Looking at the code, NFPA 13 - Installation of Fire Sprinkler Systems, only one check valve is required
within the FDG line. The common practice is to install this check valve on the inside of the building, where
it is visible and accessible. A ball drip valve is required at the 90 at the base of the FDG. My opinion and
preference would be that we discontinue the installation of the additional check valve in the underground
portion of the FDG...the Fire Department will insure the check valve is installed inside at the FDG
connection to the sprinkler system.