Gateway BP(3.1)-LR070315~~~ ~,_ r~~~~~f~ 8908 Ambassador Row, Dallas, T~ 7247 7701 W. Little York, Suite 600, Houston, TX 77040 4221 Freidrich Lane, Suite 195, Austin, TX 78744 Corporate Phone: (817) 284-1318 IN-PLACE DENSITY TESTING Client: Transwestern Commercial Services Report No.: 278546 Mr. Ric Nelson Project No.: 0712786 Transwestern Commercial Services Date of Service• 02/13/2007 5001 Spring Valley Rd., Ste 600W Report Date: 03/15/2007 Dallas TX 75244 Project: Gateway Business Center Coppell, Texas Services: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA CONTR4CTOR: Constructors & .Associates Standard Counts Test Methods: ~ ~ ASTM D-_9~2 Gauge: Troxler 3430 Moisture Density .ASTM D-3017 Gauge Serial No: 35518 Current: 745 Current: 2567 Test'Vlode: DT Previous: 740 Previous: 2562 MOISTURE DENSITY RELATIONS Maximum Project Requirements DI/D No, Description Moisture % Density pcf Moisture Density 1 Tannish Brown Silty Clay 24.5 93.5 Minimum +4 92-96 ~ Dark Brown Clay 27.0 89.0 Minimum +4 92-96 TEST NO TEST LOCATION' PROBE DEPTH ]1/D No. MOISTURE (%) WET DENSITY DRY DENSITY (pci) (pct DENSITY (% max) Fill 1 Building pad 1, 25' south, 35' east from 6" 2 33.0 1 ll3 83.7 94 northwest corner, 10th lift Fill 2 Building pad 1, 25' south, 70' east from 6" 2 32.2 110.9 83.9 94 northwest corner, 10th lift Fill 3 Building pad 1, 25' south, 110' east from 6" 2 3l .7 110.6 84.0 94 northwest corner, 10th lift Fill 4 Building pad 1, 75' south, 35' east from 6" 2 31.8 1 l 12 84.4 95 northwest corner, 10th lift LIMI'T,ATTO?~S~ The test results presented herein were prepared haled upon the specific samples provided for testing. We assume no responsibility for vaziation in quality (c;omposition. appearance, etc.) or any other feature of similar subject matter provided b.' persons or conditions over evhich we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineenng Services, Ltd. i,-TM Page 1 of 3 ~zepr,,rt'~o '%b~~'6 t'roject No.: U7L786 Client: Transti~~estern Commercia l Services q4 a FEST PROBE bI/D ,lIOISTURE w'ET DENSITY DRY DENSITY DENSITY '~~O TEST LOCATION DEPTH No. (°iu) (pct) (pct (% max) Fiil 5 Building pad 1, 75' south, 70' east from 6" 2 33.3 111.3 83.5 94 northwest corner, 10th lift Fill 6 Building pad 1, 75' south, 110' east from 6" 2 31.5 110.7 84.2 95 northwest corner, 10th lift Fill 7 Building pad 1, 125' north, 35' east from 6" 1 33.7 1 I6.2 86.9 93 southwest corner, subgrade Fill 8 Building pad 1, 125' north, 70' east from 6" 1 32.5 116.5 87.9 94 southwest corner, subgrade Fi11 9 Building pad 1, 125' north, 110' east from 6" 1 31.3 116.1 88.4 95 southwest corner, subgrade Fill 10 Building pad 1, 125' north, 35' east from 6" 1 31.6 116.6 88.6 95 southwest corner, 1st lift Fill 11 Building pad L 125' north, 70' east from 6" l 32.1 l 17.3 88.8 95 southwest corner, 1st lift Fill 1 Z Building pad 1. 12S north, 110' east from 6" 1 31.5 116.9 88.9 95 southwest corner, 1st lift Fi11 13 Building pad 1, 175' north, 35' east from 6" 1 31.7 116.7 88.6 95 southwest corner, 1st lift Fill 14 Building pad 1, 17S north, 70' east from 6" 1 32.2 116.1 87.8 94 southwest corner, 1st lift Fill 15 Building pad 1, ] 75' north, 110' east from 6" 1 34.4 116.8 86.9 93 southwest corner_ 1st lift Fili 16 Building pad 1, 175' south, 35' east from 6" l 33.2 116.7 87.6 94 northwest corner, subgrade Fill 17 Building pad 1. 