Loading...
CF-Justice Center-LR070207 Concrete Compression Test Report eM J ENGINEERING, INe. 7636 Pebble Drive Fort Worth, Texas 76118 Tel: (817) 284-9400 Fax: (817) 589-9993 Client: Project: Harrison, Walker, & Harper Police and Fire Renovation City of Cappel! Report Distribution: (1) Harrison, Walker, & Harper (1) City of Coppell (1) Brinkley Sargent Architects (1) Structural Engenuity (1) Teague, Nail, & Perkins (1) City of Coppell CMJ Report No.: 875-6111-058 Report Date: 02/07/2007 55" F min 950 F max n/a Placement Date Sampled By Weather Supplier/Mix Air Content Method Test Data 01/29/2007 Jonathan Hubbard Overcast/Mild Wind Redi Mix/724 ASTM C231 Strength Slump Air Content Concrete Temperature Ambient Temperature Specifications 3000 psi @ 28 Days 3 in min 5 in max 4 % min 6 % max Ticket Number: Slump: Concrete Temperature: Placement Location: 59001130 Time Batched: 11:18 Time Sampled: 12:15 Air Content: 4.2 % Unit Weight: N/A Ambient Temperature: 520 F Yardage (c.y.): 5 of 10 Approach to South Main entry starting at South Drive; Access Ramp: running North to 5.5 in* 500 F* Sample Location: Fire Station Sidewalk: South Door 30' Fire Station Sidewalk: Approach to South Main entry starting at South Drive; Access Ramp: South Door 30' running North to An asterisk (*) appears next to field data which does NOT meet specifications. Concrete Compression Test Results Cylinder Age Max Load Area Set# # Test Date (days) (Ibs. force) (sq.in.) 01 CPF01290701 02105/2007 7 89400 28.27 01 CPF01290702 02/26/2007 28 01 CPF01290703 02/26/2007 28 01 CPF01290704 Hold Stren,gth (pSI) 3160 Fracture Type D-shear Normal cylinder size: 6" x 12" Field and laboratory tests by CMJ are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231. * Non-Compliant: Contractor Notified o Gallons of Water Added On-Site CMJ Engineering, In LIMITATIONS: The test results presented in this report apply only to the specific samples, items, and areas described within this report. The test results do not pertain to any other samples, items or areas regardless of similarity. Our reports are produced solely for the exclusive use of our client. This report or any portion of this report may not be reproduced without the written consent of our client and CMJ Engineering, Inc. 01 Page I of I