Gateway BP(3.1)-LR070319one Engineering
Client: Transwestem Commercial Sere
Mr. Ric Nelson
Transwestern Co cial Services
5001 Sprin ey Rd., Ste 600W
Dallas 5244
Project: eway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM S
CONTRACTOR: Constructors Associates
Test Methods: ASTM D -2922
M/D No.
ASTM D -3017
1 Dark Brown Clay
Description
2 Tannish Brown Silty Clay
TEST
NO
TEST LOCATION
Middle building pad
1 25' south, 30' east from northwest corner,
8th lift
Middle building pad
2 75' south, 60' east from northwest corner,
8th lift
Middle building pad
3 125' south, 90' east from northwest corner.
8th lift
Middle building pad
4 175' south, 120' east from
8th lift
PROJECT DATA
Gauge: Troxler 3430
Gauge Serial No: 33438
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
PROBE
DEPTH
MID
No.
6" 1
6" 1
6" 1
northwest corner, 6" 1
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
IN -PLACE DENSITY TESTING
Current: 575
Previous: 577
Report No.:
Project No.:
Date of Service:
Report Date:
33.2 111.2
35.2 111.0
32.0 111.5
32.9 111.0
278950
0712786
02/17/2007
03/19/2007
Standard Counts
Moisture Density
Current: 2703
Previous: 2651
Project Requirements
Moisture Density
27.0 89.0 Minimum +4 92 96
24.5 93.5 Minimum +4 92 96
MOISTURE WET DENSITY DRY DENSITY
(pcf) (Pei)
83.5
82.1
84.5
83.5
DENSITY
max)
94
92
95
94
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7SS Page 1 of 3
Report No.: 278950
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE M.ID MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (pct) max)
Middle building pad
5 160' south, 65' west from northeast corner, 6" 1 31.3 110.8 84.4 95
8th lift
Middle building pad
6 120' south, 105' west from northeast corner, 6" 2 30.2 111.7 85.8 92
8th lift
Middle building pad
7 90' south, 65' west from northeast corner, 6" 1 32.8 111.4 83.9 94
8th lift
Middle building pad
8 30' south, 80' west from northeast corner, 6" 2 30.4 112.0 85.9 92
8th lift
Middle building pad
9 30' south, 40' east from northwest corner, 6" 1 33.0 1 1 1.3 83.7 94
9th lift
Middle building pad
10 60' south, 70' east from northwest corner, 6" 1 31.9 111.6 84.6 95
9th lift
Middle building pad
11 90' south, 100' east from northwest corner, 6" 1 31.7 112.1 85.1 96
9th lift
Middle building pad
12 120' south, 130' east from northwest corner, 6" 1 33.4 111.5 83.6 94
9th lift
Middle building pad
13 150' south, 75' east from northwest corner, 6" 1 30.7* 110.8 84.8 95
9th Lift
Middle building pad
14 80' south, 80' east from northwest corner, 6" 1 32.2 111.7 84.5 95
9th Lift
Middle building pad
15 40' south, 45' east from northwest corner. 6" 1 31.8 1 1 1.1 84.3 95
9th lift
Middle building pad
16 110' south, 100' west from northwest corner, 6" 1 32.6 111.9 84.4 95
9th lift
Middle building pad
17 40' south, 25' east from northwest corner, 6" 2 32.7 116.8 88.0 94
10th lift
Middle building pad
18 60' south, 56' east from northwest corner, 6" 2 30.8 116.9 89.4 96
10th lift
Middle building pad
19 80' south, 78' east from northwest corner, 6" 2 32.3 116.6 88.1 94
10th lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7SS Page 2 of 3
Report No.: 278950
Project No.: 0712786
Technician: Nick Ciofani
Report Distribution:
(1) Transwestem Commercial Services
(1) City of Coppell
(1) City of Coppell
(1) Constructors
Client: Transwestern Commercial Services
Started: 9:45am
(1) Murray Construction Co, Inc.
(1) Aztec Environmental
Finished: 1:45pm
Michael Cox, SET
Project Manager
TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcf) (pcf) max)
Middle building pad
20 120' south, 90' east from northwest corner, 6" 2 33.0 116.4 87.5 94
10th Lift
Middle building pad
21 36' south, 50' east from northwest corner. 6" 2 31.4 116.4 88.6 95
10th lift
Middle building pad
22 68' south, 80' east from northwest corner, 6" 2 32.4 116.5 88.0 94
10th lift
Middle building pad
23 90' south, 1 10' east from northwest corner, 6" 1 36.1 114.6 84.2 95
10th lift
Middle building pad
24 132' south, 150' east from northwest corner. 6" 1 35.5 114.5 84.5 95
10th lift
Middle building pad
25 Retest of Test #13, this report 6" 1 42.5 119.4 83.8 94
An asterisk appears next to test results which do NOT meet the project specifications.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) cr any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rope Engineering Services, Ltd.
7SS Page 3 of 3
Rone Engineering
to
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestem Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D -2922
M/D No.
TEST
NO
ASTM D -3017
1 Dark Brown Clay
Description
Tannish Brown Silty Clay
TEST LOCATION
Gauge: Troxler 3430
Gauge Serial No: 33438
Test Mode: DT
Middle building pad
1 25' south, 30' east from northwest corner,
3rd lift
Middle building pad
2 75' south, 60' east from northwest corner,
3rd lift
Middle building pad
3 125' south, 90' east from northwest corner.
3rd lift
Middle building pad
4 175' south, 120' east from northwest corner,
3rd lift
FIELD DENSITY TESTS
IN -PLACE DENSITY TESTING
Current: 577
Previous: 578
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
Report No.:
Project No.:
Date of Service:
Report Date:
27.0 89.0 Minimum +4 92 96
24.5 93.5 Minimum +4 92 96
PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (pct) (pcf) max)
6" 1 35.7 112.8
6" 1 36.0 114.2
6" 1 34.4 113.8
6" 1 35.2 113.4
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
278848
0712786
02/16/2007
03/19/2007
Standard Counts
Moisture Density
Current: 2651
Previous: 2690
Project Requirements
Moisture Density
83.1
84.0
84.7
83.9
93
94
95
94
LIMITATIONS: The test results presented herein were prepared base upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subjee t matter provided b} persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7SS Page 1 of 4
Report No.: 278848
Project No.: 0712786
TEST
NO TEST LOCATION
Client: Transwestern Commercial Services
PROBE \1 /D MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (pci) (pcl) max)
Middle building pad
5 30' south, 90' west from northeast corner, 6" 1 35.4 115.4 85.2 96
3rd Lift
Middle building pad
6 90' south, 80' west from northeast corner, 6" 1 36.0 114.5 84.2 95
3rd lift
Middle building pad
7 120' south, 105' west from northeast corner, 6" 1 36.2 114.3 83.9 94
3rd lift
Middle building pad
8 160' south, 65' west from northeast corner, 6" 1 37.8 114.2 82.9 93
3rd lift
Middle building pad
9 30' south, 40' east from northwest corner, 6" 1 34.3 114.0 84.9 95
4th lift
Middle building pad
10 60' south, 70' east from northwest corner, 6" 1 36.1 115.4 84.8 95
4th lift
Middle building pad
11 90' south, 100' east from northwest corner, 6" 1 36.9 114.0 83.3 94
4th lift
Middle building pad
12 118' south, 150' east from northwest corner, 6" 1 35.2 114.5 84.7 95
4th lift
Middle building pad
13 145' south, 75' east from northwest corner, 6" 1 36.9 114.7 83.8 94
4th lift
Middle building pad
14 80' south, 90' east from northwest corner, 6" 1 36.3 114.5 84.0 94
4th lift
Middle building pad
15 35' south, 40' west from northeast corner, 6" 1 35.9 114.4 84.2 95
4th lift
Middle building pad
16 106' south, 100' west from northeast corner, 6" 1 37.0 114.4 83.5 94
4th lift
Middle building pad
17 40' south, 25' east from northwest corner. 6" 1 38.7 113.9 82.1 92
5th lift
Middle building pad
18 60' south. 56' east from northwest corner, 6" 1 38.2 114.0 82.5 93
5th lift
Middle building pad
19 80' south, 78' east from northwest corner. 6" 1 37.4 114.6 83.4 94
5th lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering .Services, Ltd.
