submitted,
~^
This report represents only the materials tested and may or may not be representative of identical or similar
materials. This report shall not be reproduced except in its entirety and with the express written permission
of ATEC Associates, Inc.