175' south, 70' east from 6" 1 33.7 116.7 87.3 93 northwest corner, subgrade Fill 18 Building pad 1, 175' south, 110' east from 6" 1 32.4 116.8 88.2 94 northwest corner, subgrade Fill 19 Building pad 1, I25` south, 35' east from 6" 2 31.4 111.4 84.8 95 northwest corner, 1st lift LIIvIPf.ATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.j or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. ''T-~ Page 2 of 3 ` &eport No . ? b~-tt Project PTO.: 071??P,6 Client: Transwestern Commercial Sen~ices ,.,.. ,~ ~.f_ ~~ f "PEST NROBE M/D MOISTURE y~'ET DENSITY DRY DENSITY DENSITY 'i0 TEST LOCATION DEPTft No. (%) (pcf) (pct) (% max) Fill ~0 Building pad 1, 125' south, 70' east from 6" 2 32.2 111.2 84.1 94 north~~est corner. 1 st lift Fill 21 Building pad 1, 125' south, 110' east from 6" 2 31.9 1 l 1.1 842 95 northwest corner, 1st lift Fill 22 Building pad ] , 175' south, 35' east from 6" 2 31.7 111.8 84.9 95 northwest corner, 1st lift Fill 23 Building pad 1, 175' south, 70' east from 6" 2 33.2 111.2 83.5 94 northwest corner, 1st lift Fill 24 Building pad I, 175' south, 110' east from 6" 2 31.8 111.9 84.9 95 northwest corner, 1st lift Test results on this report meet Project specifica tion. Technician: Joe Jernigan Started: I ; I Spm Fini shed: 3:30pm Ro ~ Report Distribution: / (11 Transwestem Commercial Services (1) Murray Construction Co, Ina '~-'" (])CitvofCoppell (1),4ztecEnvironmental ~ 'M1Chael COX, SET { 1;i City- of Coppell ~ Project Manager (1) Constructors ~ LIMITATIO'~S The test results presented herein were prepared based upon the specific samples provided for testins. We assume no responsibility for variation in quality lcomposition_ appearance, etc.) or an}~ other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. i'TIV1 Page 3 of 3 ~~~ 89(18 :ambassador Row, Dallas, "Tx 75247 7701 w. Little York, Suite 600, Houston, TX 77040 4231 Freidrich Lane, Suite 195, Austin, Tx 78744 Corporate Phone: (817) 284-1318 IN-PLACE DENSITY TESTING Client: Transwestern Corrnnercial Services Report No.: 278528 Mr. Ric Nelson Project No.: 0712786 Transwestern Commercial Services Date of Service: 02/13/2007 5001 Spring Valley Rd., Ste 600W Report Date: 03/15/2007 Dallas TX 75244 Project: Gateway Business Center Coppell, Texas Services: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA CONTRACTOR: Constructors & Associates Standard Counts Test Methods: Gauge: Troxler 3430 Moisture Density ASTM P-2922 ASTM D-3017 Gauge Serial No: 35518 Current: 745 Current: 2567 Test Mode: DT Previous: 740 Previous: 2562 MOISTURE DENSITY RELATIONS Maximum Project Requirements b1/D No. Description Moisture % Density pcf Moisture Density 1 Tannish Brown Silty Clay 24.5 93.5 Minimum +4 92-96 2 Dark Brown Clay 27.0 89.0 Minimum +4 92-96 TEST PROBE )vI/D MOISTURE VI'ET DENSITY' DRl' DENSITY DENSITY NO TEST LOCATION DEPTH No. (%) (pcf) (pct) (% max) Fill 1 Building pad 1, 25' north, 35' east from 6" 1 32.9 116.8 87.9 94 southwest corner, 10th lift Fill 2 Building pad 1, 25' north, 70' east from 6" 1 31.4 1 16.4 88.6 95 southwest corner, 10th lift Fill 3 Building pad 1, 25' north, 110' east from 6" 1 30.8 116.9 89.4 96 southwest corner, 10th lift Fill 4 Building pad 1; 75' north, 35' east from 6" 1 32.7 116.8 88.0 94 southwest corner. 