7SS Page 2 of 4
Report No.: 278848
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE M D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (pct) max)
Middle building pad
20 120' south, 90' east from northwest corner, 6" 1 34.8 114.3 84.8 95
5th lift
Middle building pad
21 36' south, 50' east from northwest corner, 6" 1 34.2 114.2 85.1 96
5th lift
Middle building pad
22 68' south, 80' east from northwest corner, 6" 1 35.4 113.9 84.1 94
5th lift
Middle building pad
23 89' south, 110' east from northwest corner, 6" 1 35.2 114.0 84.3 95
5th lift
Middle building pad
24 132' south, 146' east from northwest corner, 6" 1 35.9 114.0 83.9 9
5th lift
Middle building pad
25 20' south, 75' west from northeast corner, 6" 1 35.3 114.2 84.4 95
6th lift
Middle building pad
26 50' south, 30' west from northeast corner, 6" 1 33.8 113.5 84.8 95
6th Lift
Middle building pad
27 70' south, 60' west from northeast corner. 6" 1 35.4 113.9 84.1 94
6th lift
Middle building pad
28 90' south, 90 west from northeast corner, 6" 1 36.5 114.9 84.2 95
6th lift
Middle building pad
29 110' south, 110' west from northeast comer, 6" 1 35.6 114.3 84.3 95
6th lkift
Middle building pad
30 30' south, 50' west from northeast corner, 6" 1 36.3 114.1 83.7 94
6th lift
Middle building pad
31 80' south, 100' west from northeast corner, 6" 1 36.7 113.6 83.1 93
6th lift
Middle building pad
32 126' south. 130' west from northeast corner, 6" 1 37.0 113.7 83.0 93
6th lift
Middle building pad
33 25' south, 40' west from northeast corner. 6" 1 36.8 114.2 83.5 94
7th lift
Middle building pad
34 75' south, 70' west from northeast corner, 6" 1 35.6 114.7 84.6 95
7th lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, at pearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
17SS Page 3 of 4
Report No.: 278848
Project No.: 0712786
TEST PROBE MD MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pci) (pci) max)
Technician: Nick Ciofani
Report Distribution:
(1) Transwestern Commercial Services
(1) City of Coppell
(7) City of Coppell
(1) Constructors
Client: Transwestern Commercial Services
Middle building pad
35 125' south, 100' west from northeast corner, 6" 1 35.5 114.4 84.4 95
7th lift
Middle building pad
36 175' south, 130' west from northeast corner, 6" 1 35.1 114.4 84.7 95
7th Lift
Middle building pad
37 30' south, l 80' west from northeast corner. 6" 1 36.2 114.3 83.9 94
7th lift
Middle building pad
38 80' south, 85' west from northeast corner, 6" 1 36.3 114.8 84.2 95
7th lift
Middle building pad
39 105' south, 105' west from northeast corner, 6" 1 34.2 113.9 84.9 95
7th lift
Middle building pad
40 180' south, 136' west from northeast corner, 6" 1 34.2 114.5 85.3 96
7th lift
Test results on this report meet project specification.
Started: 2:OOpm Finished: 6:30p
(1) Murray Construction Co, Inc.
(1) Aztec Environmental
1
Rone
Ichael Cox, SET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
ASS Page 4 of 4
Rone Engineering
to
Client: Transwestem Commercial Services
Mr. Ric Nelson
Transwestem Commercial Services
5001 Spring Valley Rd.. Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D 2922
ASTM D 3017
M/D No.
1 Dark Brown Clay
2 Tannish Brown Silty Clay
TEST
NO
Building pad
1 Pad 2, 75' north,
corner. 4th lift
Building pad
2 Pad 2, 75' north,
corner, 4th lift
Building pad
3 Pad 2, 75' north,
corner, 4th lift
Building pad
4 Pad 2, 25' north,
corner, 4th lift
Description
TEST LOCATION
35' east from southwest
70' east from southwest
110' east from southwest
35' east from southwest
Gauge: Troxler 3430
Gauge Serial No: 33438
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum Project Requirements
Moisture Density pcf Moisture Density
FIELD DENSITY TESTS
PROBE M/D
DEPTH No.
6" 1
6" 1
6" 1
6" 1
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
IN -PLACE DENSITY TESTING
Current: 582
Previous: 578
Report No.:
Project No.:
Date of Service:
Report Date:
278654
0712786
02/14/2007
03/19/2007
Standard Counts
Moisture Density
27.0 89.0 Minimum +4
24.5 93.5 Minimum +4
36.3 113.3
35.3 113.5
33.7 113.1
35.4 113.5
Current: 2685
Previous: 2676
MOISTURE WET DENSITY DRY DENSITY DENSITY
(Pei) (Pci) max)
83.1
83.9
84.6
83.8
92 96
92 96
93
94
95
94
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7SS Page 1 of 4
Report No.: 278654
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE NUD MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTII No. (pen) (pct) max)
Building pad
5 Pad 2, 25' north. 70' east from southwest 6" 1 36.3 112.7 82.7 93
corner, 4th lift
Building pad
6 Pad 2, 25' north, 110' east from southwest 6" 1 36.5 113.0 82.8 93
corner. 4th lift
Building pad
7 Pad 1, 25' south, 35' east from northwest 6" 1 35.7 113.6 83.7 94
corner, 4th lift
Building pad
8 Pad 1, 25' south, 70' east from northwest 6" 1 33.8 113.1 84.5 95
corner, 4th lift
Building pad
9 Pad 2, 25' south, 110' east from northwest 6" 1 34.0 112.6 84.0 94
corner, 4th lift
Building pad
10 Pad 1, 75' south. 35' east from northwest 6" 1 32.2 108.1 81.8 92
corner, 4th lift
Building pad
11 Pad 1, 75' south, 70' east from northwest 6" 1 31.5 108.0 82.1 92
corner, 4th lift
Building pad
12 Pad 1, 75' south, 110' east from northwest 6" 1 31.8 107.8 81.8 92
corner. 4th lift
Building pad
13 Pad 2, 25' north, 35' east from southwest 6" 1 34.1 110.0 82.0 92
corner, 5th lift
Building pad
14 Pad 2, 25' north, 70' east from southwest 6" 1 33.7 110.7 82.8 93
corner, 5th lift
Building pad
15 Pad 2, 25' north. 110' east from southwest 6" 1 36.5 112.2 82.2 92
corner, 5th lift
Building pad
16 Pad 2, 75' north. 35' east from southwest 6" 1 34.4 112.8 83.9 94
corner, 5th lift
Building pad
17 Pad 2. 75' north, 70' east from southwest 6" 1 32.8 112.6 84.8 95
corner, 5th lift
Building pad
18 Pad 2, 75' north, 110' east from southwest 6" 1 33.0 112.9 84.9 95
corner, 5th lift
Building pad
19 Pad 1, 25' south. 35' east from northwest 6" 1 35.7 111.0 81.8 9
corner, 5th lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rope Engineering Services, Ltd.
