Service Star-LR070328 CONCRETE COMPRESSIVE STRENGTH TEST , Report Number: 94061329.0067 Service Date: January 3D, 2007 lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Batch Time: 9:07 AM Plant: 01 Supplier: Nelson Bros. Redi-Mix Truck No: 111 Ticket No: 173166 Mix I.D. No.: PD36AEA Water Added Onsite Before Test: 20 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Report Date: March 28, 2007 Project: Multi-Facility Concept (Firestone Store) SWC Hwy. 121 & MacArthur Blvd. Coppell, TX Project No.: 94061329 Sample Information Date Cast: January 30, 2007 Time: 10:00 AM Sampled by: Gregory C. Martin Weather Conditions: Cloudy Accumulative Yards: 30/230 Batch Size (cy): 10.00 Placement Method: Direct Discharge Sample Locations: Noted on sketch as 1 Placement Location: Pavement (See attached sketch.) Client: ServiceStar Design Group LLC Attn: Frank Malek 5670 Greenwood Plaza Blvd, Suite 300 Greenwood Village CO 80111 Material Information Specified Strength: 3500 psi @ 28 Days Test Slump, inches: Air Content, %: Concrete Temperature, OF: Ambient Temperature, of: Plastic Unit Weight, pcf: Result 5.00 4.0 52 48 144.6 Specification 3-5 4.5-7.5 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Laboratory Test Data Age at Maximum Compressive Test Load Strength (days) (Ibs) (psi) 7 121,730 4,300 28 162,570 5,750 28 160,850 5,690 Average (28 Days) 5,720 1 4 6.00 28.27 03/27/2007 56 175,050 6,190 Services _ Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Set No. 1 1 1 Specimen ID 1 2 3 Diameter Area (inches) (sq. inches) 6.00 28.27 6.00 28.27 6.00 28.27 Date Tested 02/06/2007 02/27/2007 02/27/2007 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 3 01-PDRIR01-Fulure Key CONCRETE COMPRESSIVE STRENGTH TEST ,; Report Number: 94061329.0067 Service Date: January 30, 2007 lrerracon 8901 Carpenter Frwy, Ste #1 00 Dallas, Texas 75247 (214) 630-1010 Client: ServiceStar Design Group LLC Attn: Frank Malek 5670 Greenwood Plaza Blvd, Suite 300 Greenwood Village CO 80111 Report Date: March 28, 2007 Project: Multi-Facility Concept (Firestone Store) SWC Hwy. 121 & MacArthur Blvd. Coppell, TX Project No.: 94061329 Sample Information Date Cast: January 30, 2007 Time: 12:00 PM Sampled by: Gregory C, Martin Weather Conditions: Sunny Accumulative Yards: 140/230 Batch Size (cy): 10.00 Placement Method: Direct Discharge Sample Locations: Noted on sketch as 2 Placement Location: Pavement (See attached sketch.) Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 11 :09 AM Plant: 01 Supplier: Nelson Bros. Redi-Mix Truck No: 104 Ticket No: 173183 Mix I.D. No.: PD36AEA Water Added Onsite Before Test: o Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, of: Ambient Temperature, oF: Plastic Unit Weight, pet: Result 7.00 * 3.0 * 53 46 146.2 Specification 3-5 4.5-7.5 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C 1064 ASTM C138 Laboratory Test Data * = Field Test Results do not meet project specifications. Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 02/06/2007 7 93,380 3,300 02/27/2007 28 157,200 5,560 02/27/2007 28 154,540 5,470 Average (28 Days) 5,520 2 4 6.00 28.27 03/27/2007 56 168,960 5,980 Services _ Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Set No. 2 2 2 Specimen ID 1 2 3 Diameter Area (inches) (sq. inches) 6.00 28.27 6.00 28.27 6.00 28.27 The tests were performed in general accordance with applicable ASTM, MSHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 3 01-PDRIR01-Fulure Key CONCRETE COMPRESSIVE STRENGTH TEST . Report Number: 94061329.0067 Service Date: January 30, 2007 lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: ServiceStar Design Group LLC Attn: Frank Malek 5670 Greenwood Plaza Blvd, Suite 300 Greenwood Village CO 80111 Report Date: March 28, 2007 Project: Multi-Facility Concept (Firestone Store) SWC Hwy. 121 & MacArthur Blvd. Coppell, TX Project No.: 94061329 Sample Information Date Cast: January 30, 2007 Time: 2: 15 PM Sampled by: Gregory C. Martin Weather Conditions: Sunny Accumulative Yards: 210/230 Batch Size (cy): 10.00 Placement Method: Direct Discharge Sample Locations: Noted on sketch as 3 Placement Location: Pavement (See attached sketch.) Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 12:51 PM Plant: 01 Supplier: Nelson Bros. Redi-Mix Truck No: 218 Ticket No: 173200 Mix 1.0, No.: PD36AEA Water Added Onsite Before Test: o Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, of: Ambient Temperature, of: Plastic Unit Weight, pcf: Result 4.5 4.8 52 45 146.6 Specification 3-5 4.5-7.5 Test Method ASTM C143 ASTM C231 ASTM C 1064 ASTM C 1064 ASTM C138 Laboratory Test Data Age at Maximum Compressive Test Load Strength (days) (Ibs) (psi) 7 106,480 3,770 28 152,990 5,410 28 159,000 5,620 Average (28 Days) 5,520 3 4 6.00 28.27 03/27/2007 56 170,380 6,030 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Field Results Reported To: lei Superintendent Set No. 3 3 3 Specimen ID 1 2 3 Diameter Area (inches) (sq. inches) 6.00 28.27 6.00 28.27 6.00 28.27 Date Tested 02/06/2007 02/27/2007 02/27/2007 Terracon Rep: Gregory C. Martin Report Distribution: (1) ServiceStar Design Group LLC (1) City of Coppell TX (1) City of Coppell TX (1) ICI Construction Inc (1) ICI Construction Inc (1) Pate Engineers (1) ServiceStar Design Group LLC (1) Ratliff Group LLC Reviewed by: Lyndon J. Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 3 01.PORJR01.FuIure Key ,;$=t:,f~' ~ ..........."",.... Gt.. ~.,,",""~ ?\\) ^ ~'\ /'" .,: p.- d \ O~.),.....~ "\,j\S \ S I"~ "I'-. '~.,~' . ~J....'l'f-O\"cp:.......-.. ~\,..'O .....,/' \.'IJ p.: .../PROP. MONUMENT SIGH ............,-.- Sfr ARCH. PlANS ~,... "....<....'"'.".....:/;~~ /.. t..?~ /" .'" ..".; ;' *,,r""<'" ,< .....t. VISTA POINT II \ LOT 2, BLOCK A \ \ VISTA PIi)/NT II \ un 3, BUICK A \ \ \ ~ IS PROYlOEO rOR lNF'ORa.lAnClN ONLY. ALTHOUGH j SHO,*, AS ACCURAi lt1. Y AS POSSl'elE. 