10th lift LIMIT,4'I'IONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (compvsition_ appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over H~hich we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. ~7 rhl Page 1 of 2 EZeport No . ~7S~~8 ~~~ '~~~ Project No.: 0712786 Client: Trans«~estern Commercial Services TEST PNOBE NLD A1OISTURE 1y'E'T DENSITY DRY DENSITY DENSITY NO "LEST LOCATION DEPTId No. (%) (pcf) (pct) (% max) FiII 5 Building pad 1, 75' north, 70' east froth 6" 1 32.3 116.6 88.1 94 southw°est corner, l 0th lift Fill 6 Building pad 1, 75' north, l l0' east from 6" 1 32.4 116.5 88.0 94 southwest corner, 10th lift Fill 7 Building pad 1, 25' south, 35' east from 6" 2 35.5 1 14.5 84.5 95 northwest corner, 9th lift Fill 8 Building pad 1, 25" south, 70' east from 6" 2 36.1 114.6 84.2 95 north~~est corner, 9th lift Fill 9 Building pad 1, 25' south, 110' east from 6" 2 35.5 114.4 84.4 95 northwest corner, 9th lift Fill 10 Building pad 1, 75' south, 35' east from 6" 2 36.5 114.0 83.5 94 northwest corner, 9th lift Fill 11 Building pad 1, 75' south, 70' east from 6" 2 37.1 114.5 83.5 94 northwest corner. 9th lift Fill 12 Building pad 1, 75' sauth, 110' east from 6" 2 37.0 114.]. 83.3 94 northwest corner, 9th lift Test results on this report meet project specification. Ro e ' Technician: ,loe .lernlgan Started: 7;3~an1 Finished: 9:45a Report Distribution: Q) Transwestern Commercial Services (])Murray Construction Co, Inc. (])City of Coppell (1) Aztec Environmental ~`--~ ~ / M1Chael COX, FEZ' (1 i City of Coppell ~ Project Manager ~1 j Constructors LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality {composition, appearance, etc.j or any other feature of similar subject matter provided b} persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the v.~ritten approval of Rone Engineering Services, Ltd. 1?TR7 Page 2 of 2 . n~ nine~~in 8908 Ambassador Row, Dallas, TX 75247 7701 W. Little York, Suite 600, Houston, TY 77040 4221 Freidrich Lane, Suite 195, Austin, TX 78744 Corporate Phone: (817) 284-1318 IN-PLACE DENSITY TESTING Client: Transwestern Commercial Services Report No.: 278482 Mr. Ric Nelson Project No.: 0712786 Transwestern Commercial Services Date of Service: 02/12/2007 X001 Spring Valley Rd., Ste 600W Report Date: 03/15/2007 Dallas TX 7244 Project: Gateway Business Center Coppell, Texas Services: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA CONTRACTOR: Constructors & Associates Standard Counts Test Methods: Gauge: Troxler34~0 Moisture Density ASTM D-2922 ,ASTM D-307 7 Gauge Serial No: 35S 18 Current: 740 Current: 2560 Test Mode: l)"I~ Previous: 742 Previous: 2564 MOISTURE DENSITY RELATIONS Maximum Project Requirements IVt/D No. Description Moisture % Density pcf Moisture Density 1 Dark Brown Clay 27.0 89.0 Minimum +4 92-96 2 Tannisri Bro«~n Silty Clay 24.5 93.5 Minimum +4 92-96 'TEST PROBE M/D MOISTliRE WET DENSITY DRY DENSITY DENSTFY NO TEST LOCATLON DEPTH '_Vo. (%) (pci) (pct) (% max) Building pad 1 1 25' south. 70' east from northwest corner, 6" 1 31.7 112.1 85.1 96 7th lift Building pad 1 2 25' south, l ] 0' east from northwest corner. 6" 1 32.2 1 ] 1.7 84.5 95 7th lift Building pad 1 3 75' south, 35' east from northwest corner, 6" 1 31.8 111.1 84.3 95 7th lift Building pad 1 4 75' south. 