17SS Page 2 of 4
Report No.: 278654
Project No.: 0712 786
Client: Transwestern Commercial Services
TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcf) (pcf) max)
Building pad
20 Pad 1, 25' south, 70' east from northwest 6" 1 33.5 112.0 83.9 94
corner, 5th lift
Building pad
21 Pad 1, 25' south, 110' east from northwest 6" 1 35.1 111.6 82.6 93
corner, 5th lift
Building pad
22 Pad 1, 75' south, 35' east from northwest 6" 1 32.8 112.1 84.4 95
corner, 5th lift
Building pad
23 Pad 1. 75' south. 70' east from northwest 6" 1 33.1 110.9 83.3 94
corner, 5th lift
Building pad
24 Pad 1, 75' south. 110' east from northwest 6" 1 31.8 110.6 83.9 94
corner, 5th lift
Building pad
25 Pad 2, 25' north, 35' east from southwest 6" 1 35.3 1 1 1.2 82.2 92
corner, 6th lift
Building pad
26 Pad 2, 25' north. 70' east from southwest 6" 1 33.1 110.7 83.2 93
corner, 6th lift
Building pad
27 Pad 2, 25' north, 110' east from southwest 6" 1 32.9 111.6 84.0 94
corner, 6th lift
Building pad
28 Pad 2, 75' north, 35' east from southwest 6" 1 35.7 111.0 81.8 92
corner, 6th lift
Building pad
29 Pad 2, 75' north, 70' east from southwest 6" 1 34.0 110.8 82.7 93
corner, 6th lift
Building pad
30 Pad 2, 75' north, 110' east from southwest 6" 1 34.2 111.0 82.7 93
corner, 6th lift
Building pad
31 Pad 1, 25' south, 35' east from northwest 6" 1 34.6 110.5 82.1 92
corner, 6th lift
Building pad
32 Pad 1, 25' south, 70' east from northwest 6" 1 32.5 111.7 84.3 95
corner, 6th lift
Building pad
33 Pad 1, 25' south, 110' east from northwest 6" 1 34.3 111.1 82.7 93
corner, 6th lift
Building pad
34 Pad 2. 75' north, 35' east from southwest 6" 1 36.1 111.6 82.0 92
confer, 6th lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
i7SS Page 3 of 4
Report No.: 278654
Project No.: 0712786
TEST
NO TEST LOCATION
Building pad
35 Pad 2, 75' north. 70' east from southwest
corner, 6th lift
Building pad
36 Pad 2, 75' north, 110' east from southwest
corner, 6th lift
Building pad
37 Pad 1 25' south, 35' east from northwest
corner. 7th lift
Building pad
38 Pad 1, 25' south, 70' east from northwest
corner, 7th lift
Building pad
39 Pad 1, 25' south, 110' east from northwest
corner, 7th lift
Building pad
40 Pad 1. 75' south, 35' east from northwest
corner, 7th lift
Building pad
41 Pad 1, 75' south. 70' east from northwest
corner, 7th lift
Building pad
42 Pad 1, 75' south, 110' east from northwest
corner, 7th Lift
Building pad
43 Pad 2, 25' north, 35' east from southwest
corner. 7th lift
Building pad
44 Pad 2, 25' north. 70' east from southwest
corner, 7th lift
Building pad
45 Pad 2, 25' north. 110' east from southwest
corner, 7th lift
Building pad
46 Pad 2, 75' north, 35' east from southwest
corner, 7th lift
Building pad
47 Pad 2, 75' north, 70' east from southwest
corner, 7th lift
Building pad
48 Pad 2, 75' north, 110' east from southwest
corner, 7th lift
Technician: Nick Ciofani
Report Distribution:
(11 Transwestern Commercial Services
(1) City ofCoppell
(1) City of Coppell
(1) Constructors
Client: Transwestern Commercial Services
Test results on this report meet project specification.
Started: 4:15pm
(1) Murray Construction Co. Inc.
(1) Aztec Environmental
PROBE M/D MOISTURE WET DENSITY DRY DENSITY
DEPTIH No. (pcf) (pci)
6" 1 33.2 111.6 83.8 94
6" 1 32.9 111.9 84.2 95
6" 1 33.5 113.1 84.7 95
6" 1 34.4 112.8 83.9 94
6" 1 35.1 112.8 83.5 94
6" 1 35.7 112.4 82.8 93
6" 1 33.9 112.9 84.3 95
6" 1 34.3 112.1 83.5 94
6" 1 32.7 112.9 85.1 96
6" 1 34.0 112.4 83.9 94
6" 1 33.5 111.3 83.4 94
6" 1 32.9 111.2 83.7 94
6" 1 33.3 111.6 83.7 94
6" 1 31.2 111.1 84.7 95
Finished: 7:30p11�
ring
Michael Cox, SET
Project Manager
DENSITY
max)
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
composition. appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7SS Page 4 of 4
one Engineering
Client: Transwestem Commercial Services
Mr. Ric Nelson
Transwestem Commercial Services
5001 Spring, Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods:
MID No.
TEST
NO
ASTM D -2922
ASTM D -3017
Dark Brown Clay
Building pad
1 Pad 1, 25' north,
corner, 2nd lift
Building pad
2 Pad 1, 25' north,
corner, 2nd lift
Building pad
3 Pad 1, 25' north,
corner, 2nd lift
Building pad
4 Pad 1, 75' north,
corner. 2nd lift
Description
Tannish Brown Silty Clay
TEST LOCATION
35' east from southwest
70' east from southwest
110' east from southwest
35' east from southwest
Gauge: Troxler 3430
Gauge Serial No: 33438
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pct
FIE] ,D DENSITY TESTS
1AUD
No.
6" 1
6" 1
6" 1
6" 1
PROBE
DEPTH
IN -PLACE DENSITY TESTING
Standard Counts
Moisture Density
Current: 582
Previous: 578
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane. Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
Report No.:
Project No.:
Date of Service:
Report Date:
34.4 112.2
32.4 110.0
35.6 111.3
34.1 111.7
278626
0712786
02/14/2007
03/19/2007
Current: 2685
Previous: 2676
Project Requirements
Moisture Density
27.0 89.0 Optimum +4 92 96
24.5 93.5 Optimum +4 92 96
MOISTURE WET DENSITY DRY DENSITY DENSITY
(Pet) (pcf) max)
83.5
83.1
82.1
83.3
94
93
92
94
LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
G7SS Page 1 of 3
Report No.: 278626
Project No.: 0712786
TEST
NO TEST LOCATION
Client: Transwestern Commercial Services
PROBE MID MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (Pcf) (Pcf) max)
Building pad
5 Pad 1, 75' north, 70' east from southwest 6" 1 34.1 110.1 82.1 92
corner, 2nd lift
Building pad
6 Pad 1, 75' north, 110' east from southwest 6" 1 33.4 112.3 84.2 95
corner, 2nd lift
Building pad
7 Pad 2, 25' south, 35' east from northwest 6" 1 35.0 113.0 83.7 94
corner, 2nd lift
Building pad
8 Pad 2, 25' south, 70' east from northwest 6" 1 33.5 109.2 81.8 92
corner, 2nd lift
Building pad
9 Pad 2, 25' south, 110' east from northwest 6" 1 35.7 111.3 82.0 9
corner, 2nd lift
Building pad
10 Pad 2, 75' south, 35' east from northwest 6" 1 34.1 110.5 82.4 93
corner, 2nd lift
Building pad
11 Pad 2, 75' south, 70' east from northwest 6" 1 34.0 110.3 82.3 9
corner, 2nd lift
Building pad
12 Pad 2. 75' south, 110' east from northwest 6" 1 35.5 112.2 82.8 93
corner, 2nd lift
Building pad
13 Pad 1, 25' north, 35' east from southwest 6" 1 35.4 114.0 84.2 95
corner. 3rd lift
Building pad
14 Pad 1. 25' north, 70' east from southwest 6" 1 38.0 114.1 82.7 93
corner, 3rd lift
Building pad
15 Pad 1, 25' north, 110' east from southwest 6" 1 35.7 114.5 84.4 95
corner, 3rd lift
Building pad
16 Pad 1, 75' south, 35' cast from northwest 6" 1 37.0 114.8 83.8 94
corner, 3rd lift
Building pad
17 Pad 1. 75' south, 70' east from northwest 6" 1 36.9 114.7 83.8 9
corner, 3rd lift
Building pad
18 Pad 1, 75' south, 110' east from northwest 6" l 37.9 114.7 83.2 93
corner, 3rd lift
Building pad
19 Pad 2, 25' north, 35' east from southwest 6" 1 37.4 114.6 83.4 94
corner, 3rd lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
17SS Page 2 of 3
Report No.: 278626
Project No.: 0712786
TEST PROBE M/D TIOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (Pei) max)
Building pad
20 Pad 2, 25' north. 70' east from southwest 6" 1 39.2 114.3 82.1 92
corner, 3rd lift
Building pad
21 Pad 2. 25' north. 110' east from southeast 6" 1 35.7 114.1 84.1 94
corner, 3rd lift
Building pad
22 Pad 2, 25' south, 35' east from northwest 6" 1 38.2 114.6 82.9 93
corner. 3rd Lift
Building pad
23 Pad 2, 25' south. 70' east from northwest 6" l 37.5 114.3 83.1 93
corner, 3rd lift
Building pad
24 Pad 2, 25' south, 110' east from northwest 6" 1 34.3 114.6 85.3 96
corner, 3rd lift
Technician: Nick Ciofani
Report Distribution:
(1) Transwestem Commercial Services
(1) City of Coppel l
(1) City of Coppell
(I) Constructors
Client: Transwestern Commercial Services
Test results on this report meet project specification.
Started: 7: l Sam Finished: 9:15am
(1) Murray Construction Co, Inc.
(1) Aztec Environmental
ichael Cox, SET
Project Manager
ti
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
,7SS Page 3 of 3
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring 'Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D -2922
ASTM D -3017
M./D No.
