Report of In-Place Density Testing
Report No.: 288564
Project No.: 0712786
Date of Service: OS/24/2007
Report Date: 06/25/2007
Project: Gateway Business Center
Coppell, Texas
Services: Perform In-Place Density Testing
PROJECT DATA
Contractor: Constructors & Associates
Test Method: ASTM 0-2922
ASTM 0-3017
Gauge: Troxler 3430
Gauge Serial No: 34008
Test Mode: DT
Standard Counts
Moisture Density
Current: 643 Current: 2600
Previous: 652 Previous: 2631
MOISTURE DENSITY RELATIONS
MID No.
277809
277811
Description
Moisture
%
Maximum
Density
(pet)
89.0
94.0
Project Requirements
Moisture Density
Optimum +4 95 minimum
Optimum +4 95 minimum
Dark Brown / Clay
Tannish Brown & Dark Brown / Silty Clay
27.0
24.0
FIELD DENSITY TESTS
Test Probe MID Moisture Wet Density Dry Density Density
No Test Location Depth No. % (pet) (pet) (% max)
Paving subgrade
Parking lot north of Building 2, 70' north, 175' 6" 277811 21.9* 119.6 98.1 104
east from northwest corner, subgrade
Paving subgrade
2 Parking lot north of Building 2, 200' north, 190' 6" 277809 35.2* 117.5 86.9 98
east from northwest corner, subgrade
Paving subgrade
3 Parking lot north of Buildikng 2, 190' north, 70' 6" 277809 36.3 * 115.3 84.6 95
east from northwest corner, subgrade
Paving subgrade
4 Parking lot north of Building 2, 90' north 30' 6" 277811 30.8* 119.2 91.1 97
east from northwest corner, subgrade
Paving subgrade
5 Parking lot north of Buidling 2, 110' north, 350' 6" 277809 36.1 * 114.5 84.1 95
east from northwest corner, subgrade
An asterisk (*) appears next to results which do NOT meet the project specifications.