70' east from northwest corner, 6" 1 31.9 11 L6 84.6 95 7th lift LIMTTAT[ONS: The test results presented herein were prepared based upon the specific samples p~~ovided for testine. We assume no responsibility for variation in quality (composition. appearance, etc.) or a~iy other feature of similar subject mater provided b} persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except m full without the written approval of Rone Engineering Services, Ltd. 17TH Page 1 of 2 F'roject'Vo.: 0 7]?786 Client: Transwestern Commercial Services ff-5r PROSI; NUD IYIOISTLRE WET DENSITY DRI' DENSITY DENSITY NO TEST IACATION DEPTH No. (%) (pci) (pct) (% max) Building pad 1 5 75' south_ 1 l 0' east from northwest confer, 6" 1 33.4 111.5 83.6 94 7th lift Building pad 1 6 25' north, 35' east from southwest corner, 6" 1 32.6 111.9 84.4 95 9th lift Building pad 1 7 25' north, 70' east from southwest corner, 6" 1 33.0 111.3 83.7 44 9th lift Building pad l 8 25' north. 110' east from southwest corner, 6" 1 30.7* 110.8 84.8 95 9th lift Building pad l 9 25' south. 35' east from northwest corner, 6" 1 32.2 110.9 83.9 94 8th lift Building pad ] ] 0 25' south, 70' east from northwest corner, 6" 1 31.7 110.6 84.0 94 8th lift Building pad 1 I 1 25' south. 110' east from northwest corner, 6" 1 31.8 111.2 84.4 95 8th lift Building pad 1 12 75' south, 35' east from northwest corner, 6" 1 33.3 I 1 ] .3 83.5 44 8th lift Building pad 1 l 3 75' south. 70' east fi-om northwest corner, 6" 1 31.5 110.7 84.2 95 $th lift Building pad 1 14 75' south. 110' east from northwest corner, 6" 1 31.4 111.4 84.8 95 8th lift. Building pad 1 15 Retest #6 from report #278441 6" 1 31.7 111.8 84.9 95 Building pad 1 16 Retest #8 this report 6" 1 31.8 111.1 84.3 95 Building pad 1 17 Retest #3 from report #278441 6" 1 35.5 114.5 84.5 95 An asterisk (*) appears next to test results which do NOT meet the project specifications. Technician: Joe Jernigan Started: 12:30p Finished: 3:151 Report Distribution: (1) Transwestern Commercial Services (I) Murray Construction Co, Inc. (1 j City of Coppell (1) Anec F,nvironmenfal (1) City of Coppell (1) Constructors LIMITAT]GNS: The test results presented herein were prepared based upon the specific samples provided for testing. V.%e assume no responsibility for variation in quality (composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. "TAI Page 2 of 2 ~~ 3908 Ambassador Row, Da)las, Tt 75247 7701 Pd. Little York, Suite 600, Houston, TX 77040 4221 Freidrich Lane, Suite 195, Austin, TX 78744 Corporate Phone: (8] 7) 284-1318 IN-PLACE DENSITY TESTING Client: Transwestern Commercial Services Report No.: 278386 1v9r. Ric Nelson Project No.: 07]2786 Transwestern Commercial Services Date of Service: 02/11/2007 5001 Spring Valley Rd., Ste 600W Report Date: 03/15/2007 Dallas TX 75244 Project: Gateway Business Center Coppell, Texas Services: Perform In-Place Density Test in accordance with AST?v1 Standards. PROJECT DATA CONTRACTOR: Constructors & Associates Standard Counts Gauge: Troxler 3430 Moisture Density 'Pest Methods: ASTM D-2922 AS 1'MD-3017 Gauge Serial No: 355]8 Current: 740 Current: 2560 Test Mode: DT Previous: 742 Previous: 2564 MOISTURE DENSITY RELATIONS Maximum Project Requirements M/D No. Description Moisture % Density pcf Moisture Density 1 Dark Brown Clay 27.0 89.0 Minimum +4 92-96 2 Tannish Brown Silty Clay 24.5 93.5 Minimum +4 92-96 TEST PROBE AI/D MOISTURE wET DENSITY DRY DENSITY DENSITY NO TEST LOCATION DEPTH No. (%) (pcf) (pct) (% max) Fill 1 Building pad 1, southwest comer. 