1 Dark Brown Clay
Description
2 Tannish Brown Silty Clay
TEST
NO
Building pad
1 Pad 1, 25' south,
corner, 8th lift
Building pad
2 Pad 1, 25' south,
corner, 8th lift
Building pad
3 Pad 1, 25' south,
corner, 8th lift
Building pad
4 Pad 1. 75' south,
corner. 8th lift
TEST LOCATION
35' east from northwest
70' east from northwest
110' east from northwest
35' east from northwest
Gauge: Troxler 3430
Gauge Serial No: 33438
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
IN -PLACE DENSITY TESTING
Previous: 582
Report No.:
Project No.:
Date of Service:
Report Date:
278713
0712786
02/15/2007
03/19/2007
Standard Counts
Moisture Density
Current: 578
Current: 2690
Previous: 2685
Project Requirements
Moisture Density
27.0 89.0 Minimum +4 92 96
24.5 93.5 Minimum +4 92 96
PROBE ADD MOISTURE WET DENSITY DRY DENSITY
DEPTH No. (pcf) (pcf)
6" 1 31.2 111.1
6" 1 32.9 111.2
6" 1 32.7 112.9
6" 1 33.9 112.9
84.7
83.7
85.1
84.3
DENSITY
max)
95
94
96
95
LLMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
17SS Page 1 of 5
Report No.: 278713
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcf) (pcf) max)
Building pad
5 Pad 1, 75' south. 70' east from northwest 6" 1 35.7 112.4 82.8 93
corner, 8th lift
Building pad
6 Pad 1.75' south, 110' east from northwest 6" 1 35.7 112.4 82.8 93
corner. 8th lift
Building pad
7 Pad 2, 25' north. 35' east from southwest 6" 1 35.1 112.8 83.5 94
corner, 8th lift
Building pad
8 Pad 2, 25' north, 70' east from southwest 6" 1 32.5 111.7 84.3 95
corner, 8th lift
Building pad
9 Pad 2, 25' north, 110' east from southwest 6" 1 35.3 111.2 82.2 92
corner, 8th lift
Building pad
10 Pad 2, 75' north, 35' east from southwest 6" 1 34.0 110.8 82.7 93
corner, 8th lift
Building pad
11 Pad 2, 75' north 70' east from southwest 6" 1 32.9 1 1 1.6 84.0 94
corner, 8th lift
Building pad
12 Pad 2, 75' north, 1 1 0' east from southwest 6" 1 33.0 112.9 84.9 95
corner, 8th Lift
Building pad
13 Pad 1, 25' south, 35' east from northwest 6" 1 35.7 111.0 81.8 92
corner, 9th lift
Building pad
14 Pad 1, 25' south, 70' east from northwest 6" 1 31.8 110.6 83.9 94
corner, 9th lift
Building pad
15 Pad 1, 25' south, 110' east from southwest 6" 1 34.0 112.6 84.0 94
corner, 9th lift
Building pad
16 Pad 1, 75' south, 35' east from northwest 6" 1 31.5 108.0 82.1 92
corner, 9th lift
Building pad
17 Pad 1. 75' south, 70' east from northwest 6" 1 33.7 113.1 84.6 95
corner, 9th lift
Building pad
18 Pad 1. 75' south, 110' east from northwest 6" 1 35.4 113.5 83.8 94
corner, 9th lift
Building pad
19 Pad 2. 25' north, 35' east from southwest 6" 1 36.3 112.7 82.7 93
corner. 9th lift
L11vIITAT1ONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7SS Page 2 of 5
Zeport No.: 278713
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE MID MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcf) (Per) max)
Building pad
20 Pad 2, 25' north. 70' east from southwest 6" 1 35.3 113.5 83.9 94
corner. 9th lift
Building pad
21 Pad 2, 25' north. 110' east from southwest 6" 1 35.7 113.6 83.7 94
corner, 9th lift
Building pad
22 Pad 2, 75' north, 35' east from southwest 6" 1 33.8 113.1 84.5 95
corner, 9th lift
Building pad
23 Pad 2, 75' north, 70' east from southwest 6" 1 36.5 113.0 82.8 93
corner, 9th lift
Building pad
24 Pad 2, 75' north. 110' east from southwest 6" 1 36.3 113.3 83.1 93
corner, 9th lift
Building pad
25 Pad 1, 25' south, 35' east from northwest 6" 1 37.9 114.7 83.2 93
corner, 10th lift
Building pad
26 Pad 1, 25' south, 70' east from northwest 6" 1 37.4 114.6 83.4 94
corner, 10th Lift
Building pad
27 Pad 1, 25' south, 110' east from northwest 6" 1 34.3 114.6 85.3 96
corner, 10th lift
Building pad
28 Pad 1, 75' south, 35' east from northwest 6" 1 35.7 114.1 84.1 94
corner, 10th lift
Building pad
29 Pad 1, 75' south, 70' east from northwest 6" 1 38.0 114.1 82.7 93
corner, 10th lift
Building pad
30 Pad 1. 75' south, 110' east from northwest 6" 1 37.0 114.8 83.8 94
corner, 10th lift
Building pad
31 Pad 2, 25' north, 35' east from southwest 6" 1 31.3 111.5 84.9 95
corner, 10th lift
Building pad
32 Pad 2, 25' north, 70' east from southwest 6" 1 34.5 111.8 83.1 93
corner, 1 Oth lift
Building pad
33 Pad 2. 25' north, 110' east from southwest 6" 1 33.7 111.1 83.1 93
corner, 10th lift
Building pad
34 Pad 2, 75' north, 35' east from southwest 6" 1 31.7 110.9 84.2 95
corner. loth lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing,. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
t7SS Page 3 of 5
ReportNo.: 278713
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE MiD MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcf) (pcf) max)
Building pad
35 Pad 2. 75' north. 70' east from southwest 6" 1 33.9 110.5 82.5 93
corner. 10th lift
Building pad
36 Pad 2, 75' north, 110' east from southwest 6" 1 35.3 112.2 82.9 93
corner, 10th lift
Building pad
37 Middle pad, 25' south, 40' east from 6" 1 31.1 111.0 84.7 95
northwest corner, subgrade
Building pad
38 Middle pad, 25' south, 75' east from 6" 1 34.8 110. 82.3 92
northwest corner, subgrade
Building pad
39 Middle pad, 25' south, 125' east from 6" 1 31.3 109.6 83.5 94
northwest corner, subgrade
Building pad
40 Middle pad, 25' south, 148' east from 6" 1 32.3 109.3 82.6 93
northwest corner, subgrade
Building pad
41 Middle pad, 80' south, 40' east from 6" 1 31.8 108.6 82.4 93
northwest corner, subgrade
Building pad
42 Middle pad, 80' south, 80' east from 6" 1 31.7 111.4 84.6 95
northwest corner, subgrade
Building pad
43 Middle pad, 80' south, 130' east from 6" 1 32.9 112.7 84.8 95
northwest corner, 1st lift
Building pad
44 Middle pad, 40' south, 60' east from 6" 1 35.1 112.3 83.1 93
northwest corner, 1st lift
Building pad
45 Middle pad, 40' south, 80' east from 6" 1 36.2 112.4 82.5 93
northwest corner, 1st lift
Building pad
46 Middle pad, 40' south, 120' east from 6" 1 31.5 108.5 82.5 93
northwest corner. 1st lift
Building pad
47 Middle pad, 30' north, 40' east from 6" 1 32.3 112.6 85.1 96
southwest corner, 1st lift
Building pad
48 Middle pad, 30' north, 80' east from 6" 1 35.7 112.8 83.1 93
southwest corner, 1st lift
Building pad
49 Middle pad, 30' north, 120' east from 6" 1 35.0 113.0 83.7 94
southwest corner, 1st lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
37SS Page 4 of 5
Report No.: 278713
Project No.: 0712786
TEST PROBE M/D MOISTURE 1A ET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcf) (pcf) max)
Building pad
50 Middle pad, 30' north, 160' east from 6" 1 34.5 112.6 83.7 94
southwest corner, 1st lift
Building pad
51 Middle pad, 85' north, 35' east from 6" 1 35.1 112.7 83.4 94
southwest corner, 2nd lift
Building pad
52 Middle pad, 85' north, 75' east from 6" 1 34.1 113.2 84.4 95
southwest corner, 2nd lift
Building pad
53 Middle pad, 85' north, 115' east from 6" 1 34.4 112.4 83.6 94
southwest corner, 2nd lift
Building pad
54 Middle pad, 85' north, 136' east from 6" 1 32.4 112.8 85.2 96
southwest corner, 2nd lift
Building pad
55 Middle pad, 75' north, 45' east from 6" 1 35.9 113.2 83.3 94
southwest corner, 2nd lift
Building pad
56 Middle pad, 75' north, 78' east from 6" 1 34.2 113.1 84.3 95
southwest corner, 2nd lift
Building pad
57 Middle pad, 75' north, 122' east from 6" 1 31.9 112.8 85.5 96
southwest corner, 2nd lift
Building pad
58 Middle pad, 75' north, 150' east from 6" 1 33.4 109.5 82.1 92
southwest corner, 2nd lift
Test results on this report meet project specification.