'THE: IS CAUTIONED J)-fA T 'fliE ENGINEER NEITHER -II; IMPU(S ~y RESPONSlIIUTY F'tft T1-tE f lHlS OATA. .., I. 8E RESPONSIBlE f'OR nELD VERIF'I1NG THE ~"'l1ON OF EXISTING P.....,NG AHO ununts ~~I- OF WA TEA MAINS. SEWER .....c CONTRACTOR SHAlL . "'4HOLES UPON "".G. -'O(Lt. (!iJ ~ \ \ -------- !O" N2:J'06'$7'W 11.49' ~ VISTA POINT II LOT 2, BLOCK A 5. THE PAVlNC CONTRACTOR SHAll. BE RE:QUfREO TO CONSlltVCT STANOARD SIDE WALK RAMPS AT AU. SlAtEr INTERsECnONs, 8. AU. SUIBIGRAOE SHAU.. BE UNlroRMLY COt.lPAClIO TO A MINIMUM OF' '115 PERCENT BY ASTY D698 STANOARO PROCTOR DENsITY AT 0,," TO +3" OF' OPm.tUM MOISTURE CONl[NT. IT SHOULD BE PROTECTED AND J.4AfNTAlN(O IN A MOIST CONDITION UNl1L lHE PAVEMENT IS PlACED. SEE CEOTECHMCAI. REPORT ISSOro F'Ofl litiS sm:. 7. ALL PA\1NG DIIrAENSlONS ARE TO rACE OF CURB UNl.(SS OlHE:AlIIS( NOtto. a. CONTRACTOR SHAU. SAWCUT ExISlINC PAVEMENT AND CURBS TO PROVIDE A SMOOni CONNECTION AND INSURE POSlllVE OAAlNAG!. AU. SAWCUTS OF EXlSTINC PAVEMENT SHAll. BE FIJU. OEPlIt Of PAVEMENT. g. All CONSTRucnON SHAU. AOHERE TO RECOMMENOA nONS IN THE CEOTECHrflCAI.. REPOftT ISSUED f'OR THS !IT( AS ~L AS . "liE Ory OF COPPEU. AND N.C. T.C.O.G. STANDARDS.' "'Ut'.CII>>' ,..,....... "ROP. SIOEWALH''1tS or"'cr~o ON ~~~::btC:~~~Nf /:I1WNC / ( \. \ \ \ \ ~ ... -L; -- = D .( - - D " - ) ~ ~ ~ " ':J/:'~' ,.....-~....., ~ <"\ \- PROP. OVMP~!!!!,.Ro;'" _) --/ l'if'rn CNa.OS.".,<:. ...-' ).Y{' Waler \"11\'., (S.U :; ARG"'ttC1VRAI. \ ';ater V'JI_ PYI<($'''OR rXAc;r S'l( tt\ ,,,.,.-'1< ..AmI,Al.S) ln~~''''''' H,.1r.lr,l I-.!JO -:J.LJo7 . TERRACON REPORT NO.. qJ./{) 10132/1. tJ(J' 7 .-' v \ VISTA POINT II LOT 5, BLOCK A \ 1 (lJ ~",p)e. ~<.P, @ PI,.lL(i\l"- ~ Ar <l'1 Ie. CONTRACTOR IS TO REFER To GEOTECHNICAl REPORT FOR PAVING AEQUI'REMENTS OR an OF COPftW.. STANDARDS 'MiATE\fER IS MOAE STRINGENT. CONTRACTOR 1$ RESPOHSI8lE FOR FOlLOWIHG ALL CONSTRUCnON REQUlREI/(NlS PROI/lOEO .. lHE ClOTtCJ<NICAL REPORT. IN litE EVENT OF' A CONF'UCT Il€T"olmI lHE ClOTtCl<NICAI.. REPORT AND THESE PlNfs. CONTRACToR SHALl. IMMEDIATn.Y CONTACT [NctNE[R BEFORE PROCEEDING WITH CRAOtNC OR PAVlNC AClIVlTlES. 10. CONmllCTOR SHAll. TAKE SPEOAL CARE TO ASSURE PROPtR DOWEL PlACEMENT AT EXPANSION JOINTS. IMPROPER PlActMENT WIll NECESSITATE RDotOVAl OF PAVEMENT. 11. SAwtUT11NG SHAlL BE DONE WlTHN EIGHT HOURS Of' POUR OR AS SOON AS CONCRETE CAN SUPPORT WEICHT ANO CAN PROVIDE A. NEAT CUT Mot IS TRUE IH AUGNMENT. I Z. lHE CONTRACTOR SHALL PROVlOE AS-8VIL T PlANS TO lHE ENClNEER SO lHA T litE ENGIIlEERINO PlANS MAY 8E REVlSEO TO REFlEtT AS-BUILT CONOInONS. IJ. AlL SPOT GAAO(S RUlECT TOI' Of PAY(M[NT (CUTT€R) EILVAT1ONS, UNlESS OlHER"'S( NOtto. 14. ALL CURB SHAlL BE S" INTEGRAl.. CONCRETE CURB UNLESS OTHERWISE NOlED. IS. CONCRETE SHALL CONTAIN A MIIIIMU"" OF II:t I." PERCENT ENTRAINED AIR. R(JNF'ORCING SHAU BE NO. J QlARS ON' IS-INCH CENTER IN QlOllt OIRECMNS (MIN). PRO~CT GEOTtClHCAl ENGINEER: HSC/IEARACON 8901 CARPENTER FREEWAY. SUITE 100 QAl.l.AS. lEXAS 7"247 PH: (214)OJO-l010 CONlAn RALPH B. BARNES. JR.. P.E. REPORT NO. 940Jo5341