25' north, 6" 2 3 ] .7 116.7 88.6 95 35' east, 6th lift Fill 2 Building pad 1, southwest corner, 25' north, 6" 2 32.2 116.1 87.8 94 70' east, 6th lift Fi^ 3 Building pad 1, southwest corner, 25' north, 6" 2 34.4 116.8 86.4 93 1.10' east. 6th lift Fill 4 Building pad 1, southwest corner, 75' north, 6" ~ 33.2 1 16.7 87.6 94 35' east, 6th lift LIMITATIO'_vS: The test results presented herein were prepared based upon the specific samples provided for testing. w'e assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full ~n~ithout the written approval of IZone Engineering Services, Ltd. 7TM Page 1 of 2 €~eport No.: ?7b386 ~,~,..4~, <..; Project No.: 071276 Client: Transwestern Commercial Services TF,ST PROBE M/D MOISTliRE N'ET DENSITI' DRY DENSITY DENSITY NO TEST LOCATION DEPTH No. (%) (pct (pcf) (% max} Fill 5 Building pad i, southwest corner, 75` north, 6" 2 33.7 116.7 87.3 93 70' east, 6th lift Fill 6 Building pad 1, southwest corner_ 75' north, 6" 2 32.4 116.8 882 94 110' east, 6th lift Fill 7 Building pad 1, northwest corner, 25' south.. 6" 2 32.5 116.5 87.9 94 35' east, 5th lift Fill 8 Building pad 1, northwest corner, 25' south, 6" 2 33.7 1162 86.9 93 70' east, 5th lift Fill 9 Building pad l ,northwest corner, 25' south, 6" 2 31.3 116.1 88.4 95 110' east. 5th lift Fill 10 Building pad 1, northwest corner, 75' south, 6" 2 31.6 116.6 88.6 95 35' east, nth lift Fill 11 Building pad 1, northwest corner, 75' south, 6" 2 32.1 117.3 88.8 95 70' east. 5th lift Fill 12 Building pad I, northwest corner, 75' south, 6" 2 31.5 116.9 88.9 95 110' east. 5th lift Test results on this report me et project specification . ,~ Technician: ,loe ,lernigan Started: l :00pm Finished: ~:OOpm Rone Report Distribution: % ~~ (lj Transwestem Commercial Services (]) 1vlurray Construction Co lnc i ' , ~ ~ (l j City of Coppell (1 j Aztec Environmental ~, 1Chae1 ~ COX, SET (7) City of Coppell / Projecf Manager (1) Constructors L1MIT.-~TlONS: The test results presented herein were prepared bated upon the specific samples provided for testing. we assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided b~~ persons or conditions over which we have no control Our letters and reports are for the eadirsive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Kone Engineering Services, Ltd. ~TT~I Page 2 of 2 8908 Ambassador Row, Dallas, TX 15247 "701 W. Little York, Suite 600, Houston, Tk 77040 x221 Freidrich Lane, Suite 19~, Austin, TX 78744 Corporate Phone: (817) 284-1318 IN-PLACE DENSITY TESTING Client: I'ranswestern Commercia] Services Report No.: 278384 Mr. Ric Nelson Project No.: 0712786 Transwestern Commercial Services Date of Service• 02/11/2007 5001 Spring Valley Rd., Ste 600W Report Date: 03/15!2007 Dallas TX 75244 Project: Gateway Business Center Coppell, Texas Services: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA CONTRACTOR: Constructors & Associates Standard Counts Test Methods: Gauge: Troxler 3430 Moisture Density ,ASTM D-2922 ASTM D-3017 Gauge Serial No: 35518 Current: 740 Curreut: 2560 Test Mode: DT Previous: 742 Previous: 2564 MOISTURE DENSITY RELATIONS Maximum Project Requirements M(D No. Description !17oisture % Density pcf Moisture Density l Dark Brown Clay 27.0 89.0 Minimum +4 92-96 2 Tannish Brown Silty Clay 24.5 93.5 Minimum +4 92-96 TEST NO TEST LOCATION PROBE DEPTH M/D MOISTURE No. (%) WET DENSITY DRY DENSITY (pct) (pcf) DENSITY (% max) Fill 1 Building pad 1, southwest corner. 