Technician Time:
Two trips: 7:O0am to 10:30am
2:30pm to 5:30pm
Client: Transwestem Commercial Services
Technician: Nick Ciofani Started: Finished:
Report Distribution:
(1) Transwestem Commercial Services (1) Murray Construction Co, Inc.
(1) City of Coppell (1) Aztec Environmental
(I) City of Coppell
(1) Constructors
Rone E
M chael Cox, SET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
i7SS Page 5 of 5
one Engineering
44
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D 2922
ASTM D 3017
M/D No.
TEST
NO
Dark Brown Clay
Description
Tannish Brown Silty Clay
TEST LOCATION
Fill
1 Building pad 2, northwest corner, 125'
south, 35' east, subgrade
Fill
2 Building pad 2, northwest corner, 125'
south, 70' east, subgrade
Fill
3 Building pad 2, northwest corner, 125'
south, 110' east. subgrade
Fill
4 Building pad 2, northwest corner. 175'
south, 35' east, subgrade
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum Project Requirements
Moisture Density pcf Moisture Density
FIELD DENSITY TESTS
PROBE M/D
DEPTH No.
6" 1
6" 1
6" 1
6" 1
IN -PLACE DENSITY TESTING
Standard Counts
Moisture Density
Current: 738
Previous: 742
Report No.:
Project No.:
Date of Service:
Report Date:
24.5 93.5 Minimum +4
27.0 89.0 Minimum +4
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
MOISTURE WET DENSITY DRY DENSITY DENSITY
(Pct) (Pei) max)
33.0 116.4
31.4 116.4
30.8 116.9
32.7 116.8
279639
0712786
02/23/2007
03/19/2007
Current: 2562
Previous: 2566
87.5
88.6
89.4
88.0
92 -96
92 -96
94
95
96
94
LIMITATIONS- The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 1 of 3
Report No.: 279639
Project No.: 0712786
Client: Transwestern Commercial Services
EMMENW MOM'
TEST PROBE M/D MOISTURE VET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (pct) max)
Fill
5 Building pad 2, northwest corner. 175' 6" 1 32.3 116.6 88.1 94
south, 70' east, subgrade
Fill
6 Building pad 2, northwest corner, 175' 6" 1 32.4 116.5 88.0 94
south. 110' east, subgrade
Fill
7 Building pad 2, northwest corner, 125' 6" 1 33.7 116.2 86.9 93
south. 35' east. l st lift
Fill
8 Building pad 2. northwest corner, 125' 6" 1 32.5 116.5 87.9 94
south, 70' east, l st lift
Fill
9 Building pad 2, northwest corner, 125' 6" 1 31.3 116.1 88.4 95
south, 110' east, 1st Lift
Fill
10 Building pad 2, northwest corner. 175' south 6" 1 31.6 116.6 88.6 95
35' east, 1st lift
Fill
11 Building pad 2, northwest corner. 175' 6" 1 32.1 117.3 88.8 95
south, 70' east, 1st lift
Fill
12 Building pad 2, northwest corner, 175' 6" l 31.5 116.9 88.9 95
south, 110' east, 1st lift
Fill
13 Building pad 2, northwest corner. 125' 6" 1 31.7 116.7 88.6 95
south, 35' east. 2nd lift
Fill
14 Building pad 2, northwest corner, 125' 6" 1 32.2 116.1 87.8 94
south, 70' east. 2nd lift
Fill
15 Building pad 2, northwest corner, 125' 6" 1 34.4 116.8 86.9 93
south. 110' east, 2nd lift
Fill
16 Building pad 2, northwest corner, 175' 6" 1 33.2 116.7 87.6 94
south, 35' east, 2nd lift
Fill
17 Building pad 2, northwest corner, 175' 6" 1 33.7 116.7 87.3 93
south, 70' east, 2nd lift
Fill
18 Building pad 2, northwest corner, 175' 6" 1 32.4 116.8 88.2 94
south, 110' east, 2nd lift
Fill
19 Building pad 2. northwest corner, 125' 6" 2 33.2 111.2 83.5 94
south, 35' east, 3rd lift
LIMIT.ATIONS. The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 2 of 3
Keport 'No.: 279639
Project No.: 0712786
TEST
NO TEST LOCATION
Fill
20 Building pad 2, northwest corner, 125'
south. 70' east, 3rd lift
Fill
21 Building pad 2, northwest corner, 125'
south, 110' east, 3rd lift
Fill
22 Building pad 2, northwest corner. 175'
south, 35' east, 3rd lift
Fill
23 Building pad 2, northwest corner, 175'
south, 70' east, 3rd lift
Fill
24 Building pad 2, northwest corner, 175'
south. 110' east, 3rd lift
Technician: Joe Jernigan
Report Distribution:
(1) Transwestern Commercial Services
(1) City of Coppell
(1) City of Coppell
(1) Constructors
Client: Transwestern Commercial Services
Test results on this report meet project specification.
Started: 7:15am Finished: 11:00
(1) Murray Construction Co, Inc
(I) Aztec Environmental
Ro
Michael Cox, SET
Project Manager
WffEEI
PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (Pet) (pct) max)
6" 2 31.8 111.9 84.9 95
6" 2 35.2 111.0 82.1 92
6" 2 32.2 111.8 84.6 95
6" 2 32.2 110.9 83.9 94
6" 2 32.7 111.5 84.0 94
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 3 of 3
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
CONTRACTOR: Constructors Associates
Test Methods:
M/D No.
ASTM D -2922
ASTM D -3017
1 Dark Brown Clay
Description
2 Tannish Brown Silty Clay
TEST
NO
TEST LOCATION
Fill
1 Building pad 2, northwest corner. 25' south,
35' east, 7th lift
Fill
2 Building pad 2, northwest corner. 25' south,
70' east. 7th lift
Fill
3 Building pad 2, northwest corner, 25' south,
110' east, 7th lift
Fill
4 Building pad 2, northwest corner, 75' south,
35' east, 7th lift
PROJECT DATA
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TF,STS
IN -PLACE DENSITY TESTING
Standard Counts
Moisture Density
Current: 745
Previous: 749
Report No.:
Project No.:
Date of Service:
Report Date:
6" 2 32.5 116.5
6" 2 33.7 116.2
6" 2 32.4 116.5
6" 2 32.3 116.6
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, Tx 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
280093
0712786
02/28/2007
03/19/2007
Current: 2663
Previous: 2676
Project Requirements
Moisture Density
27.0 89.0 Minimum +4 92 -96
24.5 93.5 Minimum +4 92 -96
PROBE M/D MOISTURE WET DENSITY DRY DENSITY
DEPTH No. (pcl) (pcf)
87.9
86.9
88.0
88.1
DENSITY
max)
94
93
94
94
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing we assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rope Engineering Services, Ltd.
FM Page 1 of 3
Report No.: 28009;
Project No.: 0712786
TEST
NO
TEST LOCATION
Client: Transwestern Commercial Services
PROBE AIID MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (Pcf) (Pc1) max)
Fill
5 Building pad 2 northwest corner, 75' south, 6" 2 32.7 116.8 88.0 94
70' east, 7th lift
Fill
6 Building pad 2, northwest corner. 75' south, 6" 2 30.8 116.9 89.4 96
110' east, 7th lift
Fill
7 Building pad 2, northwest corner, 125' 6" 2 31.4 116.4 88.6 95
south, 35' east, 7th lift
Fill
8 Building pad 2, northwest corner, 125' 6" 2 33.0 116.4 87.5 94
south, 70' east, 7th lift
Fill
9 Building pad 2, northwest corner, 125' 6" 1 31.3 110.8 84.4 95
south, 110' east. 7th lift
Fill
10 Building pad 2, northwest corner, 175' 6" 1 32.9 111.0 83.5 94
south, 35' east, 7th lift
Fill
11 Building pad 2. northwest corner, 175' 6" 1 32.4 111.5 84.2 95
south, 70' east, 7th lift
Fill
12 Building pad 2, northwest corner, 175' 6" 1 32.8 111.4 83.9 94
south, 110' east, 7th lift
Fill
13 Building pad 2, southwest corner, 25' north, 6" 1 32.6 111.9 84.4 95
35' east, 7th lift
Fill
14 Building pad 2, southwest corner, 25' north, 6" 1 33.4 111.5 83.6 94
70' east, 7th lift
Fill
15 Building pad 2, southwest corner, 25' north, 6" 1 31.9 111.6 84.6 95
110' east, 7th lift
Fill
16 Building pad 2, southwest corner, 75' north, 6" 1 31.8 111.1 84.3 95
35' east, 7th Lift
Fill
17 Building pad 2, southwest corner, 75' north, 6" 1 32.2 111.7 84.5 95
70' east, 7th lift
Fill
18 Building pad 2, southwest corner, 75' north, 6" 1 31.7 112.1 85.1 96
110' east, 7th lift
Fill
19 Building pad 2, southwest corner, 125' 6" 2 30.2 111.7 85.8 92
north, 35' east, 7th lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the ssritten approval of Rone Engineering Services, Ltd.