25' north, 6" 1 35.5 1 14.5 84.5 95 35' east, 5th lilt Fill 2 Building pad l ,southwest corner_ 25' north, 6" 1 36.1 114.6 84.2 95 70' east. 5th lift Fil l 3 Building pad 1, southwest corner. 25' north, 6" 1 35.5 114.4 84.4 95 110' east. 5th lift Fill 4 Building pad 1, southwest corner. 75' north, 6" l 36.5 l 14.0 83.5 94 35' east. 5th lift LIMITATIONS: The test resulu presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.l or anp other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. "T1I Page 1 of 2 ~port No.: _-'`8 X84 'rojeet No.: O~12?86 Client: Trans~a~estern Commercial Services ,.`~~~~ ,~~_ TEST PROBE M/D A1OISTCRE ~0'ET DENSITY DRY DENSITY DENSITY NO LEST LOCATION DEPTH No. (%) (pci) (pct) (% max) Fill 5 Building pad 1, southwest corner, 7.5' north. 6" 1 37.1 114.5 $3.5 94 70' east. 5th lift Fill 6 Building pad 1, southwest corner, 75' north, 6" 1 37.0 114.1 83.3 94 1 10' east, 5th lift Fill 7 Building pad 1, northwest corner, 25' south, 6" 1 35.5 110.7 81.7 92 35' east, 4th lift Fill 8 Building pad 1, northwest corner. 25' south, 6" 2 32.4 118.6 89.6 96 70' east, 4th lift Fill 9 Building pad 1, northwest corner, 25' south, 6" 2 29.4 115.0 88.9 95 110' east, 4th lift Fill 10 Building pad 1, northwest corner, 75' south, 6" 2 28.8 115.7 89.8 96 35' east, 4th lift Fill ] 1 Building pad 1, northwest corner.. 75' south, 6" 2 29.7 1 ] 5.6 89.1 95 70' east, 4th lift Fill 12 Building pad 1, northwest corner, 75' south. 6" 2 28.5 115.5 89.9 96 110' east, 4th lift Test results on this report me et project specification. Rone Technician: Joe Jen~igan Started: 7:30am Finished: 9:30am Report Distribution: (1) Transwestem Commercial Services (1 j Murray Construction Co, Inc. ' Q) City of Copped (I } ,-1~tee Em~ironmenta] ~~,_~-~~ Michael COX, SEZ' (1 j City of Coppell Project Manager (1) Constructors `~ ~~ / LIMITA'1-IONS: The test results presented herein were prepared based upon the specific samples provided for testing. ~~e assume no responsibility for variation in quality {composition. appearance, etc.) or any other feature of similar subject matter proti~ided by persons or conditions over which we have no control. Our letters and reports are for the exclusi~~e use of the clients to whom they are addressed and shall not he reproduced except in full without the written approval of Rone Engineering Sen-ices, Ltd. -TA1 Page 2 of 2 " ~~~r~ 1=~:. 