ATM Page 2 of 3
Report No.: 280093
Project No.: 0712 786
TEST
NO TEST LOCATION
Fill
20 Building pad 2, southwest corner,
north. 70' east. 7th lift
Fill
21 Building pad 2, southwest corner,
north, 110' east. 7th lift
Fill
22 Building pad 2, southwest corner,
north. 35' east, 7th lift
Fill
23 Building pad 2, southwest corner,
north. 70' east, 7th lift
Fill
24 Building pad 2, southwest corner,
north. 110' east. 7th lift
Technician: Joe Jernigan
Report Distribution:
(1) Transwestem Commercial Services
(1) City ofCoppell
(1) City ofCoppell
(1) Constructors
Client: Transwestern Commercial Services
125'
125'
175'
175'
17
Test results on this report meet project specification.
Started: 12:15p
(1) Murray Construction Co, Inc.
(1) Aztec Environmental
M/D
No.
6" 1
6" 1
6" 1
6" 2
6" 2
PROBE;
DEPTH
Finished: 3 :00pm
MOISTURE WET DENSITY DRY DENSITY DENSITY
(Pcl) (pcf) max)
33.0 111.3
31.6 110.9
32.4 111.2
30.2 112.2
30.4 112.0
Rone
ichael Cox, SET
Project Manager
83.7 94
84.3 95
84.0 94
86.2 92
85.9 92
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 3 of 3
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D -2922
ASTM D -3017
M/D No.
1 Brown Clayey Sand
TEST
NO
Select fill
1 Building pad 1,
35' east, grade
Select fill
2 Building pad 1,
70' east, grade
Select fill
3 Building pad 1,
110' east, grade
Select fill
4 Building pad 1,
35' east, grade
Select fill
5 Building pad 1,
70' east, grade
Description
TEST LOCATION
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
southwest corner, 25' north,
southwest corner, 25' north.
southwest corner, 25' north.
southwest corner, 75' north,
southwest corner, 75' north,
MOISTURE DENSITY RELATIONS
Maximum Project Requirements
Moisture Density pcf Moisture Density
11.0
FIELD DENSITY TESTS
PROBE M/D
DEPTH No.
6" 1
6" 1
6" 1
6" 1
6" 1
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
IN -PLACE DENSITY TESTING
118.0
Report No.:
Project No.:
Date of Service:
Report Date:
279663
0712786
02/23/2007
03/19/2007
Standard Counts
Moisture Density
Current: 738
Previous: 742
-2/ +2
Current: 2562
Previous: 2566
MOISTURE WET DENSITY DRY DENSITY DENSITY
(Pct) (Pct) max)
10.7 129.9 117.3
11.8 128.4 114.8
10.9 129.3 116.6
11.8 128.7 115.1
11.5 128.6 115.3
95 min
99
97
99
98
98
LLMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shad not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 1 of 3
Report No.: 279663
Project No.: 0712786
Client: Transwestern Commercial Services
TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (pcf) max)
Select fill
6 Building pad 1. southwest corner, 75' north. 6" 1 11.4 128.6 115.4 98
110' east grade
Select fill
7 Building pad 1, southwest corner, 1 6" 1 11.5 129.6 116.2 98
north, 35' east, grade
Select fill
8 Building pad 1, southwest corner, 125' 6" 1 11.8 129.2 115.6 98
north, 70' east, grade
Select fill
9 Building pad 1, southwest corner, 125' 6" 1 11.6 128.2 114.9 97
north, 110' east. grade
Select fill
10 Building pad 1, southwest corner, 175' 6" 1 10.4 129.0 116.8 99
north, 35' east, grade
Select fill
11 Building pad 1, southwest corner, 175' 6" 1 12.8 129.0 114.4 97
north, 70' east, grade
Select fill
12 Building pad 1, southwest corner, 175' 6" 1 12.2 128.5 114.5 97
north, 110' east. grade
Select fill
13 Building pad 1, northwest corner, 25' south. 6" 1 11.6 128.8 115.4 98
35' east, grade
Select fill
14 Building pad 1, northwest corner, 25' south. 6" 1 10.7 129.5 117.0 99
70' east, grade
Select fill
15 Building pad 1, northwest corner, 25' south. 6" 1 11.4 129.3 116.1 98
110' east. grade
Select fill
16 Building pad 1, northwest corner, 75' south, 6" 1 11.6 129.7 116.2 98
35' east, grade
Select fill
17 Building pad 1, northwest corner, 75' south. 6" 1 11.6 128.8 115.4 98
70' east, grade
Select fill
18 Building pad 1, northwest corner, 75' south, 6" 1 10.7 129.5 117.0 99
110' east, grade
Select fill
19 Building pad 1, northwest corner, 125' 6" 1 11.4 129.3 116.1 98
south, 35' east, grade
Select fill
20 Building pad 1, northwest corner, 125' 6" 1 11.6 129.7 116.2 98
south. 70' east. grade
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided be persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
17T>\I Page 2 of 3
Report No.: 279663
Project No.: 0712786
Technician: Joe Jernigan
Report Distribution:
(1) Transwestem Commercial Services
(1) City of Coppell
(1) City of Coppell
(l) Constructors
Client: Transwestern Commercial Services
Test results on this report meet project specification.
Started: 1:15pm Finished: 3:15psn
(1) Murray Construction Co, Inc.
(1) Aztec Environmental
ichael Cox, SET
Project Manager
VMMEM
TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (pcf) W. max)
Select fill
21 Building pad 1. northwest corner, 125' 6" 1 10.7 129.9 117.3 99
south. 110' east. grade
Select fill
22 Building pad 1. northwest corner, 175' 6" 1 12.2 129.5 115.4 98
south. 35' east, grade
Select fill
23 Building pad 1, northwest corner, 175' 6" 1 10.8 128.9 116.3 99
south. 70' east, grade
Select fill
24 Building pad 1, northwest corner, 175' 6" 1 11.6 129.3 115.9 98
south. 1 10' east. grade
LIMITATIONS. The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 3 of 3
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
CONTRACTOR: Constructors Associates
Test Methods:
1
TEST
NO
ASTM D -2922
ASTM D -30]7
M/D No. Description
Brown Clayey Sand
TEST LOCATION
Select fill
1 Building pad 1. southwest corner,
35' east, 1st lift
Select fill
2 Building pad 1, southwest corner,
70' east, 1st lift
Select fill
3 Building pad 1, southwest corner,
110' east, 1st lift
Select fill
4 Building pad 1, southwest corner,
35' east, 1st lift
Select fill
5 Building pad 1, southwest corner,
70' east, 1st lift
PROJECT DATA
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
PROBE A'UD
DEPTH No.