8408 Ambassador Roy+, Dallas, T~ 77247 7701 W. Little York, Suite 600, I~ouston, Tl 77040 4221 Freidrich Lane, Suite 195, Austin, TX 78744 Corporate Phone: (817) 284-1318 IN-PLACE DENSITY TESTING Client: Transwestern Commercial Services Report No.: 278441 Mr. Ric Nelson Project No.: 0712786 Transwestern Commercial Services Date of Service: 02/12/2007 5001 Spring Valley Rd., Ste 600W Report Date: 43/15/2007 Dallas TX 7244 Project: Gateway Business Center Coppell, Texas Services: Perform In-Place Density Test in accordance with AS"1'_M Standards. PROJECT DATA CONTR4CTOR: Constructors & Associates Standard Counts Test Methods: Gauge: Troxler 340 Moisture Density .ASTM D-2922 ASTM D-3017 Gauge Serial No: 35~ 18 Current: 740 Current: 2560 'L'est Mode: D7 Previous: 742 Previous: 264 MOISTURE DENSITY RELATIONS )Maximum Project Requirements M/D Nu. Description Moisture "/o Density pcf Moisture Density l Dark Brown Clay 27.0 89.0 Minimum +4 92-96 2 Tannish Brown Silty Clay 24.5 93.5 Minimum +4 92-96 TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY NO TEST LOCATION DEPTH No. (%) (pcf) (pcf) (% max) Fill 1 Building pad 1, 25' north, 35' east from 6" 2 30.4 112.0 859 92 southwest corner, 7th lift Fill 2 Building pad 1, 25' north, 70' east from 6" l 31.8 111.9 84.9 95 southwest. corner. 7th lift Fill 3 Building pad 1, 25' north, 110' east from 6" 1 3 5.2 111.0 82.1 92 southwest corner, 7th lift Fill 4 Building pad 1, 75' north, 35' east from 6" 2 30.9 111.4 85.1 91 southwest corner, 7th lift LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar suhject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the «~ritten approval of Rone Engineering Services, Ltd. )7TM Page 1 of 2 report No.: ?%5441 ~~<< ..y .~ r._~_ ~;.~.~3.1;?v Project No.: 0713756 Client: Trans~~estern Commercial Services "TEST PROBE 111/D MOISTURE N'ET DENSITY DR Y DENSITY DENSITY !gip TEST LOCATION DEPTH No. (%) (pct (pcf) (% maz) 5 Fill Building pad 1, 75' north, 70' east from 6" 1 32.2 I 1 l .8 84.6 95 southwest corner, 7th lift 6 Fi^ Building pad 1, 75' north, 110' east from 6" 2 30.9 111.5 85.2 91 southwest corner, 7th lift 7 Fill Building pad 1, 25' south, 35' east from 6" 1 32.0 111.5 84.5 95 northwest corner. 6th lift 8 Fill Building pad 1, 25' south, 70' east from 6" 1 332 111.2 83.5 94 northwest corner, 6th lift Fill 9 Building pad 1, 25' south, 110' east from 6" l 33.2 111.2 83.5 94 northwest corner, 6th lift 10 Fill Building pad 1, 25' north, 35' east from 6" 1 32.8 111.4 83.9 94 southwest corner, 8th lift Fill 11 Building pad 1, 25' north, 70' east from 6" 1 32.4 111.5 84.2 95 southwest corner, 8th lift Fill 12 Building pad 1, 25' north, 1 10 east from 6" 1 32.9 111.0 83.5 94 southwest corner, 8th lift Fill 13 Building pad 1, 75' north, 35' east from 6" 1 31..3 110.8 84.4 95 southwest corner, 8th lift Fill 14 Building pad 1, 75' north, 70' east from 6" l 31.6 110.9 84.3 95 southwest comer, 8th lift Fill 15 Building pad 1, 75' north, 110' east from 6" 1 33.0 11 1.3 83.7 94 southwest corner, 8th lift 16 Fill Building pad 1, 25' south, 35' east from 6" 2 302 111.7 85.8 92 northwest corner, 7th lift An asterisk (*) appears next to test results which do NOT meet the project specifications. Technician: Joe Jernigan Report Distribution: (1) Transwestern Commercial Services (1) City of Coppell t ])City of Coppell (1) Constructors i~ Ro Started: $:p0am Finished: 10:30a (1) Murray Construction Co, Inc. (1) Aztec Environmental Michael Cox, SET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. ~\'e assume no responsibility for variation in quality (composition. appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. 