25' north, 6" 1
25'north, 6" 1
25' north. 6" 1
75' north, 6" 1
75' north, 6" 1
IN -PLACE DENSITY TESTING
Standard Counts
Moisture Density
Current: 742
Previous: 745
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
Report No.:
Project No.:
Date of Service:
Report Date:
279488
0712786
02/22/2007
03/19/2007
Current: 2596
Previous: 2550
Project Requirements
Moisture Density
11.0 118.0 -2/ +2 95 min
MOISTURE WET DENSITY DRY DENSITY
(Pci) (pcf)
11.9 128.4 114.7
11.8 129.2 115.6
11.5 129.6 116.2
11.4 128.6 115.4
11.5 128.6 115.3
DENSITY
max)
97
98
98
98
98
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
17TM Page 1 of 3
Report No.: 279488
Project No.: 0712786
Client: Transwestern Commercial Services
SI
TEST PROBE MID MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pct) (pcf) max)
Select fill
6 Building pad 1, southwest corner, 75' north, 6" 1 11.8 128.7 115.1 98
110' east, 1st lift
Select fill
7 Building pad 1, northwest corner, 25' south, 6" 1 10.9 129.3 116.6 99
35' east, 1st lift
Select fill
8 Building pad 1. northwest corner, 25' south, 6" 1 11.8 128.4 114.8 97
70' east, 1st lift
Select fill
9 Building pad 1, northwest corner, 25' south, 6" 1 11.2 128.8 115.8 98
110' east, 1st lift
Select fill
10 Building pad 1, northwest corner, 75' south, 6" 1 12.7 128.4 113.9 97
35' east, 1st lift
Select fill
11 Building pad 1. northwest corner, 75' south, 6" 1 11.4 128.4 115.3 98
70' east. 1st Lift
Select fill
12 Building pad 1. northwest corner, 75' south, 6" 1 10.9 129.2 116.5 99
110' east, 1st lift
Select fill
13 Building pad 1, southwest corner, 125' 6" 1 10.4 129.0 116.8 99
north, 35' east. l st lift
Select fill
14 Building pad 1, southwest corner, 125' 6" 1 12.8 129.0 114.4 97
north, 70' east, l st lift
Select fill
15 Building pad 1, southwest corner, 125' 6" 1 12.2 128.5 114.5 97
north, 110' east, 1st lift
Select fill
16 Building pad 1, southwest corner, 175' 6" 1 11.6 128.2 114.9 97
north, 35' east, 1 st lift
Select fill
17 Building pad 1, southwest corner, 175' 6" 1 11.6 129.3 115.9 98
north, 70' east, 1st lift
Select fill
18 Building pad 1, southwest corner. 175' 6" 1 10.8 128.9 116.3 99
north, 110' east, 1st lift
Select fill
19 Building pad 1, northwest corner. 125' 6" 1 12.2 129.5 115.4 98
south, 35' east, 1 st lift
Select fill
20 Building pad 1, northwest corner. 125' 6" 1 10.7 129.9 117.3 99
south, 70' east, 1st lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 2 of 3
Report No.: 279488
Project No.: 0712786
TEST
NO
2 1
77
23
24
Technician: Joe Jernigan
Report Distribution:
(1) Transwestern Commercial Services
(1) City of Coppell
(1) City of Coppell
(1) Constructors
TEST LOCATION
Select fill
Building pad 1, northwest corner. 125'
south, 110' east. 1st lift
Select fill
Building pad 1. northwest corner, 175'
south. 35' east, 1st lift
Select fill
Building pad 1, northwest corner, 175'
south, 70' east, 1st lift
Select fill
Building pad 1, northwest corner, 175'
south, 110' east, 1st lift
Client: Transwestern Commercial Services
PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (pci) (pct) max)
6" 1
6" 1
6" 1
6" 1
11.6 129.7
11.4 129.3
10.7 129.5
11.6 128.8
Test results on this report meet project specification.
Started: 7:15am
(I) Murray Construction Co, Inc.
(1) Aztec Environmental
Finished: 10:45a
R
116.2
116.1
117.0
115.4
Michael Cox, SET
Project Manager
98
98
99
98
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 3 of 3
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestem Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D 2922
ASTM D 3017
M/D No.
Description
1 Tannish Brown Silty Clay
TEST
NO
TEST LOCATION
Fill
1 Building pad 2, northwest corner, 125'
south, 35' east, 1st lift
Fill
2 Building pad 2, northwest corner, 125'
south, 70' east, 1st lift
Fill
3 Building pad 2, northwest corner, 125'
south, 110' east. 1 st lift
Fill
4 Building pad 2, northwest corner, 175'
south, 35' east, 1st lift
Fill
5 Building pad 2, northwest corner, 175'
south, 70' east, 1st lift
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
FIELD DENSITY TESTS
IN -PLACE DENSITY TESTING
Standard Counts
Moisture Density
Current: 741
Previous: 738
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
Report No.:
Project No.:
Date of Service:
Report Date:
279950
0712786
02/27/2007
03/19/2007
Current: 2565
Previous: 2567
Project Requirements
Moisture Density
24.5 93.5 Minimum +4 92 -96
PROBE M/D MOISTURE WET DENSITY DRY DENSITY
DEPTH No. (pcf) (pcf)
6" 1 33.0 116.4 87.5
6" 1 31.4 116.4 88.6
6" 1 30.8 116.9 89.4
6" 1 32.7 116.8 88.0
6" 1 32.3 116.6 88.1
DENSITY
max)
94
95
96
94
94
LL IITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality/
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 1 of 2
Report No.: 279950
Project No.: 0712786
Client: Transwestern Commercial Services
11 ..,.11.,
TEST PROBE MUD MOISTURE V, ET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPT No. (pct) (pct) max)
Fill
6 Building pad 2, northwest corner, 175' 6" 1 32.4 116.5 88.0 94
south, 110' east, 1st lift
Fill
7 Building pad 2, northwest corner, 125' 6" 1 33.7 116.2 86.9 93
south. 35' east, 2nd lift
Fill
8 Building pad 2, northwest corner. 125' 6" 1 32.5 116.5 87.9 94
south, 70' east, 2nd lift
Fill
9 Building pad 2, northwest corner, 125' 6" 1 31.3 116.1 88.4 95
south, 110' east, 2nd lift
Fill
10 Building pad 2, northwest corner, 175' 6" 1 31.6 116.6 88.6 95
south, 35' east, 2nd lift
Fill
11 Building pad 2, northwest corner, 175' 6" 1 32.4 116.8 88.2 94
south, 70' east, 2nd lift
Fill
12 Building pad 2, northwest corner, 175' 6" 1 33.7 116.7 87.3 93
south, 110' east. 2nd lift
Test results on this report meet project specification.
Technician: Joe Jernigan
Report Distribution:
(1) Transwestern Commercial Services
(1) City of Coppell
(I) City of Coppell
(1) Constructors
Started: 7:30am Finished: 9:45a
(1) Murray Construction Co, Inc.
(1) .Aztec Environmental Michael Cox, SET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
�7TM Page 2 of 2
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Test Methods: ASTM D 2922
ASTM D 3017
Mill No.
1 Dark Brown Clay
TEST
NO
Description
TEST LOCATION
Fill
1 Building pad 2, northwest corner, 125'
south, 35' east, 3rd lift
Fill
2 Building pad 2, northwest corner, 125'
south, 70' east, 3rd lift
Fill
3 Building pad 2, northwest corner, 125'
south, 110' east. 3rd lift
Fill
4 Building pad 2, northwest corner, 175'
south, 35' east, 3rd lift
Fill
5 Building pad 2, northwest corner, 175'
south, 70' east, 3rd lift
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
Previous: 738
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
IN -PLACE DENSITY TESTING
Report No.:
Project No.:
Date of Service:
Report Date:
Standard Counts
Moisture Density
Current: 741
27.0 89.0 Minimum +4 92 -96
PROBE M/D MOISTURE WET DENSITY DRY DENSITY
DEPTH No. (pcf) (pci)
6" 1 32.2 1 1 1.2
6" 1 31.4 111.4
6" 1 31.5 110.7
6" 1 33.3 111.3
6" 1 31.8 111.2
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
279964
0712786
02/27/2007
03/19/2007
Current: 2565
Previous: 2567
Project Requirements
Moisture Density
DENSITY
max)
84.1 94
84.8 95
84.2 95
83.5 94
84.4 95
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.l or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
i7TM Page 1 of 2
Report No.: 279964
Project No.: 0712 786
south, 70' east, 4th lift
Fill
12 Building pad 2, northwest corner, 175'
south, 110' east, 4th lift
Technician: Joe Jernigan
Report Distribution:
(1) Transwestem Commercial Services
(1) City of Coppell
(1) City of Coppel I
(1) Constructors
Client: Transwestem Commercial Services
TEST PROBF, M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO TEST LOCATION DEPTH No. (pcl) (pcf) max)
Fill
6 Building pad 2, northwest corner, 175' 6" 1 31.7 110.6 84.0 94
south, 1 10' east. 3rd lift
Fill
7 Building pad 2, northwest corner, 125' 6" 1 31.8 111.9 84.9 95
south, 35' east, 4th lift
Fill
8 Building pad 2, northwest corner, 125' 6" 1 32.2 111.8 84.6 95
south, 70' east, 4th lift
Fill
9 Building pad 2, northwest corner, 125' 6" 1 33.0 111.3 83.7 94
south, 110' east, 4th lift
Fill
10 Building pad 2, northwest corner, 175' 6" 1 32.2 110.9 83.9 94
south, 35' east, 4th lift.
Fill
11 Building pad 2, northwest corner, 175' 6" 1 31.7 111.8 84.9 95
6" 1 31.9 111.1 84.2 95
Test results on this report meet project specification.
Started: 10:30a Finished: 12:45p7
(1) Murray Construction Co, Inc_
(1) Aztec Environmental
Ro je ig
Michael Cox, SET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject natter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
I7TM Page 2 of 2
one Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
CONTRACTOR: Constructors Associates
Test Methods: ASTM D 2922
M/D No. Description
1 Tannish Brown Silty Clay
2 Dark Brown Clay
TEST
NO
ASTM D 3017
TEST LOCATION
Fill
1 Building pad 2, northwest corner, 125'
south, 35' east, 5th lift
Fill
2 Building pad 2, northwest corner, 125'
south. 70' east. 5th lift
Fill
3 Building pad 2, northwest corner, 125'
south. 1 10' east, 5th lift
Fill
4 Building pad 2, northwest corner, 175'
south. 35' east, 5th lift
PROJECT DATA
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
Current: 741
Previous: 738
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
IN -PLACE DENSITY TESTING
Report No.:
Project No.:
Date of Service:
Report Date:
279976
0712786
02/27/2007
03/19/2007
Standard Counts
Moisture Density
Current: 2565
Previous: 2567
Project Requirements
Moisture Density
24.5 93.5 Minimum +4 92 -96
27.0 89.0 Minimum +4 92 -96
PROBE M/D MOISTURE WET DENSITY DRY DENSITY
DEPTH No. (pci) (pcf)
6" 1 30.4 112.0
6" 1 30.2 111.7
6" 1 30.4 111.9
6" 1 31.3 116.1
85.9
85.8
85.8
88.4
DENSITY
max)
92
92
92
95
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject natter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7T1s1 Page 1 of 2
Report No.: 279976
Project No.: 0712786
TEST
NO
TEST LOCATION
Client: Transwestern Commercial Services
NOLOt
PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (pct) (pct) max)
Fill
5 Building pad 2. northwest corner_ 175' 6" 1 31.6 116.6 88.6 95
south. 70' east. 5th lift
Fill
6 Building pad 2, northwest corner, 175'
south. 110' east, 5th lift
Fill
7 Building pad 2, northwest corner. 125'
south, 35' east, 6th lift
Fill
8 Building pad 2, northwest corner, 125'
south, 70' east, 6th lift
Fill
9 Building pad 2, northwest corner, 125'
south, 110' east. 6th lift
Fill
10 Building pad 2, northwest corner. 175'
south, 35' east, 6th lift
Fill
11 Building pad 2, northwest corner. 175'
south, 70' east. 6th lift
Fill
12 Building pad 2, northwest corner, 175'
south, 110' east. 6th lift
Test results on this report meet project specification.
Technician: Joe Jernigan
Report Distribution:
(1) Transwestern Commercial Services
(1) City of Coppell
(1) City of Coppell
(11 Constructors
(1) Murray Construction Co, Inc
(I) Aztec Environmental
6" 2 33.2 111.2 83.5 94
6" 1 33.0 116.4 87.5 94
6" 1 31.4 116.4 88.6 95
6" 1 30.8 116.9 89.4 96
6" 1 32.7 116.8 88.0 94
6" 1 32.3 116.6 88.1 94
6" 1 32.4 116.5 88.0 94
Started: 3 l 5pm Finished: 5:OOpm
Rone
ichael Cox, SET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
I;TM
Page 2 of 2
Rone Engineering
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density Test in accordance with ASTM Standards.
CONTRACTOR: Constructors Associates
Test Methods: ASTM D 2922
ASTM D 3017
M/D No. Description
1 Dark Brown Clay
2 Tannish Brown Silty Clay
TEST
NO
TEST LOCATION
Fill
1 Building pad 2, northwest corner, 125'
south, 35' east, 5th Lift
Fill
2 Building pad 2, northwest corner, 125'
south. 70' east. 5th lift
Fill
3 Building pad 2. northwest comer. 125'
south, 110' east. 5th lift
Fill
4 Building pad 2, northwest corner, 175'
south, 35' east, subgrade
PROJECT DATA
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
IN -PLACE DENSITY TESTING
Current: 741
Previous: 738
Report No.:
Project No.:
Date of Service:
Report Date:
27.0 89.0 Minimum +4 92 -96
24.5 93.5 Minimum +4 92 -96
PROBE M/D MOISTURE WET DENSITY DRY DENSITY
DEPTH No. (pct) (pcf)
6" 1 32.8 111.4
6" 1 32.4 111.5
6" 1 32.9 111.0
6" 2 30.4 111.9
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
279857
0712786
02/26/2007
03/19/2007
Standard Counts
Moisture Density
Current: 2563
Previous: 2566
Project Requirements
Moisture Density
DENSITY
max)
83.9 94
84.2 95
83.5 94
85.8 92
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
17TM Page 1 of 2
Report No.: 279857
Project No.: 0712786
TEST
NO
Technician: Joe Jernigan
Report Distribution:
(1) Transwestern Commercial Services
(1) City of Coppell
(1) City ofCoppell
(1) Constructors
TEST LOCATION
Client: Transwestern Commercial Services
PROBE
DEPTH
MID
No.
Fill
5 Building pad 2. northwest corner, 175' 6" 2 30.4
south, 70' east, subgrade
Fill
6 Building pad 2, northwest corner. 175' 6" 2 30.2
south, 110' east. subgrade
Test results on this report meet project specification.
Started: 1:30pm Finished: 3:45pm
MOISTURE WET DENSITY DRY DENSITY DENSITY
(Pci) (Pc0 max)
112.0 85.9 92
111.7 85.8 92
Rone-
(I) Murray Construction Co, Inc.
(I) Aztec Environmental Michael Cox, SET
Project Manager
MinESSW 111
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not he reproduced except in full without the written approval of Rone Engineering Services, Ltd.
7TM Page 2 of 2
one Engineering
Test Methods:
MJD No.
1 Dark Brown Clay
TEST
NO
ASTM D -2922
ASTM D -3017
Client: Transwestern Commercial Services
Mr. Ric Nelson
Transwestern Commercial Services
5001 Spring Valley Rd., Ste 600W
Dallas TX 75244
Project: Gateway Business Center
Coppell, Texas
Services: Perform In -Place Density fest in accordance with ASTM Standards.
PROJECT DATA
CONTRACTOR: Constructors Associates
Description
2 Tannish Brown Silty Clay
TEST LOCATION
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
Fill
1 Building pad 2, northwest corner, 75' south, 6"
35' east, 4th lift
Fill
2 Building pad 2, northwest corner, 75' south, 6"
70' east. 4th lift
Fill
3 Building pad 2, northwest corner, 75' south, 6"
110' east. 4th lift
Fill
4 Building pad 2, northwest corner, 125' 6"
south, 35' east, 4th lift
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
PROBE
DEPTH
Current: 741
Previous: 738
8908 Ambassador Row, Dallas, TX 75247
7701 W. Little York, Suite 600, Houston, TX 77040
4221 Freidrich Lane, Suite 195, Austin, TX 78744
Corporate Phone: (817) 284 -1318
IN -PLACE DENSITY TESTING
Report No.:
Project No.:
Date of Service:
Report Date:
279806
0712786
02/26/2007
03/19/2007
Standard Counts
Moisture Density
Current: 2563
Previous: 2566
Project Requirements
Moisture Density
27.0 89.0 Minimum +4 92 -96
24.5 93.5 Minimum +4 92 -96
M/D MOISTURE WET DENSITY DRY DENSITY
No. (pcf) (pcf)
1
31.8 111.9
35.2 111.0
32.2 111.8
32.2 110.9
84.9
82.1
84.6
83.9
DENSITY
max)
95
92
95
94
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports ai
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
D7TM Page 1 of 2
Report No.: 7798(16
Project No.: 0712786
TEST
NO
PROBE MID MOISTURE WET DENSITY DRY DENSITY DENSITY
DEPTH No. (pcf) (pct) max)
TEST LOCATION
Technician: Joe Jernigan
Report Distribution:
(I) Transwestern Commercial Services
(1) City of Coppell
(1) City of Coppell
(1) Constructors
Client: Transwestern Commercial Services
Fill
5 Building pad 2, northwest corner, 125' 6" 1 32.7 111.5 84.0 94
south, 70' east, 4th lift
Fill
6 Building pad 2, northwest corner, 125' 6" 1 31.6 110.9 84.3 95
south, 1 1 0' east. 4th lift
Test results on this report meet project specification.
Started: 7 :30am Finished: 9:30am�
(1) Murray Construction Co. Inc.
(1) Aztec Environmental
Rone
Michael Cox, SET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
1?TM Page 2 of 2