'T114 Page 2 of 2 ~~~ 8408 Ambassador Row, Datlas,'I:X 75247 77011§'. Little S'urk, Suite 600, Houston, TN 77040 4221 Freidrich Lane, Suite 195, Austin, 1;Y 78744 Corporate Phone: (817) 284-1318 IN-PLACE DENSITY TESTING Client: Transwestern Commercial Services Report No.: 278372 Mr. Ric Nelson Project No.: 0712786 Transwestern Commercial Services Date of Service: 02/10/2007 5001 Spring Valley Rd., Ste 600W Report Date: 03/14/2007 Dallas TX 75244 Project: Gateway Business Center Coppell. Texas Services: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA CONTRACTOR: Constructors & Associates Standard Counts 'felt M1lethods: ASTM D-2922 Gauge: Troxler 3430 Moisture Density 4STM D-3017 Gauge Serial No: 35j1$ Current: 742 Current: 2564 Test mode: DT Previous: 744 Previous: 2566 MOISTURE DENSITY RELATIONS n4aximum Project Requirements M/D No. Description 19oisture % Density pcf Moisture Density 1 Tannish Brown Silty Clay 24.5 93.5 Minimum +4 92-96 TEST PROBI; M/D MOIS"TORE ~~'ET DENSITY DRY DENSITY DENSITY NO TEST LOCATION DEPTH No. (%) (pcf) (pc>) (% max) Fill 1 Building ], southwest corner, 25' north, 35' 6" 1 32.5 l 16.5 87.9 94 east, 3rd lift Fi 11 2 Building 1, southwest corner, 25' north. 70' 6" 1 33.7 116.2 86.9 93 east, 3rd lift Fill 3 Building ], southwest corner, 25' north. 110' 6" 1 32.4 116.5 88.0 94 east, 3rd lift Fill 4 Building 1, southwest corner, 75' north, 35' 6" l 32.3 116.6 88.1 94 east, 3rd lift Fill 5 Building 1, southwest corner, 75' north, 70' 6" 1 32.7 116.8 88.0 94 east. 3rd lift LIMITATIONS: The test results presented herein were prepared based upon the specific samp]es provided for testing. We assume no responsibility for variation in quality (composition. appearance, eta] or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. 'TAI ~ Page 1 of 2 i'roje~ct No.: 0%12?R~ Client: Trans~~~estern Commercial Sert'ices .~,. ,y TEST PROBE vl/D MOISTURE ~~1~ET DENSITY DRY DENSITY DENSITY NO TEST LOCATION DEPTH No. (%) (pcf) (pcf) (% mas) Fill 6 Building 1, southwest corner, 75'north, 110' 6" 1 30.8 116.9 89.4 96 east, 3rd lift Fill 7 25' south 35' northwest corner 1 ildi B 6" 1 31.4 116.4 88.6 95 , , , u ng east, 2nd lift Fill 8 Building 1, northwest corner, 25' south, 70' 6" 1 33.0 116.4 87.5 94 east, 2nd lift Fill 9 Building 1; northwest corner, 25' south, 110' 6" 1 313 116.1 88.4 95 east, 2nd lift Fill 10 Building 1, northwest corner, 75' north, 35' 6" 1 31.6 116.6 88.6 95 east, 2nd lift Fill 11 Building 1, northwest corner, 75' north, 70' 6" 1 32.1 117.3 88.8 95 east, 2nd lift Fill 12 Building 1, northwest corner, 75' north, 1 l0' 6" 1 31.5 116.9 88.9 95 east, 2nd lift Test results on this report meet project specification. Technician: Joe Jernigan Started: $:OOam Finished: 10:0 Report Distribution: (1) Transwestem Commercial Services (I) Murray Construction Co, Inc. (]) City ofCoppell (1) Artec Environmental (1) City of Coppell (1) Constructors LIMITAI7O'~S- The test results presented herein were prepared based upon the specific samples provided for testing. ~w'e assume no responsibility for variation in quality (composition, appearance, etc l or any other feature of similar subject marter provided by persons or conditions over v.-hick we have no control. Our letters and reports are for the exclusive use of the clients to whom the_5- are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. i'T'!4 Page 2 of 2